Daikin inverter | air conditioner Thermistor Failure Symptom

Sdílet
Vložit
  • čas přidán 25. 08. 2024
  • Brand : Daikin
    model : MKS80QVM
    ERROR : No error
    Symptom: Running after 45minutes,Fcu auto off and auto on back,outdoor LED 1 & 2 light up.
    Cause : Thermistor failure Symptom,thermistor short circuit.
    #bonmj #daikin #inverter

Komentáře • 108

  • @Techhvac
    @Techhvac Před 2 měsíci +1

    Sir .Bon Mj
    Your technical Video's very useful for technician. Great job
    Thank you so much 🙏🇶🇦

    • @BonMj
      @BonMj  Před 2 měsíci

      It's my pleasure

  • @Achabab
    @Achabab Před 2 lety +1

    I never find this problem before😂😂😂, first time some one share this information in CZcams.
    You are the best⭐⭐⭐⭐⭐

  • @vladimirmakhney5407
    @vladimirmakhney5407 Před 2 lety +1

    Hello. A very good tip, I'm sure many technicians didn't even know about it

  • @robinsonguanzon8092
    @robinsonguanzon8092 Před 2 lety +1

    Thanks Sir Bon Mj ❤️
    A big help to us technician, A far areas and urban areas..🙏🙏🙏

  • @JDT738126
    @JDT738126 Před 2 lety +2

    Bon your videos are excellent! Thank you

  • @carlocurotto7555
    @carlocurotto7555 Před 2 lety +2

    That’s a great tip thank another fantastic video

    • @BonMj
      @BonMj  Před 2 lety

      Thanks bro🙏

  • @februaryoakkar938
    @februaryoakkar938 Před 2 lety +3

    Thank you sir

  • @estanislauboavidabelo4975

    thank you, please continue to upload the video.

  • @birin.6884
    @birin.6884 Před 2 lety +3

    Hey, thanks for everything. explain his picture and I'm good.

  • @jagannath3839
    @jagannath3839 Před 2 lety +1

    This is very good helpful information thanx sir.

  • @narayanaya5519
    @narayanaya5519 Před rokem +1

    Very useful information

  • @linaung127
    @linaung127 Před 2 lety +1

    Hello sir, nice troubleshooting, thanks

  • @arunramachandrana1025
    @arunramachandrana1025 Před 2 lety +1

    Very good information

  • @alanwong2761
    @alanwong2761 Před 2 lety +1

    👏 bravo bro 👍

  • @shreekanay698
    @shreekanay698 Před 2 lety +1

    Thanks Boss.

  • @khaidang8614
    @khaidang8614 Před rokem +1

  • @karimchiu7527
    @karimchiu7527 Před rokem +1

    Thank Sir Bon

  • @Blueblurr112
    @Blueblurr112 Před 2 lety +1

    Great video thank you.

  • @Didik-cq8wy
    @Didik-cq8wy Před rokem +1

    Trimakasih bos

    • @BonMj
      @BonMj  Před rokem

      You Dari mana?
      Terima kasih banyak nonton video saya

  • @sarfarajshaikh4582
    @sarfarajshaikh4582 Před 2 lety +1

    Nice one bro

  • @arafteknikac
    @arafteknikac Před 2 lety +1

    Thank you so much

  • @hafeezdaikin2517
    @hafeezdaikin2517 Před 2 lety +1

    Thank you boos 👍

  • @aselajayasundara1669
    @aselajayasundara1669 Před 2 lety +1

    Thank you sir 🙏

  • @karaors8970
    @karaors8970 Před 2 lety +1

    Thank you bro

  • @winmaung4558
    @winmaung4558 Před 2 lety +1

    Thank sir

  • @mdtuhintalukder5012
    @mdtuhintalukder5012 Před 2 lety +1

    Thank you....

  • @tabresztabu562
    @tabresztabu562 Před 2 lety +1

    Tq Boss 🙏

  • @JDT738126
    @JDT738126 Před 2 lety +2

    Hi Bon, could you please provide a source for many of the common manufacturers thermistor resistance/temperature values? I cannot find any for the LG brand.

  • @peramaraj2763
    @peramaraj2763 Před 11 měsíci +1

    Normally daikin compressor discharge thermistor range 13 to 15 kilohms right ?

  • @jamestan7901
    @jamestan7901 Před 2 lety +1

    👍 👍 👍

  • @user-vz6mu7iu7j
    @user-vz6mu7iu7j Před rokem +1

    hi sir im p paul kolkata i lick you video

  • @alembattlerealmsgamefowl6631
    @alembattlerealmsgamefowl6631 Před 4 měsíci +1

    sir inverter daikin 1.5hp ,indoor fan motor stay in low speed what maybe the reason o the problem ? even we changes to high speed in the remote fan speed still low,thanks for the reply

    • @BonMj
      @BonMj  Před 4 měsíci

      Any coil choke

  • @MrRandyj72
    @MrRandyj72 Před 2 lety +1

    That would be hard to find on the system unless its in cooling mode developing condensation at the time you are checking.
    Did the error code send you in the direction to check the thermistors?
    Last question did you full change the harness or just dry and seal the bad thermistor?

    • @BonMj
      @BonMj  Před 2 lety +3

      Just happen after running 45minutes.
      Only outdoor LED 1&2 on when stop running,indoor auto off and will auto on back after for awhile.
      We replace the new harness.

    • @Achabab
      @Achabab Před 2 lety +1

      @@BonMj thank you share your knowledge 🙏🙏🙏god bless you

    • @BonMj
      @BonMj  Před 2 lety

      @@Achabab welcome

  • @ThesecretS_a_n_3_1
    @ThesecretS_a_n_3_1 Před 3 měsíci +1

    Daikin Indoor fan motor no running a6 alarm coming I replace indoor motor and indoor PCB board also but still have a6 alarm ? What is problem

    • @BonMj
      @BonMj  Před 3 měsíci

      Check thermistor

  • @azadabduellahal8116
    @azadabduellahal8116 Před rokem +1

    Same can happen Mitsubishi system

  • @antoinetuyongo6527
    @antoinetuyongo6527 Před 2 lety +1

    Bonjour , comment je pourrais avoir la version française

  • @errantpmd3765
    @errantpmd3765 Před rokem +1

    Sir. My aircon.. cut in compressor n fan for 30min for 3 room.
    Is it thermistor of outdoor? I saw your ismike series, u change the indoor thermistor...
    May I know if is the same logic?
    Mine are toshiba

    • @BonMj
      @BonMj  Před rokem +1

      What is your setting temperature

    • @errantpmd3765
      @errantpmd3765 Před rokem +1

      @@BonMj sir.. even in the lowest also the same.

    • @errantpmd3765
      @errantpmd3765 Před rokem +1

      @@BonMj correction sir. Is 30sec..not min.

    • @BonMj
      @BonMj  Před rokem +1

      @@errantpmd3765 may be outdoor pcb problem

    • @errantpmd3765
      @errantpmd3765 Před rokem +1

      @@BonMj sad.. :(
      Thought is some thermistor...

  • @zse0118
    @zse0118 Před 2 lety +1

    Hi Sir!
    What's the reason you put the thermistor in the water and than you checked the countinity again?

    • @BonMj
      @BonMj  Před 2 lety +2

      Put in the water just show the thermistor is short circuit when water go in to the parts.
      When the thermistor locate at suction pipe,the water will go into the parts after gas pipe condensation.

    • @zse0118
      @zse0118 Před 2 lety +1

      @@BonMj Thank you so much for your answer.

  • @narayanaya5519
    @narayanaya5519 Před rokem +1

    If short thermistor what could happen PCB

    • @BonMj
      @BonMj  Před rokem

      For this case intermittent blinking, pcb ok.

  • @arasanairconsolution4u9
    @arasanairconsolution4u9 Před 2 lety +1

    Hai sir ,vrv 3 Daikin system one outdoor 3 indoor ,all running good but , standard compressor Haven't run even one FCU haven't achieve room required temperature.please advise

    • @BonMj
      @BonMj  Před 2 lety

      May be already by pass.
      Check mode2

    • @peramaraj2763
      @peramaraj2763 Před 11 měsíci

      ​@@BonMjalready bypass how to find ? Bro

  • @randypatcho6051
    @randypatcho6051 Před rokem +1

    How to apply your company sir

  • @janshaw5472
    @janshaw5472 Před 2 lety +1

    这种情况好难被发现!感谢老师!contiuniry中文是什么?

    • @BonMj
      @BonMj  Před 2 lety

      谢谢你。去了两次才发现

    • @BonMj
      @BonMj  Před 2 lety

      Continuity 是联系的,比如wire用meter 量continuity 。

  • @ManojKumar-zu2yz
    @ManojKumar-zu2yz Před rokem +1

    Sir daikin vrv3 modal rxyq12pry6 error code p4 Cheng master PCB

  • @gothandaraj860
    @gothandaraj860 Před 2 lety +1

    Hi sir vrv 3 Daikin AC e2 error and E3 error how to make rectify

    • @BonMj
      @BonMj  Před 2 lety

      E2 may earth leakage
      E3 high pressure sensor/high pressure switch

  • @govindarasugovindarasu7440

    Hi sir I have problem is Diakin air conditioning vrv system celling saspanded units have the error UF this error what is the problem sir thanks

  • @abidshirhatti6815
    @abidshirhatti6815 Před 2 lety +2

    Hi sir my wathsup no not going for comment

  • @nagarajvenkat8476
    @nagarajvenkat8476 Před 2 lety +1

    Hi sir I have problem daikin package unit error E 32 how to rectify this problem sir

  • @mycountrymyvlog1
    @mycountrymyvlog1 Před 2 lety +1

    i need job i am air conditioning and refrigeration mechanic

  • @azizullahkhanpathan2693
    @azizullahkhanpathan2693 Před 2 lety +1

    Hello sir I am Aziz. I have a Daikin 1.5 ton inverter split AC. My AC is showing C3 error code. Can you please tell me what C3 error code is and how to solve it . Model no FTKZ50U