How to solve error E4-01 Daikin VRV4
Vložit
- čas přidán 26. 08. 2024
- Brand : Daikin VRV4(A)
model : RXQ10AYM
Error : E4-01
Description of Fault
Master outdoor unit low pressure switch activation.
Detail of Fault
This is stating that there has been a low pressure error on the Master outdoor unit.
This could have been caused by a blockage in the pipe work or a possible shortage of refrigerant.It could be due to a fault with the low pressure sensor/switch.
Error : E4
Description of Fault
Low pressure switch activation.
Detail of Fault
This is stating that there has been a low pressure error on the system.
This could have been caused by blockage in the pipe work or a possible shortage of refrigerant. It could also be due to a fault with the low pressure sensor/switch.
Solution
Open the valve.
Check the amount of refrigerant and recharge the unit.
Check the user interface display.
Check the transmission wiring between the indoor and outdoor units.
#Daikin #VRV #bonmj
Trimakasi Bapak berkat ilmu AC yg di beritahu cara cari kerusakan trimakasih.
Sama sama master
Thanks Mr. Bon for the video
Thanks
Hi sir. Im from daikin vn, nice to meet you.
Thanks
good job, thanks for ure experience share.
Thanks
you’re awesome man thank you
Thanks
Thinks sir your video information very good
Great video , sir.
Thanks
I have e4 error code but system has 228psi how do I determine if it's the pcb or switch. Thanks
Check the low pressure switch or low pressure sensor
How many hours you guys conduct vacuuming on the system ?
500 micron
Sir cooling only vrv show U3-10 error what is the reason
Try test run
Hi, can an E4 be interrmitent? Once in a while I will get this error, and when it happens, I turn off the power to the indoor unit (using the thermostat) wait a few minutes, then turn it on. It can be several days or a week or more until it happens again. When I do get the error, other indoor thermostats show the same message. Can I damage the compressor if I keep doing it, The whole system is less than two years old. Thank you.
Do you check the refrigerant pressure.
How to determine if the low pressure switch is okay what reading should i get
Pressure switch just a switch,check continuity
Please make a video on inverter analyzer testers please
🇹🇷👍
Thanks
Hello sir Bon gud day.
i've watched the video.
When the leak is repaired and refrigerant was injected already accordance with the amount needed,
Is the error E4-01 will eventually vanish away or need to reset?
When on back outdoor power supply,will back to normal.
Normally we will press return button after on outdoor power supply to reset the system.
Hi Bon..I heve H4 Master Mode Fault code.What can that be?
May low pressure switch open
Hai sir...
Plz VRV X H3 errors problam haw to analyzing...
Use multi meter check high pressure switch. (Close is normal, open is faulty)
Hi sir , pls tell how to use Transistor check mode for L5 error in daikin vrv X. 12hp unit.
L5 may inverter compressor or inverter pcb problem, check the output voltage
Sir how to check out put voltage in inverter pcb. With compressor or without compressor.
@@mujeeb7100 if outdoor fan motor running, use claim meter to check inverter compressor ruunig amp
@@BonMj sir yes fan motor starts but compressor UVW is not drawing any current . After three attempts indoor display shows L5. And inverter drive is not giving any kind of voltage AC and DC.
@@mujeeb7100 should inverter pcb faulty
Hi sir...my name suhaimi from Kuala Lumpur..I have a problem my customer acond multisplit Daikin inverter model RZR 71...the outdoor error is high pressure protector work or freeze up in operating or stand by unit I look at cover outdoor.Can you help to solve this problem..tq sir
Try check the high pressure sensor
czcams.com/video/FWnF1G7l_nE/video.html
Follow this reading
E4 eror dikin falt wht problm
Check gas pressure
Is this have an orifice?
No.is installer never tighten the nut properly.
师傅,那个检测软件是什么?
Daikin Air Conditioner
Monitor Tool
Ver 1.1.32
Halo sir
Eror e4-02
Bagaimana solusinya?
Terimakasih
Sifu E4-02 slave 1 low pressure
Check gas, low pressure sensor Dan pressure switch
Greetings. Can you send me a video that show me how to use the service checker
Can i topup the R410 refrigerant in vrv system
By refrigerant manufacture notice,need to clear all the refrigerant in the system and recharging if got leakage .
If customer agree to pay you just follow.
If you ask can top up or not,i think a lot off the technician do it.
@@BonMj thank you sir
That's an expensive mistake. Leaking from a flare nut.
Yes
L4-01
Check inverter board heat sink sensor
@@BonMj thanks