HIPOT TEST FOR HV BUS BAR

Sdílet
Vložit
  • čas přidán 28. 08. 2019
  • HIPOT TEST FOR HV BUS BAR
    FOR HV 6.6KV Switchboard
    Before going into Test we have to check the following things
    1. Open earth switch.
    2. Rack out VT
    3. Check The barricade around Testing AREAR.
    4. IR test has to conducted before hipot testing.
    5. Check the humidity of the place.
    For switchboard bus bar peak withstand voltage is 20 KV so we are going for 80% on it. Ie is 16KV
    DOWNLOAD HIPOT TEST REPORT
    drive.google.com/open?id=1GBT...

Komentáře • 29