ABB ACS 880 DRIVE - MOTOR ID RUN / IDENTIFICATION RUN STEPS - HINDI ME

Sdílet
Vložit
  • čas přidán 31. 03. 2020
  • This video contents -
    1. HOW TO DO MOTOR IDENTIFICATION RUN i.e. ID RUN FOR INDUCTION MOTORS FOR ABB ACS 880 DRIVE : • ABB ACS 880 DRIVE - MO...
    PART 2 - (NEXT VIDEO WILL SHOW HOW TO RUM THE ABB ACS 880 DRIVE FROM HMI/CONTROL PANEL i.e. FROM LOCAL MODE (NEXT VIDEO)

Komentáře • 87

  • @kamtaprasad784
    @kamtaprasad784 Před 4 lety +1

    Superb 👌

  • @nagireddisivaganesh4784
    @nagireddisivaganesh4784 Před 3 lety +2

    Thankyou sir 🙏

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety

      Welcome sir. Please support the channel, subscribe and share 🙏

  • @rohitdubey6221
    @rohitdubey6221 Před 2 lety +1

    Thank u sir

  • @shaikmeharaj5011
    @shaikmeharaj5011 Před rokem +1

    Hi bro thank u

  • @TheGamaCom
    @TheGamaCom Před 2 měsíci +1

    Great

    • @bishantkumar12589
      @bishantkumar12589  Před 2 měsíci

      Thank you so much sir 😊 kindly share with your Electrical team 🙏🏽

  • @vighneshlad7926
    @vighneshlad7926 Před 2 lety +1

    👌

  • @siddasantha
    @siddasantha Před 2 lety +1

    Thanks

  • @Atul_3012
    @Atul_3012 Před rokem +1

    Sir please make the video Dcs 880

  • @worldinstrumentationengineer

    BAHUT ASSA VI

  • @Fire_palace
    @Fire_palace Před 11 měsíci

    Sir acs 880 me Encoder by aur circuits me kaise lete espar bhi video banayiyega please

  • @ch.industrialelectricity5625

    Hi! I need help. In DTC mode, the motor must be equipped with an encoder and must be connected to the inverter or only in necessary cases must an encoder be attached to the motor. Thaks!

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety +1

      Hi. We use DTC mode for motor identification run, but we don't use encoder but Id run is performed perfectly.
      So, I don't think encoder is necessarily be connected to motor.

    • @ch.industrialelectricity5625
      @ch.industrialelectricity5625 Před 3 lety +1

      @@bishantkumar12589 Yes! I also think that it is only in special cases with certain applications that an encoder needs to be connected. in inverter default mode is DTC mode so i think it is suitable for most motor control applications without encoder.

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety

      @@ch.industrialelectricity5625 Yes. Even you can select scalar mode if operation doesn't need very high precision.

    • @syedsajawalshah4045
      @syedsajawalshah4045 Před 10 měsíci

      Why we use or required to use id run parameter

  • @norddine2402
    @norddine2402 Před rokem

    sir please I need help I changed the main fan cooling, acs880
    but the warning message is still on display A581

    • @bishantkumar12589
      @bishantkumar12589  Před rokem +1

      You have to reset the fan working time using laptop. I have made a video regarding it for ACS 800. You can check. It will be useful

  • @munnalalbharadwaj4175

    When parameters set ther anye auto twining option this drive which parameters no select??? Explane pleas next vidio

  • @Fire_palace
    @Fire_palace Před rokem +1

    Acs 880 control wiring par video banayiye Sir please

  • @Atul_3012
    @Atul_3012 Před rokem +1

    Sir Dcs 880 ke bare me v video baniye please

  • @AvinashMathur-bl7xu
    @AvinashMathur-bl7xu Před 6 měsíci +1

    Hello brother... No display issue in ACS880.. now ready smps section, but I saw rating ID mismatch 5093.
    Can u help me ?? Please

  • @ntpawar1982
    @ntpawar1982 Před 3 lety +1

    thanks sir,
    please i want n purchase remote for ACQ 80 solar pump Drive ,
    where can available

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety +1

      Sir. Right now I don't have any idea. I'll ask abb vendor once

  • @tirthankardeb7992
    @tirthankardeb7992 Před 2 lety +1

    I am getting AE8C warning CODE IN ACS880 HMI,CHANGED The battery CR2032 ,3V of HMI but warning still persists..What to do..Kindly help.

  • @5G...
    @5G... Před rokem +1

    ID run complet hone ke bad DTC ya Scaler rakhna padega?
    Weigh feeder ka Drive main Scaler rakha hai service engineer ne, isko DTC kadna padega?

    • @bishantkumar12589
      @bishantkumar12589  Před rokem +1

      ID run k liye DTC mode must hai, iske baad scalar mode daal sakte hai, no problem with that.
      WF k liy scalar mode chalega sir 👍
      DTC mode bahut kam place pe critically use hota hai.

    • @5G...
      @5G... Před rokem

      @@bishantkumar12589 Thanks

    • @bishantkumar12589
      @bishantkumar12589  Před rokem

      @@5G... wlcm

  • @tomasmacius7023
    @tomasmacius7023 Před rokem +1

    hi
    what that problem in my case what you think ? drive says "Run enable missing "
    no run enable signal received

    • @bishantkumar12589
      @bishantkumar12589  Před rokem

      check parameter - 20.12 : must be - ON for acs880,,,
      Check setting of parameter 20.12 Run
      enable 1. Switch signal on (e.g. in the
      fieldbus Control Word) or check wiring of
      selected source.

    • @tomasmacius7023
      @tomasmacius7023 Před rokem +1

      hm i tryed open 20.12 setting but there is so many options did'nt understand what to choose

    • @bishantkumar12589
      @bishantkumar12589  Před rokem

      @@tomasmacius7023 select - ON for that

  • @gyanendrasahoo4731
    @gyanendrasahoo4731 Před 4 lety +2

    After I'd run 99.04 Parmentier necessary to change scalar

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety

      No sir. Keep it as dtc only

    • @Sansangeetgeet08
      @Sansangeetgeet08 Před 3 lety

      Most of The application are run in DTC mode.
      But scalar control is nothing but a V/ F control .
      In DTC mode motor will get the better protection also energy consumption is less.
      So ID run is must required for DTC(direct torque control) control.

  • @hemantpatel3126
    @hemantpatel3126 Před rokem +1

    Sir How to check Motor Running Hours.VFD ACS880 . Please Reply

  • @CUTE-MUST-MUSTI
    @CUTE-MUST-MUSTI Před 6 měsíci +1

    Vfd se speed Kum jada kesey krrte hai 🙏🙏🙏🙏🙏

    • @bishantkumar12589
      @bishantkumar12589  Před 6 měsíci

      Analog input pe speed depend karta h. Ya phir potentiometer se kar sakte hai

  • @Fire_palace
    @Fire_palace Před rokem +1

    Sir mere ko Eot crane ne acs 880 vfd lagani hai agar aapke pas drawing aur parameter pdf ho to bhej dijiye please

    • @bishantkumar12589
      @bishantkumar12589  Před rokem

      800 ka details I can arrange, abhi 880 install nai hua h yaha

    • @Fire_palace
      @Fire_palace Před 11 měsíci

      Sir ID run ke bad local me kaise run karte par bhi video banayiye

  • @atulchoubey9152
    @atulchoubey9152 Před 3 lety +1

    Sir.. how to running hours show on display

  • @er.pratapsingh5845
    @er.pratapsingh5845 Před 9 měsíci +1

    Abb acs 880 dtc mode m hi chalte hai kya sir

    • @bishantkumar12589
      @bishantkumar12589  Před 9 měsíci

      Nai. DTC must nai h, aap aaram se scalar mode me chala sakte ho.

    • @bishantkumar12589
      @bishantkumar12589  Před 9 měsíci

      Kindly share this CZcams channel with your electrical team 🙏🏼

    • @er.pratapsingh5845
      @er.pratapsingh5845 Před 9 měsíci

      Ok sr but motor running mode torque negative shown on screen and control word hex 77 show kr change kaise kre

    • @er.pratapsingh5845
      @er.pratapsingh5845 Před 9 měsíci

      I am more share this vedio

  • @shaikmeharaj5011
    @shaikmeharaj5011 Před rokem +1

    Bro plz tell basic data of drive

    • @bishantkumar12589
      @bishantkumar12589  Před rokem

      Sure sir, soon. Many videos are available on this channel, ▶️ pl check ✅ you may find some useful ones

  • @muhammadnaeem1219
    @muhammadnaeem1219 Před rokem +1

    Sir abb Acs 580 Ka fault number 5093 ha

    • @bishantkumar12589
      @bishantkumar12589  Před rokem

      Rating ID mismatch fault hai aapka. Drive k hardware ka information match nai ho raha h drive k stored memory se.

  • @ganeshs.c1100
    @ganeshs.c1100 Před 2 lety +1

    Sir Disply nòt show any problem solve solution

    • @bishantkumar12589
      @bishantkumar12589  Před 2 lety

      Check the cable. There are 2 types of cable. Both doesn't fit with each other.
      Check the connection port. Mismatch of port and connecting lead causes this issue.
      Or else. Replace the CDP

  • @sujitsutar4953
    @sujitsutar4953 Před 3 lety +1

    880 me standstil & 800 me reduce kiun ?

  • @flyingzero4840
    @flyingzero4840 Před 3 lety +1

    Acs 550 current limt parameters?

  • @Sansangeetgeet08
    @Sansangeetgeet08 Před 3 lety +1

    Why standstill !! Go for Normal ID run . If Motor shaft can be decouple from load.
    It will always better to get the Motor Characteristics Value by VFD during the Motor Identification Run In "Normal(Rotary)" mode.
    One thing to do better is to Perform A Power recycling if possible ! Or Control board Boot . (Parameter-96.08 )control board boot changing the value of this parameter to 1 reboots the control unit (without requiring a power off/on cycle of the complete drive module).the value reverts to 0 automatically.note: this parameter cannot be changed while the drive is running.

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety +1

      But sir. As per MANUAL, standstill is recommended

    • @Sansangeetgeet08
      @Sansangeetgeet08 Před 3 lety

      @@bishantkumar12589 ok understood। But standstill recommend when motor shaft decoupling from load is not possible or a huge hard job.
      Otherwise to take Normal ID run is always better for critical applications.

    • @Sansangeetgeet08
      @Sansangeetgeet08 Před 3 lety +3

      See As per manual
      "" Standstill ID run.
      The motor is injected with DC current. With an AC induction (asynchronous) motor, the motor shaft is not rotated. With a permanent magnet motor or synchronous reluctance motor, the shaft can rotate up to half a revolution. Note: A standstill ID run should be selected only if the Normal, Reduced or Advanced ID run is not possible due to the restrictions caused by the connected mechanics (eg. with lift or crane applications).

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety

      @@Sansangeetgeet08 ok sir. Thank you

  • @ahamedmeeran7719
    @ahamedmeeran7719 Před rokem +1

    What is id run?

    • @bishantkumar12589
      @bishantkumar12589  Před rokem

      Motor identification run. Drive get to know about the motor details.
      Check my channel, u will find seperate video about it.

  • @kirtimistry3572
    @kirtimistry3572 Před rokem +1

    ID run ka meaning