How to check EEV coils from daikin aircon multzone ductless

Sdílet
Vložit
  • čas přidán 26. 08. 2024
  • Air conditioner how to Check EEV coils from daikin unit, expansion valve

Komentáře • 48

  • @johnricsolayao8431
    @johnricsolayao8431 Před 2 lety +1

    How to check the board if it's short circuit 😊
    Thank you love your all videos

    • @FriotecAVAC
      @FriotecAVAC  Před 2 lety

      Hi dude...multimeter is the first instrument to use it...and your eyes 👁️ to see any Black point burned

  • @orlandorizzo5780
    @orlandorizzo5780 Před 3 lety +1

    so you had 2 replace the expansion valve coil ? or both the board and coil[ or did u use a heat gun and replaced the IC chip?

    • @FriotecAVAC
      @FriotecAVAC  Před 3 lety +1

      Hello .
      I used a micro heat gun to replace de I.C driver and a coil kit .
      I'm gonna do a video to replacing a kind of components like that ..

    • @orlandorizzo5780
      @orlandorizzo5780 Před 3 lety +1

      Friotec Refrigeração you should of said that to begin with ! Here in USA we replace the board lol

    • @FriotecAVAC
      @FriotecAVAC  Před 3 lety +2

      Yes I know but the component its only 2 $ the new board around 500$ ...

  • @mikintos
    @mikintos Před 2 lety +1

    Hello, I have an LG Multi split air conditioner, and 3 indoor units connected to it, the model is "FM30AH UE3", I noticed that it heats me poorly and that if only one indoor is on, the pipes of all units are warm, although only one included. What could be the problem. Thanks a lot!

    • @FriotecAVAC
      @FriotecAVAC  Před 2 lety

      Hello... first of all, you need to check the pressure, maybe it leaks anywhere. When the pressure is lower you've got poor warm up.

  • @santhoshparuchuri9997
    @santhoshparuchuri9997 Před 3 lety +1

    Sir does eev is present in both indoor and outdoor unit of vrf

  • @joseguerreiro1166
    @joseguerreiro1166 Před 3 lety +1

    boas amigo… onde posso comprar pasta térmica e qual a melhor para as placas de ar condicionado ?

    • @FriotecAVAC
      @FriotecAVAC  Před 3 lety

      Boas se for em Portugal...RS componentes, aquário ,aswo, qualquer loja de eletrônica vais encontrar .
      Bia sorte

    • @joseguerreiro1166
      @joseguerreiro1166 Před 3 lety

      @@FriotecAVAC e qual a melhor para as placas de ar condicionado ?

    • @joseguerreiro1166
      @joseguerreiro1166 Před 3 lety

      mas qual a melhor para as placas eletrónicas ? vejo vários tipos e preços .
      nãos ei qual comprar

    • @FriotecAVAC
      @FriotecAVAC  Před 3 lety +1

      Boas ,então a cinzenta e quando comprar procure uma que na características tenha maior transferência de calor.
      Qualquer marca é boa desde que a transferência de calor seja maior então é assim que compro procurando sempre uma com maior transmissão de calor.

  • @Arieldny
    @Arieldny Před 2 lety +1

    What the normal reading should be between each wire ? Can you please post that ?
    Thanks

    • @FriotecAVAC
      @FriotecAVAC  Před 2 lety

      47 to 50 ohms and 90 to 98 ohms

    • @Arieldny
      @Arieldny Před 2 lety

      @@FriotecAVAC great thank you!

  • @user-qb5oi4ur1q
    @user-qb5oi4ur1q Před 3 lety

    Hello, how to check if board is faulty after knowing EEV is faulty? Able to help? Is it testing 12V? If so how?

  • @sujjubond007
    @sujjubond007 Před 3 lety +1

    Does it trips the main breaker ?

  • @parvejalam3380
    @parvejalam3380 Před 5 lety +1

    Hi. Sir a Daikin inverter ac running condition but whole outdoor unit after 30 second sutt off but neutral and communication between come to voltage
    Than idu pcb dead or odu pcb dead I don't know sir please reply me

  • @javiervidal2242
    @javiervidal2242 Před 4 lety +1

    do you know where I can buy this board? I have a U4 error and it looks damage

    • @FriotecAVAC
      @FriotecAVAC  Před 4 lety

      Hi from Daikin...
      I`ve got some but it`s EURO vers 50hz

    • @javiervidal2242
      @javiervidal2242 Před 4 lety

      @@FriotecAVAC yes the only thing is they sell it for 500$ I think a new unit is better then...
      thank you for the answer and the videos

  • @rikay113
    @rikay113 Před 5 lety +1

    Hello sir, did the problem in this video the code error is U0? Cuz I have problem with this error code the indoor didn't want to operate indoor unit not operate also the outdoor, I need your answer, and then sorry for my bad English

    • @FriotecAVAC
      @FriotecAVAC  Před 5 lety

      Hello...in this video I'm explaining how to checking the EEV's coils and sometimes it's burn up the PCB and shows the erro code U0

    • @rikay113
      @rikay113 Před 5 lety

      @@FriotecAVAC okay thanks sir

  • @zanhghh3758
    @zanhghh3758 Před 6 lety +1

    Hello I have like a main PCB A problem is not working and a new main PCB has been replaced
    A malfunction was identified from the main PCB

  • @parvejalam3380
    @parvejalam3380 Před 6 lety +1

    How to check inverter outdoor Pcb Doid brige and ipm modul
    Please clean the picture and write the part name

    • @FriotecAVAC
      @FriotecAVAC  Před 6 lety +1

      I've got a video explaining how to check but it's in Portuguese...I'll do another video in English thanks

  • @parvejalam3380
    @parvejalam3380 Před 5 lety

    5volt and 12 volt and 315 volt dc whereupon check odu pcb ( part name where do check)
    Please reply me

  • @parvejalam3380
    @parvejalam3380 Před 5 lety

    How to check ipm modul and diod bridge from Daikin air-conditioning

    • @FriotecAVAC
      @FriotecAVAC  Před 5 lety +1

      Hi every IGBT Diode are the same away to tester.

  • @parvejalam3380
    @parvejalam3380 Před 5 lety

    Please make one video so display on not come to error code than how to check pcb
    And my last question Daikin inverter ac in neutral and communication between come to voltage AC or DC
    Please..... Reply me fast sir
    Because I am ac technician from Daikin air-conditioning

  • @user-bz3mi1vf7p
    @user-bz3mi1vf7p Před 3 lety +1

    ftxc25... EEV, blue / brown 4.3 ohm. WTF

  • @parvejalam3380
    @parvejalam3380 Před 5 lety

    Sir Daikin inverter ac in error code F3 seen what problem. What check

    • @FriotecAVAC
      @FriotecAVAC  Před 5 lety +1

      F3
      Error Details
      Condensing Unit
      Malfunction
      Malfunction of discharge pipe temperature
      Causes
      Shortage of gas
      Defect of connector contact
      Clogged refrigerant piping
      Defect of discharge pipe thermistor
      Applicable Products
      SkyAir
      VRV
      RA
      Compressor Compartment
      Malfunction
      Malfunction in discharge pipe temperature
      Causes
      Defect of discharge pipe thermistor
      Defect of connection of discharge pipe thermistor
      Insufficient refrigerant amount
      Defect of compressor
      Discharge pipe thermistor dissconnected
      Applicable Products
      Altherma

    • @FriotecAVAC
      @FriotecAVAC  Před 5 lety +1

      It cold be the short freon or EEV valve coil and main board

    • @parvejalam3380
      @parvejalam3380 Před 5 lety

      Thanks sir
      I love u video

  • @parvejalam3380
    @parvejalam3380 Před 5 lety

    No error code

    • @FriotecAVAC
      @FriotecAVAC  Před 5 lety

      Check the outdoor unit voltage, check for 5 volts, 12,volts and 315 volts vdc... If the outdoor is work for 30 seconds for sure you've got the Erro code wait for a couple minutes and use your handset to check the error code.