  • Working on this Carrier rooftop unit, in a commercial HVAC application, and found that the flame was rolling out, what caused this flame roll out condition? The video goes through some HVAC troubleshooting steps in order to find the problem.
    Check out Jobber getjobber.com/hvacknowitall
    Save 8% on your purchase at www.trutechtools.com/ with promo code knowitall
    Check out the HVAC Know It All app app.hvacknowitall.com
    www.hvacknowitall.com/pages/a...
    Visit HVAC Know It All on social media
    Facebook
    / hvacknowitall
    Instagram
    / hvacknowitall1
    #flamerollout #heatingrepair #carrierrooftop
  • Auta a dopravní prostředky

Komentáře • 63

  • @HVACKnowItAll
    @HVACKnowItAll  Před rokem +11

    Hop this helped those learning

    • @P9rkour90
      @P9rkour90 Před rokem +1

      So jobber has really helped you ? I’d love to do this

    • @HVACKnowItAll
      @HVACKnowItAll  Před rokem

      @@P9rkour90 yes 100%, very easy to use and great support on the product

  • @tylerlockwood2976
    @tylerlockwood2976 Před rokem +7

    A friendly suggestion is to pull that heat exchanger door below the blower. I have found about 12 in the past year with the infamous carrier crack where the tubes have been pressed in place.
    Not a giant safety issue but shouldn’t go left un checked

  • @kyle-yq1rb
    @kyle-yq1rb Před rokem +2

    Those model carriers are so common , I often see the heat exchanger plate where the inducer motor and burners mount on absolutely rusted. And the doors always bent with tappers everywhere lol

  • @bassmaster2009
    @bassmaster2009 Před rokem

    Dude what a helpful vid this is, i would have spent hours and might not have figured out why the flame was rolling out.

  • @mikeclark1756
    @mikeclark1756 Před rokem +2

    Great Video Gary.

  • @LongTrout
    @LongTrout Před rokem +1

    I love this video channel. Makes me miss my service in the field

  • @jamesladeroute6380
    @jamesladeroute6380 Před rokem +1

    Good catch Gary. Well done! Keep it up brother.

  • @syedimam8328
    @syedimam8328 Před rokem +1

    More videos like this man. They help a lot !

  • @Eric_5475
    @Eric_5475 Před rokem +2

    Super helpful. Thank you Gary.

  • @LongTrout
    @LongTrout Před rokem +1

    Slow Rolling draft motor. Changed my diagnosis about 5 seconds later considering the amperage draw on the motor

  • @stevencossaboon3237
    @stevencossaboon3237 Před rokem +1

    Yes your videos help a lot Gary. I hope you are doing well.

    • @HVACKnowItAll
      @HVACKnowItAll  Před rokem +1

      I appreciate that, doing well here. I hope the same for yourself

  • @drewc7479
    @drewc7479 Před rokem

    Still remember my very first service call alone , had the exact same problem. New lennox tripping on roll out . Gas pressure was never set and ventor was on it's way out

  • @rahimshah9981
    @rahimshah9981 Před rokem

    Dear Sir,
    I like you're all descution . and also andrusteand well . because you're english verey simple .anyone cen learn from you. Thenks

  • @l.crossjr
    @l.crossjr Před rokem +2

    Quality content. Congratulations

  • @markshipley1532
    @markshipley1532 Před rokem +1

    Nice catch with the amp draw.

  • @RC-Heli835
    @RC-Heli835 Před 3 měsíci

    Great job man!
    When is a furnace old enough that you cant recommend using it any longer?

  • @ramirabee3717
    @ramirabee3717 Před rokem +1

    Great video. Thank you

  • @JuanGomez_
    @JuanGomez_ Před rokem +1

    Awesome video I learned something

  • @Garcia112
    @Garcia112 Před rokem

    Nice!!! Good job

  • @Nba19980
    @Nba19980 Před rokem

    Thx primo content

  • @ori4640
    @ori4640 Před rokem +1

    It's clearly the combustion fan motor, why do you recommend replacing the gas valve, In my opinion, the gas valve is working and there is no need to replace it. thanks for sharing your videos.

    • @jasongoertzen
      @jasongoertzen Před rokem +1

      Because the gas pressure can't be adjusted.

    • @HVACKnowItAll
      @HVACKnowItAll  Před rokem +1

      As I mentioned the gas pressure is high, the caps to adjust are seized and stripped.

  • @kaylalee20201
    @kaylalee20201 Před 13 dny

    Nice video

  • @gwonminsu
    @gwonminsu Před 4 měsíci

    Did it work well after changing the gas valve and Inducer motor???

  • @Almtyhalfbreed
    @Almtyhalfbreed Před rokem +1

    Did you get video on diagnosing this rtu?

  • @mayburnwright3434
    @mayburnwright3434 Před rokem +2

    Hey we put it American standard 3 ton propane gas pack residential unit at a house in 2019 that was early spring. We went back out there in the fall of 2020 and found the rollout tripped and found the inducer motor was covered in Suet. Gas pressure was at 10.5. Talk to the tech support of Team Air and had a technician come out we reduced the gas pressure to 9. Check to make sure they gave us the right LP kit and replace the regulator. After a week it did it again so we swapped the whole unit for a brand new one. Went back out there this past week and it’s doing the exact same thing and the inducer motor and heat exchanger was clogged. Could you please help me with this call. Any information would be great from all technicians. I went out there Wednesday and replace the inducer motor and heat exchanger. Now I’m just waiting for it to do that again.

    • @HVACKnowItAll
      @HVACKnowItAll  Před rokem +2

      Has anyone put a combustion analyzer on it. Start there.

    • @jaymz0074
      @jaymz0074 Před rokem +1

      Does the lp furnace have a low gas pressure safety shutoff? Silly question I know but you could be dropping pressure.

    • @aaronga90
      @aaronga90 Před rokem +1

      @@jaymz0074 I'm with you brother. Running the furnace till tank is empty will kill the unit without a low gas pressure safety

  • @gingerstrand6153
    @gingerstrand6153 Před rokem +1

    Hey, great video. When you say you sub-contract, you bill the contractor or the business?

  • @LongTrout
    @LongTrout Před rokem

    My first guess at 4 minutes and 43 seconds is broken blades on the inducer fan wheel.

  • @keaters123
    @keaters123 Před rokem +1

    Gas valve caps are seized and stripped ? By another tech or was it built like that?

    • @HVACKnowItAll
      @HVACKnowItAll  Před rokem +1

      Stripped by another tech, seized due to corrosion

  • @allentraylor5659
    @allentraylor5659 Před rokem +1

    So, is the roll-out sensor , shutting the unit down ??
    Or do roof-top units not have them??

    • @HVACKnowItAll
      @HVACKnowItAll  Před rokem

      Rooftops have them, the gas off when I got there, so I don't know if it went off on roll out prior

    • @joeychops
      @joeychops Před rokem

      Any fuel fired unit, ducted or not, has at least one roll out switch in the burner section, not uncommon to even have 2.

    • @allentraylor5659
      @allentraylor5659 Před rokem

      @@joeychops
      Thanks for that.......I don't think I fully understand why the flame rolled back, if the exhaust duct isn't clogged

  • @stephwaylonwells3218
    @stephwaylonwells3218 Před rokem +1

    👍

  • @iamdjnam
    @iamdjnam Před 6 měsíci

    Mine did this and lit the unit on fire. Melted all the wires.

  • @Airman93
    @Airman93 Před rokem +1

    Opening part of the video gas valves off

    • @HVACKnowItAll
      @HVACKnowItAll  Před rokem

      ? The flame is rolling out, the gas valve is not off

  • @Dahvacman100
    @Dahvacman100 Před rokem

    I had a 70% furnace burn my mustache off I was up close at the burners and soon as that blower came out a ball of fire shot out at my face as we was demoing it we came across a massive hole in the heat exchanger

  • @aaronga90
    @aaronga90 Před rokem

    The reason why is just the fact that it is a CARRIER lol

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Před rokem +1

    Great video Gary.