How to check Motorized Valve Coil reading |Daikin inverter
Vložit
- čas přidán 26. 08. 2024
- Brand : Daikin inverter (multi split)
model : 3MKS50ESG (CU)
Error : A5
symptoms : There were icing on the evaporator coil aircon was switched on.
Cause : CU EEV or parts name is Motorized Valve Coil faulty
Good condition Motorized valve coil reading is around 48 ohm.
please Subscribe my CZcams channel.
/ bonmj
#bonmj #daikin #airconditioner
Video uncle semuanya bagus2 .. uncle tak kedekut ilmu . Semoga diberi kesihatan dan umur yang panjang
Terima kasih
trimakasih ilmu yah bos ku bon MJ sukses selalu berguna buat ilmu yah
Terima kasih
Hello from New York. Great video, thanks!
Welcome
Great and informative video…Thanks
Thanks
Great video Bon! Thanks
Thanks
Çok teknik işi yapıyonuz teprik
Super info sir..thanks a lot
Thanks
Trimaksih bos
Good job you job
Thanks
Very useful information Boss.....
Thanks
Sir what is the ohm range for a good EEV?
Bon Mj love your content. Does anybody know where I can buy the Daikin wireless adapter btsc in the United States. Thank you
Thank for info .for me usefully.
Thanks
Great video brother 👍
Thanks
Good job sir
Thanks
Hello bon mj,. Is the motorized coil value for each AC the same? for example Panasonic or other brands
Most same
Thank you bhon
Thanks
Hi 👋, Thanks 😊
Thanks
Hello bro. Thank you for good jobs. Eev electrinoc expansion valve and motorized valve. Are they both the same thing? Are they just different names?
Thanks for visiting.
Normally we call EEV.the original parts name is motorized valve coil.
@@BonMj thank you bro. Greating from Turkey
@@mazarat4768 welcome
GooD
Thanks
will this cause L5 error too ?
compressor is running. pcb checked okay . compressor okay.
Inverter pcb
@BonMj outdoor pcb was changed. Compressor now can run back normally. But the L5 still beep. Is there prosedure required to reset fault code ?
lev is stepping motor ? thx ~
Normally we call swing motor is stepping motor, LEV is linear expansion valve
Kalau cara check body coil motorized nya rusak atau tidak seperti apa?
Tengok reading
Hi bon my gas 410 Toshiba invartar ac indor nois and not coling and section pip ice gas pressure 70 running off ac 220 pressure ac gas by wait 1.40 kg proper and veccume properly 1 hour ..... my problem what you think soldinet valv problem ?? Indor proper flash with nitrogen and pip not pinch ....
Try check piping any double expension.
My house do not have latch can you change the valve for me
I need your help sir I am live in India job for Daikin .... One mathcine outdoor motor not working
Vrv?any error
hi sir Indoor and outdoor how to check the on coil and off coil temperature thanks
Use thermometer to check
On coil is temperature of air entering into evaporator coil.
Off coil is air temperature leaving the evaporator coil.
Thanks sir
Hi sir can I ask can we interchange EEV A,B,C, or D.
If got empty unit should ok
@@BonMj if ever C and D has no piping can I transfer the EEV to the defective EEV ?
@@jonjieeray-fu7ui should no problem
Ok sir @Bon Mj I will try it if ever there's a trouble of EEV.
Good day..sir.,can i apply to your company where you work now? Im aircon technician here in brunei ..thankyou
Thanks.i at Singapore
Good day..So how can i apply to your company sir? Any information where to apply..thank you very much
@@ramdugat7232 you in Singapore?
Good eve..here in brunei right now sir..thank you
Any possibilities sir you can help me direct to apply to your company from here in brunei to singapore?
Motszingmoter modesl
Tn"q
TQ