Will a furnace with a blocked vent cause a flame rollout

Sdílet
Vložit
  • čas přidán 15. 06. 2024
  • This one tests whether a vent blockage will cause a flame rollout or the pressure switch will shut down the burners.
  • Jak na to + styl

Komentáře • 109

  • @MSxLoNeWoLf
    @MSxLoNeWoLf Před 4 lety +5

    Crossovers between burner 1 and 2 seemed show show some rollout after blower startup. But seeing that , I normally double check the 5/16s screws holding the clamshell to the front plate. When loose will allow blower air to hit the burners. Enjoy your vids.

  • @renj6531
    @renj6531 Před 5 lety +6

    i like the fact that you dive into the experimental/ scientific aspect of HVAC like what if cases, vs simple repair vids.

  • @michaelc2765
    @michaelc2765 Před 4 lety +4

    Had a call last night on a gas package unit on the side of the house. The roofing company just replaced the roof and put a tarp over the package unit and blocked the exhaust vent which made the flame rollout and trip the rollout switch. After resetting the switch I watch the flames for 30 minutes and checked for carbon monoxide everything was good. Point being in my opinion a blocked exhaust will cause the flames to rollout and trip the rollout switch.

  • @TheGhettoLobster
    @TheGhettoLobster Před 5 lety +2

    On Rheem condensing furnaces I've seen flame rollout due to one models Inducer tranistion tees had a restrictor inside to slow down the flue gas. Rheem did this to gain an extra 1% efficiency. In some conditions it causes the flames to rollout back out into the burner box and either trip the rollout or burn up the rollout wires.

  • @alfredo4956
    @alfredo4956 Před 5 lety

    Your like the new and improved Dr zarkloff. New subscriber here!

  • @MsFishingdog
    @MsFishingdog Před 5 lety +1

    great video. very helpful.

  • @ahmedalshakarchi6076
    @ahmedalshakarchi6076 Před 5 lety

    Very helpful, thanks for this great video

  • @kaboom362
    @kaboom362 Před 4 lety +1

    Just did a Reno and the ductwork needs to change but I was wondering if it could run for temporary heat. Maybe till the spring

  • @uxwbill
    @uxwbill Před 5 lety +2

    Somehow I thought I'd commented on this video. I tried something similar on a 98% efficient Bryant furnace in the classroom, just to see if I could starve it of enough air to trip the pressure switches. At the time, the idea of a flame rollout possibly taking place never occurred to me. Although I didn't kick it up to the second stage, nothing I could do to the combustion air intake would get it to stop running.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      What is being attempted here is not reducing combustion air but blocking vent gas from exiting the furnace.
      GFM

    • @JPTinioMedia
      @JPTinioMedia Před 4 lety

      @@grayfurnaceman Blocking the flue pipe on a high efficient furnace the board won't let it run if its blocked.

  • @jphvac5725
    @jphvac5725 Před 5 lety

    Have has roofers cut thru the double walled Y style pvc pipe at the roof line. Obviously the exhaust and vent weren’t separated correctly afterward. Pressure switch killed it everytime unless I held it in correct place.

  • @reygomezhvac8346
    @reygomezhvac8346 Před 5 lety

    Its hard to stop a trane. Unless theres a bird in the flue. Good video this is something i will keep an eye out from now on.

  • @yavuzc
    @yavuzc Před 2 lety +1

    Yes, it does. My 4th burner (lowest) and eventually 3rd burner was choking and going off after 10-20 seconds and flame sensor was turning the furnace down. I detached the vent in the attic for a short test and it recovered back. Other furnace was fine so gas pressure was ok. I had my roof done recently and gas caps were replaced. Likely that they pushed it way too much, I called the guys and they will come/check.

    • @grayfurnaceman
      @grayfurnaceman  Před 2 lety +1

      They do sometimes push them down far enough to block it off.
      GFM

    • @haywardkong1213
      @haywardkong1213 Před rokem +1

      Why not get a twist and lock cap? Recently, I have to replace furnace vent since the original builders of the house did a poor job and never really secured the very top 4 foot of the furnace vent. It was never twisted and locked and was secured by vent lead flashing for Spanish tile. So after about 14-15 years it rip away and blow off the 2nd level roof. When inspecting the furnace one day during the summer noticed that I can see light outside. Ended up replacing about 5 foot of the B-vent with home depot brand and ordered online a twist and lock b-vent cap that matches up with the same home depot b-vent brand. Also replaced the the rip up lead flashing.... I shortened the b-vent by a foot since current city regulations allowed it. It's just funny in this time and age that there are no industry standard for twist and lock for b-vent. You have to keep with the same brand or have some kind of adapter for different brand of b-vents.

  • @geojor
    @geojor Před 5 lety

    very good, thank you ...

  • @moparerrnocar
    @moparerrnocar Před 5 lety +3

    Both.. This is still a rollout condition, towards the end you can see that the crossovers are lifting (most notably the far left). I assure you if you let this labor for 20-30 min that burner box would trip a rollout. However it may not run that long b4 it faults on flame rectification or pressure switch. Now for a real world scenario, throw a gust of wind at it and its likely to trip the PS especially being that closs to the balance point.
    A newer furnace with dual reference points, one before combustion blower housing (collector box) and one within blower housing, makes this an even less plausible condition. Usually a partially plugged secondary or large breach in primary is the only thing that will allow heavy rollout and not fault a pressure switch. Also worth noting, shouldnt any termination going threw structure be class B, pretty unlikely for a cap to be pushed too far down on interlocking fitting.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      I will do a test of the longer operation. As for dual reference points, this is an 80% furnace. It does not use dual reference points. I may even try the wind gust.
      All 80% furnaces should be using B vent for the entire vent. But I would not guarantee that even with B vent, the termination could not be pushed down too far.
      GFM

    • @moparerrnocar
      @moparerrnocar Před 5 lety

      @@grayfurnaceman I dont know that its really worth the effort for something so trivial, either way there is no harm or danger in either outcome as one of the 3 safeties would cause suspect. I think a better use of your time may be in testing the flame characteristics vs unmetered air like we spoke about in your other video. As far as wind caps, the ones I'm familiar with spin and lock into place, making it impossible to goof. And correct, which is why I said newer furnaces with dual ref design.

    • @joshualucero6054
      @joshualucero6054 Před rokem

      This rose a red flag with me as well, time to start working this out after making this a proper installation. Then and only then can you actually be confident in your diagnostics. Trying to fix a leaning building with a trash foundation.

  • @christianlibertarian5488

    I had this exact issue at my house. Except it took 15 years, one replaced heat exchanger, and two new furnaces to figure it out. The issue, it appears, is a partial blockage. The inducer fan spins up at a relatively fast rate, then settles to a more normal rate. That creates the vacuum needed, and the flame will start. But, after a while, back pressure builds, and you get enough heat backing up that the rollout switch detects a rollout. No actual flame rollout is evident.

  • @Aztec6737
    @Aztec6737 Před 5 lety +1

    I just came across that exact problem on a new construction and sure enough I checked the vent on the roof and it was blocked by the cap

  • @ericdiefel4505
    @ericdiefel4505 Před 3 lety

    I see this quite a bit where the Roofer pushes down the Vent cap. Most of the time a water heater is "Y" into the vent. So the furnace exhaust pushes out the water heater hood. These roofers could kill someone with CO poisoning. Plus, the condensation at the venting seams is a dead giveaway

    • @grayfurnaceman
      @grayfurnaceman  Před 3 lety

      I have seen that too. I think they just don't understand how that cap works.
      GFM

  • @johncote2776
    @johncote2776 Před 5 lety

    What's the Carbon monoxide reading at the burners?

  • @jeffpeterson1331
    @jeffpeterson1331 Před 5 lety +1

    I think it would be interesting to see at what point the pressure switch WOULD drop the burner out. It got as high as -.45 which I would have though would drop out the burner.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      If it got below .4, it shut down the burners. The point of this exercise was to determine if there was a point that the pressure switch would stay closed and the flame would rollout.
      GFM

  • @HighVoltageMadness
    @HighVoltageMadness Před 5 lety +1

    Please do a co/combustion test on a furnace with this condition!

    • @metx9915
      @metx9915 Před 3 lety

      That will be a good idea see the Ppm s. With a combustion test.

  • @RayRay-nb7tn
    @RayRay-nb7tn Před 5 lety +1

    I had a bird block a vent and it was a concentric termination and had someone at the furnace and the flames did roll out it was a Bryant furnace.

    • @RayRay-nb7tn
      @RayRay-nb7tn Před 5 lety

      @Marco A yes they do but somehow it wasn't working.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety +1

      All furnaces have pressure switches that are expressly there to stop the cycle if the vent is not clear. Does not mean they always work as they should.
      GFM

    • @RayRay-nb7tn
      @RayRay-nb7tn Před 5 lety

      @@grayfurnaceman this is true.

  • @JuanTodoli
    @JuanTodoli Před 5 lety

    Good one.

  • @MrRondeezzee
    @MrRondeezzee Před 4 lety +1

    Sir I'm back, you helped me with my gas valve issue. Thanks you saved me 600 bucks. Now I'm back lol I'm getting 6 flashes on my Goodman and its says it's the flame rollout . My fans wont stop and the flame wont come on. How to fix?

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety +3

      This probably an open rollout switch. It is a manual reset switch probably located near the burners.
      However, resetting the switch is not a repair. It rolled out the flame for a reason. You could have a crack in the heat exchanger.
      Careful on this one. You may need a repairman.
      GFM

  • @CommonSenseFishing209
    @CommonSenseFishing209 Před 4 lety

    Also.happens all the time on a plugged secondary heat exchanger or plugged cva on high efficient unit.

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety

      You are correct. A blocked secondary heat exchanger will cause a rollout, but will not shut off the pressure switch. However, a blocked CVA will cause the firebox pressure switch to open.
      GFM

    • @uski
      @uski Před 3 lety

      @@grayfurnaceman What is a CVA ?

    • @grayfurnaceman
      @grayfurnaceman  Před 3 lety

      @@uski Combustion and ventilation air.
      GFM

    • @uski
      @uski Před 3 lety

      @@grayfurnaceman Thanks !

    • @grayfurnaceman
      @grayfurnaceman  Před 3 lety

      @@uski Welcome
      GFM

  • @Pablo1on1
    @Pablo1on1 Před 5 lety +3

    It look like a rollout flame,to me

  • @thelightninghunter23
    @thelightninghunter23 Před 5 lety +1

    If there is a water heater sharing the same vent, will a full blockage on the roof cause the furnace to malfunction? Or will the exhaust gases backfeed down the water heater exhaust and into the structure?

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety +1

      If there is a W/H on the vent, it will definitely backfeed. The result of this usually is the pilot light is extinguished. I look at this as a good result. The problem then is the tech that comes out for the water heater problem has to figure out it is not a problem with the water heater, but with the furnace venting.
      GFM

    • @mattkime7615
      @mattkime7615 Před 5 lety +1

      Yes it will come out the draft hood on the water heater.

  • @mattschamel6550
    @mattschamel6550 Před 4 lety

    Grayfurnaceman, I just cleaned my burner tubes and orifices on my furnace. I switched it on to test it, and when I shut it off, there are small flames at all five orifices. It has spark ignition, no pilot light. It's been off for almost 10 minutes and the small orange flames are still burning? It's an older, Weather King outdoor combo unit, and has a Honeywell regulator? Flow valve? Not sure what it's called. Any suggestions would be appreciated.

    • @mattschamel6550
      @mattschamel6550 Před 4 lety

      @@grayfurnaceman It wasn't doing this prior to cleaning the unit. I'm assuming there's no way to clean the valve if I accidentally got some crud in it? Also, I'm running lpg, if I buy a new valve set for natural gas, can I use the lpg conversion out of the old valve to convert the new one? It only regulates flow pressure, and doesn't function as a valve, correct?
      Thank you for your speedy response to my initial question.

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety +1

      @@mattschamel6550 It is a combination valve which means it provides regulation, safety shut down and solenoid valve. Any replacement valve must be designed for LPG.
      GFM

    • @mattschamel6550
      @mattschamel6550 Před 4 lety

      @@grayfurnaceman thank you, I appreciate your help.

  • @RockoRocko-rz7kx
    @RockoRocko-rz7kx Před 5 lety

    Because it’s not completely blocked and that inducer motor pulling 1inch wc and the pressure switch closing at 0.5. It may or may not open the switch and error off on safety. If the exhaust pipe was completely blocked it would have error out and the pressure switch would not have closed. If u look at the manometer it’s running 0.4 wc which is still within tolerance, thus it’s still running.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety +1

      The 1" wc is with a clear vent. I closed off the vent until the pressure would just barely close. The point of this exercise was to block the vent to the point that the pressure switch would barely close. If the flame then rolled out, there is a design problem with the furnace. The pressure switch is there to protect from this problem.
      GFM

    • @blackdog5560
      @blackdog5560 Před 5 lety

      Having a supplemental rollout switch is something that most furnsces have have down here in Oz for more than 20 years....AND perhaps pressure switch build qualitycould be tweeked somewhat?

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      The rollout switch became standard when induced furnaces were developed. The pressure switch on this unit operates within specs.
      GFM

  • @CommonSenseFishing209
    @CommonSenseFishing209 Před 4 lety

    At 4:27. Duh. It does roll out. But there isn't a roll out switch right there. That's your flame sensor on the left burner. Also.if the flue was partially plugged just enough for that pressure switch to stay closed for longer you would have seen that roll out again.

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety

      The unit was set so that there was just enough vacuum to keep the pressure switch closed. And again, that is not a rollout. It is a flame failure.
      GFM

  • @toneblair
    @toneblair Před 5 lety

    So what’s the conclusion? That the pressure switches and inducer are not working right? Or a blocked vent doesn’t matter? I bet on a wall furnace there would be rollout.
    I don’t know...

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      There is no exact conclusion. I will be doing this on more models of furnace to see if there is a difference with them. Actually a wall furnace with a draft hood will not rollout flame. The draft hood will spill.
      GFM

  • @eeelauj6431
    @eeelauj6431 Před 4 lety

    I know I have a issue with flame rolling over because I can see it, but it only does it when the fan kicks on? Can you point me in the right direction?

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety +2

      That is classic cracked heat exchanger. Either the heat exchanger or the furnace must be replaced. This is an unsafe condition. Possible CO poisoning.
      GFM

  • @throttlebottle5906
    @throttlebottle5906 Před 5 lety

    it's dancing and flickering enough on the cross overs it may eventually cause the roll-out switch to trip. but no guarantees.

  • @eddenson1
    @eddenson1 Před 4 lety

    Would you happen to know what model that furnace is. I have one just like it but I cannot find anywhere where it says the brand or model number.

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety

      Its a Goodman GMP080 from the middle 1990s.
      GFM

    • @eddenson1
      @eddenson1 Před 4 lety

      grayfurnaceman thank you so much!

  • @kaboom362
    @kaboom362 Před 4 lety +1

    How to wire a furnace and therostat?

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety +1

      The power wiring is straightforward. Black to black, white to white green to ground. Thermostat, R to R and W to W.
      GFM

  • @colonelradec5956
    @colonelradec5956 Před rokem

    theres a video on youtube of a blocked vent causing rollout. he went on roof moved it and it ran fine after.

    • @grayfurnaceman
      @grayfurnaceman  Před rokem

      Send me the link.
      GFM

    • @colonelradec5956
      @colonelradec5956 Před rokem

      @@grayfurnaceman czcams.com/video/fWC2smK9hvg/video.html thats the youtube vid link.

    • @grayfurnaceman
      @grayfurnaceman  Před rokem +1

      @@colonelradec5956 Thanks for the link. The furnace rollout did its job and shut down the burner when the temp got too high. I can't give a reason for the failure of the pressure switch. It should have shut down the sequence of operation before the burner came on.
      GFM

    • @colonelradec5956
      @colonelradec5956 Před rokem

      @@grayfurnaceman yea im no pro but i thought the same. seems like they don't always work? which is kinda sketchy lol.

  • @atch_n_sons
    @atch_n_sons Před 5 lety

    Would instead trip on high limit? I've seen roll out do to cracked heat exchanger, pressure switch issues with blocked flue.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety +2

      The limit should not open.
      GFM

    • @JoeLinux2000
      @JoeLinux2000 Před 5 lety

      I was thinking it may have tripped on the high limit switch, but his second test eliminated that thought as it ran much longer.

    • @atch_n_sons
      @atch_n_sons Před 5 lety

      I was thinking more about a true residential set up with return air. As the space nears set point, warmer air and a blocked flue, to me would go off on high limit

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      A blocked flue will not open the high limit.
      GFM

    • @JoeLinux2000
      @JoeLinux2000 Před 5 lety

      @@grayfurnaceman , Just curious, why do you believe that? I get that there is limited air flow, but the heat of the flame is close to the limit switch, at least on my older furnace, which I believe both opened and closed within a predetermined heat range. Modern furnaces probably have a limit switch that cuts out only above a set temperature.

  • @hvac1238
    @hvac1238 Před 5 lety

    It's a Janitrol, cant use a GMP to test any theory. I'd put my career on that there are rings voided on that thing which would effect draw readings also. Love the vids tho.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      The ht exchanger is intact on this one. No rings off.
      GFM

    • @hvac1238
      @hvac1238 Před 5 lety

      I'll quit tomorrow, good day.

  • @kaboom362
    @kaboom362 Před 4 lety +1

    Can a natural gas furnace be utilized without duct work.

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety +1

      It can be, however, the circulating fan may overdraw power without ductwork.
      GFM

    • @kaboom362
      @kaboom362 Před 4 lety +1

      @@grayfurnaceman Thank you so much for the reply. Any chance you could slap a video together? ?

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety

      I will see what I can do.
      GFM

    • @kaboom362
      @kaboom362 Před 4 lety

      @@grayfurnaceman I got her fired up today. . Ran it for a few Cycles. . Iran a manifold on the top and an air intake. I used the old stuff. Now I've just got to run some ductwork to the house. And we're in business. Thanks, brother. !

  • @johncote2776
    @johncote2776 Před 5 lety

    A low powered Inducer motor or failing inducer motor will cause flame rollout.

  • @EpicBenjo
    @EpicBenjo Před 3 lety +1

    My kid put a rock into the exhaust. Is that bad? I can't get it out.

    • @grayfurnaceman
      @grayfurnaceman  Před 3 lety

      If the furnace still works ok, its fine. If it stops and give a pressure switch fail, you will have to get it out.
      GFM

  • @brynduffy
    @brynduffy Před rokem

    I question how blocked that furnace flue was. Where is the heated gas going if the flue is blocked? Back out anyway it can.
    As with the first test, you saw rollout on the left burner which made perfect sense... but not on the second test. What changed?
    CZcams is often untrustworthy.

    • @grayfurnaceman
      @grayfurnaceman  Před rokem +1

      I am not making a conclusion here. The 2 tests were done back to back. The only difference was the furnace during the first test was cold. The second test had a warm furnace.
      What I do think is that with an almost totally blocked vent, the pressure switch should have shut down the furnace.
      GFM

  • @lee-johnson
    @lee-johnson Před 5 lety

    You still have a draft. Try blocking the vent completely. The flames can’t get drawn in unless there is air moving out of the flue.

    • @grayfurnaceman
      @grayfurnaceman  Před 5 lety

      If you block the vent completely, (and this vent was very close to that) the pressure switch will shut it down.
      GFM

  • @capitolrefrigerationheatin7501

    interesting,nice post GFM

  • @randallcalhoun6604
    @randallcalhoun6604 Před 5 lety

    side note the c.o. would be high and rising. danger danger

    • @HighVoltageMadness
      @HighVoltageMadness Před 5 lety

      right i have seen this before on a furnace with a partially blocked chimney

  • @CommonSenseFishing209
    @CommonSenseFishing209 Před 4 lety

    You tripping? The left burner was rolling out sporadically the first time you fired it up.

    • @grayfurnaceman
      @grayfurnaceman  Před 4 lety +1

      That is not a rollout. The intermittent flame failure is a failure to pull enough fuel air mix into the heat exchanger. If I had a rollout, the flames would be continuously rising above the entrance to the heat exchanger.
      GFM

    • @CommonSenseFishing209
      @CommonSenseFishing209 Před 4 lety +1

      @@grayfurnaceman I agree but at 4:27 the flame failure kind of has a roll out effect. And I've seen the newer units with more sensitive roll out switches trip on things like that. Also the switches on certain units are right above those burners and trip easily from.flame abnormalities. I love how you put a theory to a test. I would like to see and do more of this myself with a.c and heat.

    • @JuanRivera-ff6fd
      @JuanRivera-ff6fd Před 3 lety

      What causes intermittent flame failure?

    • @CommonSenseFishing209
      @CommonSenseFishing209 Před 3 lety

      @@JuanRivera-ff6fd intermittent would look at flame sensor. Gas valve. Depends if millivolt system etc

    • @JuanRivera-ff6fd
      @JuanRivera-ff6fd Před 3 lety

      @@CommonSenseFishing209 my system has a standing pilot light ?