How to solve error code F4 | Wet Alarm | Daikin VRV4

Sdílet
Vložit
  • čas přidán 10. 03. 2022
  • Brand : Daikin
    model : RXQ8AYM (CU)
    model : FXMQ140PAVE (FCU)
    Symptoms : Blinking and error F4
    Cause : One of the indoor unit gas temperature thermistor reading abnormal.
    Action : Check CU error and indoor error using wire remote control.
    Check thermistor reading.
    Replace indoor gas temperature thermistor R3T.
    Test run .
    Method Of Error Detection
    In cooling operation, detect the condition under which liquid refrigerant returns to the compressor, according to the temperature and pressure of each part.
    Error Decision Conditions
    When the following wet state continues for a period of 90 minutes, an alert is issued. An error is defined for 120 minutes.
    * Wet state in outdoor units.
    When the following wet state continues for a period of 45 minutes, an alert is issued.
    * Wet state in some indoor units.
    Supposed Cause
    * Defective suction pipe thermistor.
    * Defective discharge pipe thermistor.
    * Defective high pressure sensor.
    * Defective indoor unit electronic expansion valve.
    * Dirty air filter.
    #bonmj #daikin #vrv4

Komentáře • 86

  • @briansmith3681
    @briansmith3681 Před 2 lety +1

    You always do a great job at your videos, keep up

  • @GodCzPl
    @GodCzPl Před 2 lety +1

    Thanks for your videos, I can really learn something from these.

  • @anbasellamuthu3658
    @anbasellamuthu3658 Před 2 lety +2

    Good job thanks for the info 🙏

    • @BonMj
      @BonMj  Před 2 lety

      Thanks bro🙏

  • @brandonle4930
    @brandonle4930 Před 2 lety +1

    Good finding Bon!

  • @CT-vm4gf
    @CT-vm4gf Před 2 lety +1

    You’re a very good technician 👍🏽

  • @peramaraj2763
    @peramaraj2763 Před 2 lety +1

    Very useful sir your latest update video

  • @CCL13984
    @CCL13984 Před 9 měsíci +2

    Thx,sir good video

  • @16valve64
    @16valve64 Před 2 lety +1

    Thanks a lot bon

  • @matazglb5346
    @matazglb5346 Před 2 lety +1

    Thanks you ☺

  • @daniloborges4869
    @daniloborges4869 Před 6 měsíci +1

    Obrigado , ajudou muito f4/02

  • @alonsoacosta8545
    @alonsoacosta8545 Před 2 lety +1

    Gracias por la información. Eres el mejor.

  • @BonMj
    @BonMj  Před 2 lety +1

    Thanks for watching my video.
    Please Like, Share and Subscribe .
    🙏🙏🙏🙏

  • @goparismail9727
    @goparismail9727 Před 2 lety +2

    trimakasih ilmu yah mr bon sukses selalu bos ku thak you goood👍👍👍👍 mantapppp

    • @BonMj
      @BonMj  Před 2 lety +1

      Terima kasih master.
      Tolong share kawan kawan ya🙏🙏

  • @salimullahkhan5594
    @salimullahkhan5594 Před 2 lety +1

    thinks sir g thinks

  • @peramaraj2763
    @peramaraj2763 Před 2 lety +3

    I have one doubt sir DAIKIN vrv-3 indoor ducted unit set point -16 cut off the valve and set point -30 cut off the valve but set -24 can't cut off the valve more cooling the off what is the issue sir recently replaced EEV

    • @peramaraj2763
      @peramaraj2763 Před 2 lety

      I have one doubt sir DAIKIN vrv-3 indoor ducted unit set point -16 cut off the valve and set point -30 cut off the valve but set -24 can't cut off the valve more cooling the off what is the issue sir recently replaced EEV

  • @karthickkeya7078
    @karthickkeya7078 Před 2 lety

    Thank you sir👍👍
    We need more info about wirless adapter
    How to use it, and how to find it the issues

  • @sahiljuned3762
    @sahiljuned3762 Před 2 lety

    Hi boss please one video outdoor airnet address just demo

  • @byyou1000
    @byyou1000 Před 2 lety +1

    hello sir., can you i form the normal themperature range.? for the liquid and gas.. thank you

  • @syaha-dw9pj
    @syaha-dw9pj Před rokem +1

    Hi Mr Bon,nk tnya klau sensor c4 rosak adkah boleh buat eev fully open jgak?

    • @BonMj
      @BonMj  Před rokem

      Selamat pagi, kena tengok keadaan, check c4 reading dulu.kalau reading kecil mungkin, boleh juga eev rosak punca eev fully open.

  • @user-kf1ml3hw9q
    @user-kf1ml3hw9q Před 10 měsíci +1

    Hi, my house unit is also having this issue but it is not happening daily, currently 3 weeks. Why is this so? Do you help to do checks? We used to have this issue in 2021 and Daikin is unable to find out root cause till they changed the entire PCB outdoor. Before this, they changed the valve indoor. What is the impact of not fixing this F4 alarm?

    • @BonMj
      @BonMj  Před 10 měsíci

      Need collect data and check any parts reading abnormal

    • @user-kf1ml3hw9q
      @user-kf1ml3hw9q Před 10 měsíci

      previously daikin collected data for 1 full week and cannot find a conclusion till they changed the PCB outdoor. Now this issue comes back again but not on a daily basis. However there is still aircon during the blinking light period. After we turn on and off, the light stopped blinking.

  • @AA-su7up
    @AA-su7up Před 2 lety +1

    Hi I have problems putting in back my blower wheel into the shaft for my mitsubishi starmex aircon. Previously was stuck and I took it out, maybe I didnt screw the shaft properly. But now it could not be put in properly. Thanks. Is there any way to put it back smoothly?

    • @BonMj
      @BonMj  Před 2 lety

      Check the fan motor shaft alignment

    • @BonMj
      @BonMj  Před 2 lety

      czcams.com/video/GXLTcSNI3v8/video.html

    • @AA-su7up
      @AA-su7up Před 2 lety +1

      @@BonMj Hi thanks for the fast reply, but I tried all angle plus putting lubricant, the blower wheel can only go in half the shaft, I see through the hole of the blower wheel and there is nothing stuck... feel the shaft and visual check also dont seem to have any protruding...

    • @BonMj
      @BonMj  Před 2 lety

      @@AA-su7up try to remove the blower screw and push in or the shaft uneven

  • @yipgary6073
    @yipgary6073 Před rokem +1

    請教Bon,如3代大金VRV,室內故障碼F4,會是那裡出錯?

    • @BonMj
      @BonMj  Před rokem

      先检查indoor eev 还有thermistor

  • @jakesales7321
    @jakesales7321 Před 2 lety +1

    What was wrong with office ac? Remote flashing.

    • @BonMj
      @BonMj  Před 2 lety +1

      Remote flashing and error F4, indoor thermistor faulty .

  • @toufikmatib9855
    @toufikmatib9855 Před 2 lety +1

    Hello Boj hope you well Thanks for the video .
    Is it same for the vrv3 ?.
    Please how do I know if example a error code appear on the control board , is the fault will be in indoor unit or at outdoor unit (condenser).
    Many thanks
    T.Matib

    • @BonMj
      @BonMj  Před 2 lety

      What is the error?

    • @toufikmatib9855
      @toufikmatib9855 Před 2 lety +1

      @@BonMj Hello Thank you for replying to me ,the error code is F4 on VRV3.
      Also in general when I get error code flashing on controller how do I know is a fault on outdoor unit or on indoor unit.
      Many thanks
      Have good day Bon .
      T.Matib

    • @BonMj
      @BonMj  Před 2 lety +1

      @@toufikmatib9855 F4 normally is indoor EEV problem.
      Is fully open

    • @toufikmatib9855
      @toufikmatib9855 Před 2 lety +1

      @@BonMj Thank you Bon

    • @toufikmatib9855
      @toufikmatib9855 Před 2 lety +2

      Hello Boj I'm having trouble on this vrv3 with code error E2 so my read resistance is between white and red is 12mega ohm and red and black is 96 ohm
      Ombiante temperature is around 40 degree what do you think about this sensor? as I don't have new one to compare
      Thank you Bon

  • @karaors8970
    @karaors8970 Před 2 lety +1

    hi bon nice Job bro.
    J4 error code for video pls. Thnx.

  • @peramaraj2763
    @peramaraj2763 Před 11 měsíci +1

    Normally F4 error code is outdoor side or indoor side issue

    • @BonMj
      @BonMj  Před 11 měsíci

      Check Fcu eev

  • @osailoliveira1489
    @osailoliveira1489 Před rokem

    Tenho uma máquina daykin vrf, são 7 máquinas, 4 k7 e 3 piso teto , já limpei as bombas de treno ,o código PJ fica a.onde , na unidade evaporadora ou na condensadora?

    • @BonMj
      @BonMj  Před rokem

      Do you replace any pcb.
      PJ normally is model setting issue

  • @gothandaraj860
    @gothandaraj860 Před rokem +1

    What is error f4-05 Daikin vrv

    • @BonMj
      @BonMj  Před rokem

      Check indoor EEV

    • @gothandaraj860
      @gothandaraj860 Před rokem +1

      Okay bon there is totally 7 indoor units and this model ac 18 hp &16hp master and slave unit how to check

    • @BonMj
      @BonMj  Před rokem +1

      @@gothandaraj860 try on half of the fcu in cool mode and half in fan mode.
      If the fcu in fan mode still cold,mean the eev got problem

  • @raremember331
    @raremember331 Před rokem +1

    Permasalahannya di indoor atau outdoor ?

  • @juliojulio6295
    @juliojulio6295 Před 2 lety +1

    Eror kode e9 24 diagnosis mr.

  • @janshaw5472
    @janshaw5472 Před 8 měsíci

    F4-02师傅

    • @BonMj
      @BonMj  Před 8 měsíci

      F4 check indoor EEV

  • @muhammadarifbinhamdan6027

    Saya punya unit vrv3 keluar error F4, saya check Outdoor unit, inverter compressor sejuk kenapa ye?

    • @BonMj
      @BonMj  Před rokem

      Selamat pagi,F4 biasa nya salah satu indoor EEV rosak, EEV buka habis.check mana satu indoor yang terlalu sejuk,itu mungkin yang rosak.

  • @vishnurajak3349
    @vishnurajak3349 Před 8 měsíci +1

    Sir video hindi me. Daliye

  • @torushchannel5830
    @torushchannel5830 Před 3 měsíci +1

    Pengalaman.e peno iku

  • @-maynenkhitrucvitoquangkha4748
    @-maynenkhitrucvitoquangkha4748 Před 6 měsíci +1

    Dear Sir,
    I am a daikin air conditioning technician, I have followed your channel and learned a lot of useful things. Thank you for sharing that useful information.
    By the way, can you let me know your email or somehow contact you directly so that you can advise me when I encounter any problems?
    I really hope to get your help.

    • @BonMj
      @BonMj  Před 5 měsíci

      bonmj81@gmail.com