How to solve error E4-01 Daikin VRV4

Sdílet
Vložit
  • čas přidán 26. 08. 2024
  • Brand : Daikin VRV4(A)
    model : RXQ10AYM
    Error : E4-01
    Description of Fault
    Master outdoor unit low pressure switch activation.
    Detail of Fault
    This is stating that there has been a low pressure error on the Master outdoor unit.
    This could have been caused by a blockage in the pipe work or a possible shortage of refrigerant.It could be due to a fault with the low pressure sensor/switch.
    Error : E4
    Description of Fault
    Low pressure switch activation.
    Detail of Fault
    This is stating that there has been a low pressure error on the system.
    This could have been caused by blockage in the pipe work or a possible shortage of refrigerant. It could also be due to a fault with the low pressure sensor/switch.
    Solution
    Open the valve.
    Check the amount of refrigerant and recharge the unit.
    Check the user interface display.
    Check the transmission wiring between the indoor and outdoor units.
    #Daikin #VRV #bonmj

Komentáře • 60

  • @Didik-cq8wy
    @Didik-cq8wy Před rokem +1

    Trimakasi Bapak berkat ilmu AC yg di beritahu cara cari kerusakan trimakasih.

    • @BonMj
      @BonMj  Před rokem

      Sama sama master

  • @albertarmecin6671
    @albertarmecin6671 Před 3 lety +1

    Thanks Mr. Bon for the video

  • @nguyennam880
    @nguyennam880 Před 2 lety +1

    Hi sir. Im from daikin vn, nice to meet you.

  • @aryatutor69
    @aryatutor69 Před 3 lety +1

    good job, thanks for ure experience share.

  • @unknownsf0
    @unknownsf0 Před 3 lety +2

    you’re awesome man thank you

  • @salimullahkhan5594
    @salimullahkhan5594 Před 3 lety

    Thinks sir your video information very good

  • @mujeeb7100
    @mujeeb7100 Před 3 lety +1

    Great video , sir.

  • @brandonunderwood4224
    @brandonunderwood4224 Před 2 lety +2

    I have e4 error code but system has 228psi how do I determine if it's the pcb or switch. Thanks

    • @BonMj
      @BonMj  Před 2 lety +1

      Check the low pressure switch or low pressure sensor

  • @john-cj6ml
    @john-cj6ml Před 2 lety +1

    How many hours you guys conduct vacuuming on the system ?

  • @vinodkumar7l963
    @vinodkumar7l963 Před 5 měsíci +1

    Sir cooling only vrv show U3-10 error what is the reason

    • @BonMj
      @BonMj  Před 5 měsíci

      Try test run

  • @erichsh58
    @erichsh58 Před 2 lety +1

    Hi, can an E4 be interrmitent? Once in a while I will get this error, and when it happens, I turn off the power to the indoor unit (using the thermostat) wait a few minutes, then turn it on. It can be several days or a week or more until it happens again. When I do get the error, other indoor thermostats show the same message. Can I damage the compressor if I keep doing it, The whole system is less than two years old. Thank you.

    • @BonMj
      @BonMj  Před 2 lety

      Do you check the refrigerant pressure.

  • @rolandoperez1168
    @rolandoperez1168 Před 2 lety +1

    How to determine if the low pressure switch is okay what reading should i get

    • @BonMj
      @BonMj  Před 2 lety +1

      Pressure switch just a switch,check continuity

  • @chandansahani8242
    @chandansahani8242 Před 3 lety

    Please make a video on inverter analyzer testers please

  • @karaors8970
    @karaors8970 Před 2 lety +1

    🇹🇷👍

  • @johnnyroxannebautista2063

    Hello sir Bon gud day.
    i've watched the video.
    When the leak is repaired and refrigerant was injected already accordance with the amount needed,
    Is the error E4-01 will eventually vanish away or need to reset?

    • @BonMj
      @BonMj  Před 2 lety

      When on back outdoor power supply,will back to normal.
      Normally we will press return button after on outdoor power supply to reset the system.

  • @todmabotesimbine6588
    @todmabotesimbine6588 Před 2 lety +1

    Hi Bon..I heve H4 Master Mode Fault code.What can that be?

    • @BonMj
      @BonMj  Před 2 lety +1

      May low pressure switch open

  • @lokeshlokeshkumar2107
    @lokeshlokeshkumar2107 Před 2 lety +1

    Hai sir...
    Plz VRV X H3 errors problam haw to analyzing...

    • @BonMj
      @BonMj  Před 2 lety

      Use multi meter check high pressure switch. (Close is normal, open is faulty)

  • @mujeeb7100
    @mujeeb7100 Před 3 lety +1

    Hi sir , pls tell how to use Transistor check mode for L5 error in daikin vrv X. 12hp unit.

    • @BonMj
      @BonMj  Před 3 lety +2

      L5 may inverter compressor or inverter pcb problem, check the output voltage

    • @mujeeb7100
      @mujeeb7100 Před 3 lety

      Sir how to check out put voltage in inverter pcb. With compressor or without compressor.

    • @BonMj
      @BonMj  Před 3 lety +1

      @@mujeeb7100 if outdoor fan motor running, use claim meter to check inverter compressor ruunig amp

    • @mujeeb7100
      @mujeeb7100 Před 3 lety +1

      @@BonMj sir yes fan motor starts but compressor UVW is not drawing any current . After three attempts indoor display shows L5. And inverter drive is not giving any kind of voltage AC and DC.

    • @BonMj
      @BonMj  Před 3 lety +1

      @@mujeeb7100 should inverter pcb faulty

  • @isniaga4927
    @isniaga4927 Před 2 lety +1

    Hi sir...my name suhaimi from Kuala Lumpur..I have a problem my customer acond multisplit Daikin inverter model RZR 71...the outdoor error is high pressure protector work or freeze up in operating or stand by unit I look at cover outdoor.Can you help to solve this problem..tq sir

    • @BonMj
      @BonMj  Před 2 lety

      Try check the high pressure sensor

    • @BonMj
      @BonMj  Před 2 lety

      czcams.com/video/FWnF1G7l_nE/video.html
      Follow this reading

  • @mohsinsatti.470
    @mohsinsatti.470 Před 2 lety +1

    E4 eror dikin falt wht problm

    • @BonMj
      @BonMj  Před 2 lety

      Check gas pressure

  • @nardgallarde8835
    @nardgallarde8835 Před 2 lety +1

    Is this have an orifice?

    • @BonMj
      @BonMj  Před 2 lety

      No.is installer never tighten the nut properly.

  • @user-rc1lu6ig1q
    @user-rc1lu6ig1q Před 2 lety +1

    师傅,那个检测软件是什么?

    • @BonMj
      @BonMj  Před 2 lety +1

      Daikin Air Conditioner
      Monitor Tool
      Ver 1.1.32

  • @rezkypradipta5228
    @rezkypradipta5228 Před 22 dny

    Halo sir
    Eror e4-02
    Bagaimana solusinya?
    Terimakasih

    • @BonMj
      @BonMj  Před 22 dny

      Sifu E4-02 slave 1 low pressure
      Check gas, low pressure sensor Dan pressure switch

  • @donovangayle1119
    @donovangayle1119 Před rokem +1

    Greetings. Can you send me a video that show me how to use the service checker

  • @ayubbahaddur8034
    @ayubbahaddur8034 Před 3 lety +1

    Can i topup the R410 refrigerant in vrv system

    • @BonMj
      @BonMj  Před 3 lety

      By refrigerant manufacture notice,need to clear all the refrigerant in the system and recharging if got leakage .
      If customer agree to pay you just follow.
      If you ask can top up or not,i think a lot off the technician do it.

    • @ayubbahaddur8034
      @ayubbahaddur8034 Před 3 lety +1

      @@BonMj thank you sir

  • @m.haslam8495
    @m.haslam8495 Před 2 lety +1

    That's an expensive mistake. Leaking from a flare nut.

  • @user-of7ub3sl5v
    @user-of7ub3sl5v Před 2 lety +1

    L4-01