Siemens PS2 Smart Positioner used as Remote Positioner

Sdílet
Vložit
  • čas přidán 7. 01. 2017
  • Smart Positioner can be used as Remote Positioner for avoiding damage from heat, vibration, humidity etc..

Komentáře • 13

  • @somvitbakshi1105
    @somvitbakshi1105 Před 7 lety

    same I have done for fisher positioner

  • @mr.nizamulhoq851
    @mr.nizamulhoq851 Před 4 lety

    Dear sir,
    have a good day.
    i have recently facing problem in a a newly buying Siemens PS2 positioner connect with existing Single acting linear actuator , 20mm stroke.during comissioning this new control valve/actuator in initial condition its display shows P 85 and NOINI mode, at that time when i press + and - button the actuator totally not move.only small sound hearing inside the positioner and some air release backside of positioner , however pneumatic and electrical connection is ok.if i place old existing positioner there then it easily move
    the actuator after pressing + and - key in NOINI mode.
    Moreover when i go in Log 5 ,NOINITM mode 30% open the valve in both YEND1 and YEND2 once i press both + and - key.once i release button then actuator go to zero condition.it doesn't hold at all.
    If its abnormal what can i do.would you please advice me.
    if i press only either + or - button then actuator not move in YEND1 and YEND2 mode.but when i press both + and - button simultaneously then it open actuator only 30% but not hold at all then when press hand button its display range message.
    will you please advice me its normal or abnormal?
    Really i am facing a horrible condition for this positioner at my site and i am apologetically wish to get you kind advice please.
    Thanking You,
    Engr.Nizamul hoq.
    proprietor.
    United Mechatronics Engineers.
    Bangladesh.
    Email: united.mechatronics@gmail.com
    Mobile : 0088-01814792505 and 0088-01935675378(whatsapp)
    Skype: nizamul.hoq1

  • @markvirgiltapere5145
    @markvirgiltapere5145 Před 5 lety +1

    Nice video Sir.
    What model of Siemens positioner are you using?
    I'm using sipart ps2 Hart pos. 6dr5120. Is this applicable for that configuration?
    Thanks Sir.

  • @28vidhipatelxa83
    @28vidhipatelxa83 Před 6 lety

    what is the value of pot meter i want to do in my plant please help me to do this

    • @instrumentationandsolution5013
      @instrumentationandsolution5013  Před 6 lety

      Positioner already having POT so why u need another POT....so u can use the same POT. If you want use any other POT then max 10k ohms POT u can use ..

  • @markjason1887
    @markjason1887 Před 2 lety

    Is the wiring of the potentiometer of the base positioner tapped to the remote positioner?

  • @MdArafat-js2bi
    @MdArafat-js2bi Před 6 lety

    apni ki BangladeshiI?

  • @rajaramp366
    @rajaramp366 Před 7 lety

    there is no calibration done by a positioner. the positioner is long time to take to calibrate and show a error of u...d (