IDMT curve testing | REF620 relay Testing | OMICRON QUICK CMC TESTING | Overcurrent Testing
zhlédnutí 1,1KPřed 14 dny
IDMT curve testing , REF620 relay Testing, OMICRON QUICK CMC TESTING ,Overcurrent Testing full form of IDMT it’s inverse define minimum time IDMT Curve formula they are For normal inverse formula = TMS X 0.14 /Ir^0.02-1 For Very Inverse formula = TMS X 13.5/Ir-1 For extremely inverse formula = TMSX80/Ir^2-1 For Long Inverse formula = TMS X 120/Ir-1 On this formula TMS is time Multiple Ir is fau...
HOW TO CONNECTED SIMOCODE WITH TIA PORTAL SOFTWARE | UPLOAD & DOWNLOAD FILE FROM SIMOCODE RELAY
zhlédnutí 1,2KPřed 4 měsíci
HOW TO INSTALL TIA PORTAL SOFTWARE FOR SIMOCODE RELAY COMMUNCIATION czcams.com/video/5BwjPcszJxc/video.html IN THIS SECETION CLEARLY EXPLANINED ABOUT SIMOCODE RELAY CONNECTION WITH TIA PORTAL SOFTWARE . AND ALSO HOW TO TAKE FILE FROM RELAY AND SEND FILE TO RELAY.
simocodo software installation | TIA Portal software installation
zhlédnutí 871Před 5 měsíci
How to install simocode siemens protection relay software step by step in tamil TIA Portal is the software used for simocode relay commiunication. simocode relay or TIA Portal software download link support.industry.siemens.com/cs/document/109811683 /simocode-es-v18-(tia-portal)?dti=0&lc=en-ID
Core Type Transformer Basic Construction
zhlédnutí 1,1KPřed 7 měsíci
We are going to see about construction of Three phase core type transformer. Main part of the transformer are core and winding This core is nothing but the laminated silicon steel sheets. For three phase transformer the core is in the shape of digital eight and over each vertical each phase will have LV winding near to core and next to that hv Winding. Here mostly we are going to see two main t...
Checking Fault Record for SPAM Relay | SPAM & SPAJ Trip Test
zhlédnutí 2KPřed 10 měsíci
Checking Fault Record for SPAM Relay , SPAM & SPAJ Trip Test for trip test is common for both spam and spaj
SPAM 140 | SPAM 150 | SPAM Relay Configuration & System Setting | How to do spam relay configuration
zhlédnutí 2,6KPřed 10 měsíci
SPAM 140 , SPAM 150 , SPAJ 140 , SPAM & SPAJ Relay Configuration & System Setting , both Spam and Spaj relay configuration will be same method for configuration. Easy way to do SPAM relay configuration and relay settings. #abbrelay #SPAM #SPAJ #RelayConfiguration #Relaysetting
SPAM 150C | HARDWARE CONFIGURATION | HOW TO CHANGE SETTING | MOTOR PROTECTION RELAY
zhlédnutí 2,9KPřed 11 měsíci
SPAM 150C , HARDWARE CONFIGURATION , HOW TO CHANGE SETTING , MOTOR PROTECTION RELAY. #spam150c #motortest
Why CT Secondary should not keep open
zhlédnutí 8KPřed 11 měsíci
DIFFERENT BETWEEN POWER TRANSFORMER AND CURRENT TRANSFORMER? WHY CT SHOULD NOT KEEP OPEN? IS IT CT WILL BLAST WHEN IT KEEP OPEN. WHAT HAPPEN IF INSULATION FAIL ON CT?
Why We use CT Secondary STAR Connection.
zhlédnutí 4,5KPřed rokem
Why We use CT Secondary STAR Connection. comparison of star and delta connection
CT Secondary Double point Earthing side effects | Mal operation of Double Earthing on CT Secondary
zhlédnutí 5KPřed rokem
CT Secondary Double point Earthing side effects | Mal operation of Double Earthing on CT Secondary
Why is a Current Transformer Secondary is always connected to Earthing
zhlédnutí 5KPřed rokem
Why is a Current Transformer Secondary is always connected to Earthing
How To Calculated Capacitor bank value
zhlédnutí 2,1KPřed rokem
How To Calculated Capacitor bank value
DDB monitor in Easergy studio | DDB monitor in Micom relay | Online monitor for Micom relay
zhlédnutí 1,8KPřed rokem
DDB monitor in Easergy studio | DDB monitor in Micom relay | Online monitor for Micom relay
Use of Capacitor bank in Inductive load
zhlédnutí 1,4KPřed rokem
Use of Capacitor bank in Inductive load
About Apparent power active power Reactive power | VAR | W | VA
zhlédnutí 3,2KPřed 2 lety
About Apparent power active power Reactive power | VAR | W | VA
Generator capability curve
zhlédnutí 16KPřed 2 lety
Generator capability curve
Rotor Earth fault protection | part-II
zhlédnutí 7KPřed 2 lety
Rotor Earth fault protection | part-II
Rotor Earth Fault Part-I
zhlédnutí 10KPřed 2 lety
Rotor Earth Fault Part-I
Loss of Field Relay testing | Under excitation relay Testing
zhlédnutí 12KPřed 2 lety
Loss of Field Relay testing | Under excitation relay Testing
Loss of field protection reason | Loss of field operating Region | Under excitation protection
zhlédnutí 9KPřed 2 lety
Loss of field protection reason | Loss of field operating Region | Under excitation protection
Loss of Field in Generator protection | - PART 1
zhlédnutí 9KPřed 2 lety
Loss of Field in Generator protection | - PART 1
100% STATOR EARTH FAULT PROTECTION IN GENERATOR
zhlédnutí 9KPřed 2 lety
100% STATOR EARTH FAULT PROTECTION IN GENERATOR
95% STATOR EARTH FAULT PROTECTION IN GENERATOR
zhlédnutí 9KPřed 2 lety
95% STATOR EARTH FAULT PROTECTION IN GENERATOR
Generator Stator Earth fault Protection
zhlédnutí 2,5KPřed 2 lety
Generator Stator Earth fault Protection
Generator negative phase sequence protection | ANSI CODE 46
zhlédnutí 16KPřed 2 lety
Generator negative phase sequence protection | ANSI CODE 46
pole slip protection Relay Testing
zhlédnutí 10KPřed 3 lety
pole slip protection Relay Testing
GENERATOR POLE SLIP PROTECTION | HOW POLE SLIP PROTECTION IS DETECTED BY RELAY
zhlédnutí 12KPřed 3 lety
GENERATOR POLE SLIP PROTECTION | HOW POLE SLIP PROTECTION IS DETECTED BY RELAY
GENERATOR LOW FORWARD AND REVERSE POWER PROTECTION
zhlédnutí 3,5KPřed 3 lety
GENERATOR LOW FORWARD AND REVERSE POWER PROTECTION
Reverse power protection in generator
zhlédnutí 18KPřed 3 lety
Reverse power protection in generator

Komentáře

  • @meghanasr3098
    @meghanasr3098 Před 4 hodinami

    Hi sir can u make a video of protection testing of numerical relays like RED670, RET670,REB670. With parameter setting and calculation

  • @khangnguyenhoangtrung5816

    hi sir, my RTU web server is stucked at "input and output", it display "loading user interface...", and i try all of things but can not acces, can you help me please, thank you

  • @GamerMonu
    @GamerMonu Před 3 dny

    Hindi

  • @agriculturefarming5922

    very explanation of BBP ,it will be a great value if you add the setting parameter of BBP relay for any vendor like SIEMENS BBP relay or any other like ABB,SEL,MICOM. Thanks

  • @wondercartoonss
    @wondercartoonss Před 6 dny

    Bro, you are doing great work, I am following your channel and watching your Testing and Commissioning Playlist, but your video sequence making me confuse, kindly arrange/sort it according to date, so that we can see accordingly.

  • @fabiomaia122
    @fabiomaia122 Před 7 dny

    Indian engineers always helping me. Tks

  • @SatheeshKumar-ic9jz

    Sir, We need video regarding Siemens Toolbox software

  • @laxmandas1317
    @laxmandas1317 Před 8 dny

    Sir what about zone -4

  • @rukmagoud
    @rukmagoud Před 8 dny

    There is a mistake in drawing . You are showing Ynd11 from generator. Generator is star connected and it is connected to step up transformer with vector group Ynd11. Here Y is always high voltage side. But in drawing you are showing in reverse way. Please check

  • @getalemkassa2831
    @getalemkassa2831 Před 11 dny

    TMS selection

  • @PUSHPARAJDANGI
    @PUSHPARAJDANGI Před 15 dny

    its great video sir thank you keep updating /watching from NEPAL

  • @srikanth0282
    @srikanth0282 Před 16 dny

    How n<1 , n>1 curves are drawn

  • @PraveenManchiraju
    @PraveenManchiraju Před 16 dny

    is the value of I is CT ratio of relay? and how to consider theta a and theta b percentages please explain

    • @baranitech1026
      @baranitech1026 Před 16 dny

      K*Set current is less then fault then need to considered theta A, if higher then need to considered Theta B thankyou.

  • @adityayadav6712
    @adityayadav6712 Před 17 dny

    Use better mic sir

  • @semalkumar5633
    @semalkumar5633 Před 17 dny

    Your videos are very informative.

  • @Jono-7-r2n
    @Jono-7-r2n Před 18 dny

    Can u revise the video with clear sound which is more useful yo us

  • @Jono-7-r2n
    @Jono-7-r2n Před 18 dny

    Sound not clear

  • @DanielRibeiro-jc4pz
    @DanielRibeiro-jc4pz Před 18 dny

    Missed your videos my friend. Very nice! 👏🏻👏🏻

  • @bhuvaneshm7864
    @bhuvaneshm7864 Před 18 dny

    Super bro.. 🎉

  • @raghavmohan7599
    @raghavmohan7599 Před 19 dny

    You are Great👍👏😊👍👏😊👍👏😊👍👏😊_Sir G_🎉🎉🎉

  • @azharilibra114
    @azharilibra114 Před 19 dny

    Don't forget guys,like coment and share

  • @PrabakarRamakrishnan
    @PrabakarRamakrishnan Před 20 dny

    Hi brother We already using Matching factor then how relay give trip.

    • @baranitech1026
      @baranitech1026 Před 16 dny

      with out matching factor current value is unequal.

  • @nkoupaternenkou7464
    @nkoupaternenkou7464 Před 21 dnem

    Great teaching. I am learning a lot, thanks

  • @livingstonechando2613
    @livingstonechando2613 Před 21 dnem

    l have a question in Cross polarization.If the operating current leads the polarizing voltage ,are we not supposed to use negative on RCA settings?

  • @livingstonechando2613
    @livingstonechando2613 Před 21 dnem

    Good Morning l have questions in Cross polarization.If the operating current lead the polarizing voltage ,are not supposed to use negative on RCA settings?

    • @baranitech1026
      @baranitech1026 Před 16 dny

      if you want to check on this area need to make reverse direction

  • @abidali.6873
    @abidali.6873 Před 25 dny

    Very interesting

  • @abidali.6873
    @abidali.6873 Před 25 dny

    Very interesting

  • @f__navid8800
    @f__navid8800 Před 25 dny

    Thanks, Dear🌹

  • @polytechnicelectricalengin5849

    Very good explanation

  • @Edcunha_2024
    @Edcunha_2024 Před 27 dny

    Good

  • @rahi172197
    @rahi172197 Před 28 dny

    hi can we get MCUSetup installation file

    • @baranitech1026
      @baranitech1026 Před 22 dny

      i use in Project file. it get from ABB thank you.

  • @doontales8421
    @doontales8421 Před 28 dny

    Thank you for this video. 1) Can you please explain settings for REM611. I urgently need to set it. 2) Also I am using 2 stages for overcurrent protection. I have set first stage as 1.2*I_FLC with IEC very inverse curve and time dial 1.12, so do I still need to set thermal overload (49) element?

  • @venkataramanakannuri4769
    @venkataramanakannuri4769 Před měsícem

    Good morning sir can you explain relay testing procedures with single phase kit

  • @owinookello9358
    @owinookello9358 Před měsícem

    One of my best teachers keep up good work sir, kindly arrange for your substations complete testing and commissioning for equipment and ht panels all test appreciate

  • @badshahibrahim8475
    @badshahibrahim8475 Před měsícem

    Sir please make on timing testing of GIS

  • @vinothselvam6240
    @vinothselvam6240 Před měsícem

    Thanks bro

  • @daleshwarpatel4789
    @daleshwarpatel4789 Před měsícem

    Sir please make video in ht motor thermal overload protection,how motor numerical relay detect thermal overload kindly explain in detail

  • @devendrabhatt7490
    @devendrabhatt7490 Před měsícem

    Sir why negative phase sequence occur ?

  • @owinookello9358
    @owinookello9358 Před měsícem

    One of my best teachers ,sir kindly those videos in hindi please translate in english and also put all your videos in one playlist for easy assess

  • @surendrakverma555
    @surendrakverma555 Před měsícem

    Good

  • @akashshah7088
    @akashshah7088 Před měsícem

    Thanks

  • @nkoupaternenkou7464
    @nkoupaternenkou7464 Před měsícem

    Excellent

  • @rassjnr
    @rassjnr Před měsícem

    Good good brother!!

  • @mostafaali2850
    @mostafaali2850 Před měsícem

    Mr Barani ‏‪ l have a problem during downloading and installing IED Products that gives me message " fail to download and install "

    • @TapasDas-ze2jo
      @TapasDas-ze2jo Před měsícem

      Same problem is arrive my system Kindly help

    • @baranitech1026
      @baranitech1026 Před 22 dny

      some time it will happens . can get connectivity package by 1.reset laptop and connect with different inter net. 2.download from ABB website. 3.Updated Updated manager and then try to download. 4.dowload from other laptop and export IED package.

  • @anisurrahman3941
    @anisurrahman3941 Před měsícem

    Thanks a lot,Sir🥰

  • @gustavomarcelo7250
    @gustavomarcelo7250 Před měsícem

    Sir. When you select the type of fault, you randomly draw the line on the circle? What actually the meaning of drawing the line amd where to start the line?

  • @muhammadfaraz1177
    @muhammadfaraz1177 Před měsícem

    Very informative....please upload more videos for application configuration like for goose function and communication and for TCS logics function also

  • @dharmendrakumarsingh8898
    @dharmendrakumarsingh8898 Před měsícem

    Can we change trip NC contact to NO contact ?

  • @meghanasr3098
    @meghanasr3098 Před měsícem

    Sir do the ABB relay protection testing videos

  • @bluemarble825
    @bluemarble825 Před měsícem

    Please prepare a video of CTS, VTS & BF and load shedding