  • ABB ACS 800 DRIVE - MOTOR ID RUN PROCEDURE
    Motor ID run of ABB ACS 800 Drive

Komentáře • 44

  • @austinf3810
    @austinf3810 Před 22 dny

    Great video!

  • @g.shivakumar5309
    @g.shivakumar5309 Před 10 měsíci +1

    Thx sir, good information

    • @bishantkumar12589
      @bishantkumar12589  Před 10 měsíci

      Welcome sir. Kindly share this technical channel with your electrical team 🙏🏼

  • @sushantchhatar9598
    @sushantchhatar9598 Před 2 lety +2

    Thank you sir

  • @mrchiefjena355
    @mrchiefjena355 Před 8 hodinami

    SPD MATCM FLT

  • @sandeepdas2641
    @sandeepdas2641 Před 3 lety +1

    Pls upload video how to run two motors different rating through a single drive...dual user system

  • @jkj1459
    @jkj1459 Před 3 lety +1

    OUR MACHINE IS COUPLED NOT POSSIBLE TO DECOUPLE , IN THIS SITUATION HO TO PERFORM ID RUN ?? KINDLY REPLY . "ID MAGN " IS THE SELECTED PARAMETER IN THE ORIGINAL PARAMETER LIST .

  • @phamangmanhquynh779
    @phamangmanhquynh779 Před 4 lety +1

    Hi guy. Thanks for you video.
    Can I upload to PC by using drive composer entry software ? What type of cable and how to set communication ?

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety

      Yes, laptol can be connected. Ethernet type cable can be used

    • @krishnamohan6104
      @krishnamohan6104 Před rokem

      What is the difference between I'd run and id magnetization

  • @smrhaashmi67
    @smrhaashmi67 Před 9 měsíci +1

    How to reset the fault Start Inhibit FF7A coming in acs 800 5 kva

    • @bishantkumar12589
      @bishantkumar12589  Před 9 měsíci

      czcams.com/video/WZzo8Ak68Y4/video.html

    • @bishantkumar12589
      @bishantkumar12589  Před 9 měsíci

      Check if your problem is covered in this video

    • @smrhaashmi67
      @smrhaashmi67 Před 9 měsíci

      I found the solution... Shorting wires were not plugged near the Rashi card on main RINT board

  • @francisolmedillo4183
    @francisolmedillo4183 Před 2 lety +1

    the motor should be uncoupled in the load side prior to ID run.

  • @user-gz8ss8gy9g
    @user-gz8ss8gy9g Před 5 měsíci +1

    how to check drive running hours

  • @amitpagare5946
    @amitpagare5946 Před 3 lety +1

    🙏🙏🙏🙏🙏👍

  • @psr2109
    @psr2109 Před 4 lety +1

    Sir in ID run what is the difference between the " reduced" and "standard "selection

    • @bishantkumar12589
      @bishantkumar12589  Před 4 lety +1

      P S R in Reduced mode, motor will not run on rate/greater speed, max it will run 5-10% but on Standard mode, drive will make the motor run up to rated speed.
      It is preferred to do ID Run @ Reduced/Standstill mode.

    • @sujitsutar4953
      @sujitsutar4953 Před 3 lety

      Id run complete hone k baad reduce ko firse standard karna padega ky ?

    • @athish6716
      @athish6716 Před 3 lety +2

      There are 3 modes to perform ID run in different possible conditions.
      Standard,
      Reduced,
      ID MAGN (ID Magnetization),
      If the motor is decoupled from load and with empty shaft you can perform Standard, In standard ID Run the motor is accelerated and decelerated multiple times with shorter ramp time, this is most accurate way of measuring the motor characteristics,
      If the motor is coupled with light load where the load can be driven by the motor but smoothly, you can use reduced option, this option does accelerate and decelerate the motor slowly so that the mechanical load is safe. Accuracy is also better than the 3rd option.
      If any chance the motor cannot be rotated due to mechanical load limitation then, you can use Standstill option, in which 3 phase current are measured by feeding DC voltage and motor does not rotate, accuracy is not good as Standard and Reduced mode, but it is ok to run most of the applications like pump, fan, compressor, etc
      Well the accuracy I mentioned here is not so important for you,
      If the application is very demanding and dynamic (for example cold rolling mill, crane hoist, conveyor, some compressors,etc..) then standard ID RUN is mandatory

    • @jashimuddin-ve5fm
      @jashimuddin-ve5fm Před rokem

      As per manual when i select ID mag that time motor not rotal also brake not open , but when i select ID Mag brake open , why .....please give me a feedback.

  • @salimmulla5446
    @salimmulla5446 Před 4 měsíci +1

    How to get reference mode

  • @satyajitprusty9127
    @satyajitprusty9127 Před 3 lety +1

    Why we perform identification run.. sir

  • @hashamkhan7044
    @hashamkhan7044 Před 3 lety +1

    We have two acs 800 drives but in perameter 33.01 software version of drives is different,so is it possible to use one drive hmi to other,?when i want to upload perameter to 1st drive by using 2nd drive hmi it gives uploading failed and 1st drive hmi connect in 2nd drive it gives communication fault 7510,what can be reason,please give me solution,thanks

    • @bishantkumar12589
      @bishantkumar12589  Před 3 lety

      No brother. It will show error. Same version is must for uploading or downloading program

    • @athish6716
      @athish6716 Před 3 lety +1

      The HMI for all ACS800 is same but of the drive has different software version or different software type then, you cannot use upload and download function using HMI, Instead manually enter the parameters

  • @calisthenicsworkout3432

    If i have alarm failure puls conter what i will do?

  • @jhankarvideo6275
    @jhankarvideo6275 Před 4 lety +1

    what is the need of id run plz explain