ABB ACH580 VFD SETTING

Sdílet
Vložit
  • čas přidán 29. 08. 2024

Komentáře • 16

  • @KrotKrot-np6gz
    @KrotKrot-np6gz Před 5 měsíci

    Amazing

  • @semnansteel
    @semnansteel Před 25 dny

    With regards and respect to your service
    In ABB inverter model ACS580 we have error 6581
    During continuous operation, it gives this error every three hours, and in case of fault, the inverter is turned off.
    please guide me
    Of course, it goes without saying that we have also done a factory reset
    Thank you

  • @kuruvillaabraham7702
    @kuruvillaabraham7702 Před 2 lety

    How to change its out put frequency??
    ie How to change the speed (purpose of this drive is this so pls explain about it)

    • @rafiautomation
      @rafiautomation  Před 2 lety

      czcams.com/video/h24LyaPekh4/video.html plz watch this video

  • @AliRaza-iq3fd
    @AliRaza-iq3fd Před 2 lety +1

    i have inverter ach580 am working today my vfd fault is AFF6the fault is id run fault when the drive is run command the vfd triped and ahow fault of display is id run plz help me thankyou and gaid me

    • @rafiautomation
      @rafiautomation  Před 2 lety

      I'd run fault is not causing vfd to trip just check the parameters in group 99 feed the motor nominal values correctly

  • @dankauye
    @dankauye Před 2 lety +1

    How can I clear a fault of 4981 on the ABB VFD Model ACH580.

    • @rafiautomation
      @rafiautomation  Před 2 lety

      Have u connected the motor sensor to the vfd? If yes the motor temperature rises. Check motor temperature if ok then sensor of ur motor is faulty disconnect that or replace

    • @dankauye
      @dankauye Před 2 lety

      @@rafiautomation Thanks for the quick response.No I have not connected the motor sensor to the VFD.

    • @dankauye
      @dankauye Před 2 lety

      Its AHUnit that we want to commission and the motor is not even hot.

    • @rafiautomation
      @rafiautomation  Před 2 lety

      Check parameter 35.11 if any source is selected by mistake

    • @rafiautomation
      @rafiautomation  Před 2 lety

      Or check the paremeter 35.12 and 35.13 may be temperature limit I too low need to increase it

  • @dankauye
    @dankauye Před 2 lety

    The fault is External temperature to high