Daikin | How to solve error code U3 after replacing new main pcb |VRVA

Sdílet
Vložit
  • čas přidán 26. 08. 2024
  • Brand : Daikin
    model : RXQ16AYM
    Replace new main PCB.
    Important, for Daikin VRV-A ,after replacing new PCB, must conduct Auto Charge before
    test run.
    #daikin #bonmj #vrv4

Komentáře • 152

  • @paulbrown1079
    @paulbrown1079 Před 2 lety +4

    Wouldn't mind shadowing you for a few weeks with fault finding on different systems 👍👍

  • @hossainurrahman6700
    @hossainurrahman6700 Před 2 lety +2

    great teacher nobody like him for me
    thanks

  • @vladimirmakhney5407
    @vladimirmakhney5407 Před 2 lety +1

    Hi ,this video is just in time, I will have to change the main board to Daikin. Thanks

    • @BonMj
      @BonMj  Před 2 lety +1

      This is vrv4- A , auto charge system.

  • @bago-uw2cw
    @bago-uw2cw Před 6 měsíci +1

    -I'm Myanmar Citizen.
    -I want to work and learn from you.
    -I'm in Singapore now!

  • @rogelebro3456
    @rogelebro3456 Před 2 lety +1

    It is a very nice tutorial, Sir Bon...I've learned another trouble and how to rectify it..thanks..

  • @user-pb1dz6bd4s
    @user-pb1dz6bd4s Před 5 měsíci +1

    mr bon juat wanna ask when i want to do auto charge should i open valve to release gas from compressor first or dont open the valve and auto charge it and then release the gas from compressor ?

  • @narayanaya5519
    @narayanaya5519 Před rokem +2

    Could you please let me know the details about that copper line connected to pcb

  • @deshanabeysekara5124
    @deshanabeysekara5124 Před rokem +1

    your videos big help for us.Thank you sir...

  • @CHOPPA78
    @CHOPPA78 Před rokem +1

    Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?

  • @sweetswocas7646
    @sweetswocas7646 Před 3 měsíci +1

    Thank You

    • @BonMj
      @BonMj  Před 2 měsíci

      You're welcome

  • @ismaielchaudhary
    @ismaielchaudhary Před 9 měsíci +1

    Sir what would be reason Daikin VRV liquid line is freezing, I check solenoid and sensors and ohms reading look acceptable.

  • @taqmeemalam8852
    @taqmeemalam8852 Před 2 lety +1

    ❤️❤️

  • @juliocesarherrerasierra3074

    exelente pagina muchas gracias

  • @suhanurrahman9822
    @suhanurrahman9822 Před 10 měsíci +1

  • @dicksonfu8604
    @dicksonfu8604 Před rokem +1

    Why need to do freon charging when replacing the PCB?

  • @sarfarajshaikh4582
    @sarfarajshaikh4582 Před 2 lety +1

    As always
    Great jo brother 👍

  • @jiezhang730
    @jiezhang730 Před rokem +1

    Hi, May I ask for Daikin R407c, ds2 and ds3 which button should be on?

  • @BonMj
    @BonMj  Před 2 lety

    Correction.
    The model is RXQ16AYM.
    Thanks

  • @sonukurmi305
    @sonukurmi305 Před rokem +1

    Hi sir please tell me 99 settings video

  • @Marcelo.M.Quaiotti.01
    @Marcelo.M.Quaiotti.01 Před rokem +1

    Hi. Do you have U3-10 in the manual?

  • @Actechwala
    @Actechwala Před 2 lety +1

    Superb sir.

  • @Ramprasad-fo5ui
    @Ramprasad-fo5ui Před 2 lety +1

    So great video

  • @electrolatif
    @electrolatif Před rokem +1

    Thank you Mr Bon to share you knowledge

  • @VinodKumar-ix7rt
    @VinodKumar-ix7rt Před rokem +1

    Thank you sir❤❤

  • @voonkengchong5465
    @voonkengchong5465 Před 2 lety +1

    Do u conduct any course for water cooled package / air cooled package unit?

  • @JayaKumar-sj3oo
    @JayaKumar-sj3oo Před 2 lety +1

    Thank you sir

  • @NaimKhan-tv4rz
    @NaimKhan-tv4rz Před rokem +1

    Great 👍sir

  • @alanwang2900
    @alanwang2900 Před 2 lety +2

    Great video, by the way, when auto charge active, is this gonna cause the system over charged?

    • @BonMj
      @BonMj  Před 2 lety +1

      When new air con is done,u can gauge the amount of refrigerant needed to be charged by measuring the pipe lenght and pipe size.
      Auto charge can only charge 4kg of refrigerant.

    • @BonMj
      @BonMj  Před 2 lety +1

      For this case the the auto charge just run for awile and stop.just a bit charge in only

    • @CHOPPA78
      @CHOPPA78 Před rokem

      Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?

  • @patrociolacic6088
    @patrociolacic6088 Před rokem +1

    MERCI GREAT JOB

  • @CircinusMusic
    @CircinusMusic Před 2 lety +1

    Sir if panel fault no need gas recharge? Just to observe the to1 to po9 only?

    • @BonMj
      @BonMj  Před 2 lety +1

      After reset if U3 , u need to do .

  • @engineeringpteltdshengheng833

    Thanks a lot

  • @Lee-mu2jc
    @Lee-mu2jc Před 2 lety +1

    老板谢谢你每次用心讲解
    如果是换其他电板也是一样要这样做吗
    也是vrv4 还是只是换你这样的电板才需要这样做 谢谢

    • @BonMj
      @BonMj  Před 2 lety +1

      VRV4 有两个款
      1)有Auto charge
      2)没有Auto charge
      这个video 是 vrv4 有auto charge,所以要这样做。
      如果没有auto charge, 只需要test run 就好。

    • @Lee-mu2jc
      @Lee-mu2jc Před 2 lety +1

      @@BonMj 老板要怎样分辨哪一个款式是有没有auto charge谢谢

    • @BonMj
      @BonMj  Před 2 lety +1

      @@Lee-mu2jc你注意看service valve那边(check gas 的地方右手边),有个进gas 的service port.
      你注意看我video,蓝色pipe就绑在那个service port.

  • @pappykwabee5296
    @pappykwabee5296 Před 2 lety +1

    I have worked on the vrv 2 and 3 a lot but I have not worked on vrv 4 yet.Please why do you have to do all these settings(auto charge and test run) after you have replaced the main Pcb.On vrv 2 and 3
    Is straight forward you don't need to do anything.
    What is auto-charge by the way?Is it something to do with the refrigerant being recharged into the system?
    PLEASE advise.thank you

    • @BonMj
      @BonMj  Před 2 lety

      VRV 4 auto charge system, when you replace the main pcb, this procedure is compoundsery. by manufacturer.

  • @doninovithendrianto1269
    @doninovithendrianto1269 Před 2 lety +1

    Halo Mr.bon,untukVRV A apabila ada additional indoor perlu melakukan prosedur Auto charge juga ?

  • @karaors8970
    @karaors8970 Před 2 lety +1

    Hello nice Job bro 🇹🇷👍🛠️

  • @joycetan4180
    @joycetan4180 Před 2 lety +1

    Hi I got the same model and it show f6 error on the peu controller. Can advise please? Thanks I advance

    • @BonMj
      @BonMj  Před 2 lety

      May system overcharge
      Or check liquid pipe thermistor

  • @selvarasumanikandan7646
    @selvarasumanikandan7646 Před 2 měsíci +1

    how to do troubleshoot daikin vrv 3 cu side ice

  • @ersham13
    @ersham13 Před 2 lety +1

    What was the error meaning and wht did we get the error
    Just reset it and pretend nothing is wrong?

    • @BonMj
      @BonMj  Před 2 lety

      U3-Test run execution failure.
      This error appear when we do the test run after replace new pcb.
      Try it twice is same error U3.
      Use the new installation method, Auto charge and after that test run.
      The unit but to normal.

  • @laxmanbhaloriya729
    @laxmanbhaloriya729 Před rokem +1

    Explain sir Aircon bypass settings

  • @cutacatas9207
    @cutacatas9207 Před 2 lety +1

    Bagus ah you...

    • @BonMj
      @BonMj  Před 2 lety

      Terima kasih master

  • @syaha-dw9pj
    @syaha-dw9pj Před rokem +1

    Hi Mr Bon, if a model RXQ14TY1 VRV4 after replace the main pcb are we can test run without auto charge first?

    • @BonMj
      @BonMj  Před rokem

      Depend by error, if no error no need

  • @geralddiaz5491
    @geralddiaz5491 Před 7 měsíci +1

    Hi mr.bon please help we was replacing the main pcb.after that ua is appear please help.what the next step

  • @faresimrod3483
    @faresimrod3483 Před rokem +1

    Thank you very much sir, What about error code LC - 14 . AND F6 -02

    • @BonMj
      @BonMj  Před rokem +1

      LC-14 transmission error master cu inverter pcb

    • @faresimrod3483
      @faresimrod3483 Před rokem +1

      @@BonMj thank you very much.

    • @faresimrod3483
      @faresimrod3483 Před rokem

      Hi mr bon, i have to change both the INV1 pcb and the CU pcb but the problem Still exist, do you have an idea plz

  • @traduccion1024
    @traduccion1024 Před 2 lety +1

    What happens when the three displays are fixed but do not turn off?

    • @BonMj
      @BonMj  Před 2 lety

      Comunication problem

  • @choonhaukwa1878
    @choonhaukwa1878 Před 2 lety +1

    请问Auto charge 出现 P9 过后,是不是就说明gas已经足够,不用再进了?

    • @BonMj
      @BonMj  Před 2 lety +1

      其实auto charge 最多可以进4kg.
      如果新装的VRV要先算pipe的长度,在auto charge之前要先进gas,然后再auto charge.
      如果像这个video,只是换电板,程序上一定要做auto charge,但是过程是很快的,应为gas是足够的。
      对,P9是完成了auto charge.

  • @SasiKumar-gj3jg
    @SasiKumar-gj3jg Před 2 lety +1

    What is the reason for E2 error in Daikin vrv4 outdoor unit and how to rectify?and also three times second inverter compressor changed but again second inverter compressor grounded

    • @BonMj
      @BonMj  Před 2 lety

      E2 you need to check the high pressure switch and high pressure sensor reading.
      Compressor replace 3 times!suggest you release all the gas,make the pipe calculation ,and recharge gas with correct quantity.

    • @CHOPPA78
      @CHOPPA78 Před rokem

      Release means reclaim in to a reclaim cylinder , don't want to release" could be misunderstood !

  • @aircondbala
    @aircondbala Před 2 lety +1

    super nice 👌👌👌

  • @narayanaya5519
    @narayanaya5519 Před rokem +1

    What is the voltage between f1f2

  • @Omprakash-cg8zo
    @Omprakash-cg8zo Před 2 lety +1

    Hello brother
    We are getting UF 01 error code during test run mode
    My mchine is new vrv x
    Can it be problem if we do not provide earthing

    • @BonMj
      @BonMj  Před 2 lety

      Check all the valve make sure is open.
      Restart your test run

  • @kcomfortsystemshvac7060
    @kcomfortsystemshvac7060 Před 2 lety +1

    Bon,,,, very 👍 job,,, mate,,,,, I have question. Those DS1 and DS2 setting what there for ? Can you help me that please

    • @BonMj
      @BonMj  Před 2 lety

      Thanks.
      This pcb for all model.
      DS1 and DS2 is model setting

    • @kcomfortsystemshvac7060
      @kcomfortsystemshvac7060 Před 2 lety +1

      @@BonMj thanks Bon…. I really appreciate!!!👍

    • @BonMj
      @BonMj  Před 2 lety

      @@kcomfortsystemshvac7060 welcome

  • @suryavns7338
    @suryavns7338 Před 2 lety

    Very nice video sir,u2 error code in what is problem,thank you sir

    • @BonMj
      @BonMj  Před 2 lety

      Check inverter pcb voltage

  • @salimagwan9672
    @salimagwan9672 Před 2 lety +1

    RXYMQ8ARY16
    Will auto gas charging be done in this model sir

    • @BonMj
      @BonMj  Před 2 lety

      Sorry.this model i not sue,but in the cu should have the auto charge instruction if this is auto charge system

  • @hvacandvrvspecialvedoindus7891

    🙏🙏🙏

  • @hvacandvrvspecialvedoindus7891

    Only mastar dip swich setting

  • @hvacandvrvspecialvedoindus7891

    Help sar

  • @vipinkumar5098
    @vipinkumar5098 Před 2 lety +1

    Please tell me
    E3 daikin vrv 3

    • @BonMj
      @BonMj  Před 2 lety

      Check high pressure switch

  • @chongyawteng8297
    @chongyawteng8297 Před 2 lety +1

    老师请问RSQ14TAYM,出U4. 3fcu,第一台没 连接后两台会走,第一台给他一对一会走,三台连接等一台出U4,CU,PCB可以reset故障吗?我有打电话去间,他们说reset电 就ok了,电我关了两天喽!都不可以😂😂😂

    • @BonMj
      @BonMj  Před 2 lety

      是关CU的电对吧!
      开回,按reset button 超过5秒

    • @BonMj
      @BonMj  Před 2 lety

      我比较担心是comunication wire 没有接对

    • @BonMj
      @BonMj  Před 2 lety

      1对1=可以
      1对2=可以
      3台接一起不可以。
      你花点时间check 3台fcu comunication wire 有接对吗

    • @chongyawteng8297
      @chongyawteng8297 Před 2 lety

      @@BonMj cu/fcu都关2天

    • @chongyawteng8297
      @chongyawteng8297 Před 2 lety

      @@BonMj 都连接对。

  • @Sundar_ramanujam_
    @Sundar_ramanujam_ Před 11 měsíci +1

    How could you ensure pcb board faulty? Can you elaborate more?

  • @rogelebro3456
    @rogelebro3456 Před 2 lety +1

    Good Day Sir Bon...How can you rectify the Error Code U9 on Daikin VRV 4 unit? ..If you have a video for this error, its better....Thanks

    • @BonMj
      @BonMj  Před 2 lety +1

      U9 mean other fcu got problems

    • @rogelebro3456
      @rogelebro3456 Před 2 lety +1

      @@BonMj Yes Sir...some of the units had a problem

  • @Ramprasad-fo5ui
    @Ramprasad-fo5ui Před 2 lety +1

    And English after use hind best long before

  • @alanwong2761
    @alanwong2761 Před 2 lety

    Mr Bon isn't need to auto charging first before test run for all VRV 4 models?

    • @BonMj
      @BonMj  Před 2 lety +1

      No, for Auto Charge system only, depend by model

    • @alanwong2761
      @alanwong2761 Před 2 lety +1

      Thanks your reply Mr Bon

  • @hvacandvrvspecialvedoindus7891

    Bon sar pleas help me u1-16

  • @MYDUBAI78628
    @MYDUBAI78628 Před 2 lety +1

    Is machine run automatically after test run ??

    • @BonMj
      @BonMj  Před 2 lety

      After test run aircon stop running.
      You need to on indoor .

    • @MYDUBAI78628
      @MYDUBAI78628 Před 2 lety +1

      @@BonMj understood

    • @MYDUBAI78628
      @MYDUBAI78628 Před 2 lety +1

      @@BonMj Bon I am h fresher with 1 year experience can i get job in Singapore as Aircon technician from abroad

    • @BonMj
      @BonMj  Před 2 lety

      @@MYDUBAI78628 👍

    • @MYDUBAI78628
      @MYDUBAI78628 Před 2 lety +1

      @@BonMj guide m sir how to i apply from abroad

  • @hvacandvrvspecialvedoindus7891

    Please sar 🙏😊

  • @bulbmandai2024
    @bulbmandai2024 Před 2 lety +1

    Sir how to fix daikin vrv 3 ac AH error code

    • @BonMj
      @BonMj  Před 2 lety +1

      This hot water system?

    • @bulbmandai2024
      @bulbmandai2024 Před 2 lety +1

      Not hot water system.

    • @BonMj
      @BonMj  Před 2 lety +1

      @@bulbmandai2024please check indoor pcb

    • @bulbmandai2024
      @bulbmandai2024 Před 2 lety +1

      Ok sir is this complint about indoor section?

    • @BonMj
      @BonMj  Před 2 lety +1

      @@bulbmandai2024 ya.may be

  • @hvacandvrvspecialvedoindus7891

    Bon sar vrvx u7 11

    • @BonMj
      @BonMj  Před 2 lety

      Check outdoor to outdoor unit connections

  • @nirajgalthariya
    @nirajgalthariya Před 2 lety +1

    Hello
    Why am I in your country I can get a job

  • @mohamedelsadk7362
    @mohamedelsadk7362 Před 2 lety

    My name is Mohamed Al-Sadiq Mohamed, VRV refrigeration and air conditioning technician. I am from Egypt. I want to travel to work and work hard. I need help

  • @janshaw5472
    @janshaw5472 Před 2 lety +1

    VRV 感觉好难(⊙o⊙)for me

    • @BonMj
      @BonMj  Před 2 lety

      不会难,换了pcb要auto charge然后再test run