Video není dostupné.
Omlouváme se.

VRV4 | Emergency maintenance | error E2-01 L5-14 J5-01

Sdílet
Vložit
  • čas přidán 24. 02. 2023
  • Brand : Daikin VRV4
    model : RXQ16TY1
    Error : E2-01, L5-14, J5-01
    #bonmj #daikin #airconditioner

Komentáře • 138

  • @jrbfyp7065
    @jrbfyp7065 Před rokem +2

    No body like sir Bon Mj and his team.
    Thank you sir for all the updated videos ,it helps a lot.
    Please don't skip ads

  • @JuanTodoli
    @JuanTodoli Před rokem +3

    Good one Bon, thoroughly diagnosis as usual 👌

  • @salimagwan9672
    @salimagwan9672 Před rokem +1

    Sir, I watch every video of yours, we are getting to learn a lot from you, we eagerly wait for your videos. To check the head compressor, we can also check setting 2-28, comp 1, comp 2 by setting checker instead of compressor

  • @Didik-cq8wy
    @Didik-cq8wy Před rokem +2

    Trimakasih bos surabaya jawa timur

  • @emersonalbano2112
    @emersonalbano2112 Před rokem +1

    Nice watching you sir bon, my idol and together your team.

  • @IMAGINE-06956
    @IMAGINE-06956 Před 11 dny +1

    Good job dear ❤

    • @BonMj
      @BonMj  Před 5 dny

      Thank you 😊

  • @reubenbugeja4066
    @reubenbugeja4066 Před rokem +1

    Thanks for sharing mr bon!If inverter board needs to be replaced this model guess tou have to empty refrigerant.

    • @BonMj
      @BonMj  Před rokem

      No need.

    • @reubenbugeja4066
      @reubenbugeja4066 Před rokem +1

      If someday you replace one,can you be so kind and share it please!! Thanks

  • @akzcreation7339
    @akzcreation7339 Před rokem +1

    Hi ,Bon nice to meet you , I also working SINGAPOR

  • @jonasalmonicar1578
    @jonasalmonicar1578 Před 3 měsíci +1

    Good day sir bon..im your number 1 viewer..i always watch your video to learn more about from you..question..can i do this bypass at VRV X series?
    Can you make a video to return the bypass from its normal operation after replace the compressor..thanks in advance..more power for your channel❤

    • @BonMj
      @BonMj  Před 3 měsíci +1

      Thanks

    • @BonMj
      @BonMj  Před 3 měsíci +1

      Single cu or multi cu

    • @jonasalmonicar1578
      @jonasalmonicar1578 Před 3 měsíci

      Multi indoor ceiling cassette..master and slave outdoor

  • @j26a24d
    @j26a24d Před rokem +1

    New York city presente 👍good video thanks you

  • @oiltubewalker
    @oiltubewalker Před rokem +3

    Q1#_ In the operation sequence of the both compressor, the INV 1 shld be fail first as compare to INV 2(lower demand), why the INV comp 2 fail in the first place??
    Q2#_ Why the guy didn't use the Megger meter to mega the INV 2 compressor? What's the normal range of the ohm of the compressor?
    Please kindly clear the doubts for us.Thanks

  • @GodofredoTalin
    @GodofredoTalin Před 2 měsíci +1

    thank you teacher Bon👍👍👍

    • @BonMj
      @BonMj  Před 2 měsíci

      You are welcome!

  • @aymanharris4599
    @aymanharris4599 Před rokem +3

    So was the inverter board bad for second compressor or the compressor was bad? You checked the ohms and they checked out ok?

  • @Raam1977
    @Raam1977 Před 3 měsíci +1

    Mr. Bon I want to tutorial from you what is the procedure
    I'm living in singapore

  • @RamKrishna-zb5ng
    @RamKrishna-zb5ng Před rokem +1

    Good work sir nice, ,🎇 from india

  • @peramaraj2763
    @peramaraj2763 Před rokem +1

    Thanks for your update video sir

  • @ankushgupta973
    @ankushgupta973 Před rokem +2

    Osm sir

  • @Didik-cq8wy
    @Didik-cq8wy Před rokem +1

    Trimakasih bos

  • @MasterJay26
    @MasterJay26 Před 5 měsíci +1

    Sir how/ where did you get service manuals of different models of Daikin unit?🙏

  • @MedridAATOUN
    @MedridAATOUN Před 11 měsíci +1

    Thank you ❤

    • @BonMj
      @BonMj  Před 11 měsíci

      Welcome!

  • @abdulthoufiq6402
    @abdulthoufiq6402 Před 5 měsíci +1

    What is mean by VRV Daikin TFA error code LC

  • @karaors8970
    @karaors8970 Před rokem +1

    Nice job bro .
    🧿🛠️🤳👍🇹🇷

  • @pjstv5833
    @pjstv5833 Před rokem +1

    Nice sir bon...

  • @Marcoguima45
    @Marcoguima45 Před rokem +1

    Good Job!😎🇧🇷

  • @chhayachhan2922
    @chhayachhan2922 Před 2 měsíci +1

    Ask how to check code 1

  • @KalabogbosyotvHenrygalicia
    @KalabogbosyotvHenrygalicia Před 2 měsíci +1

    Sir bon mj help me for may VRV4 the error is uf-01 in outdoor and L5 in indoor RXQ18TY1

    • @BonMj
      @BonMj  Před 2 měsíci

      UF check indoor LEV and thermistor
      L5 check inverter pcb and compressor

  • @arifbabulotapalkatti7643

    Thanks bro

  • @sabujsarkar7962
    @sabujsarkar7962 Před 10 měsíci +1

    Hlo sir I am very interested for your working still I am very impressed Sir. So I have a joine Your team please.

  • @mohammedshoaibsaiyed3901

    Hi mr.bon problem is compressor?? circuit?

  • @moorthilatha5739
    @moorthilatha5739 Před rokem +1

    Hi sir thank you u sharing video i have 1 question RXQ10TY1 error code E2-01
    We change high pressure sensor, compressor and inverter pcb already replaced done and low pressure sensor ohms ok .but still E2-01 blinking any other solution ?

    • @BonMj
      @BonMj  Před rokem

      Try check thermistor

  • @binhdinhthanh2001
    @binhdinhthanh2001 Před měsícem +1

    Can you give me code error VTV ? Thank you

  • @antanasrudminas9414
    @antanasrudminas9414 Před rokem +1

    👍👍👍

  • @peramaraj2763
    @peramaraj2763 Před 5 měsíci +1

    Hi sir I have a doubt vrv-4 master unit's inverter comp-01 we can do bypass ?

    • @ronaldoxotza9145
      @ronaldoxotza9145 Před 3 měsíci

      Yes you can. In vrv 4 you can do bypass to all the compressors. Either you have a system vrv or a single unit .except vrv 3 you can do bypass compressors only if we have a single unit. If we have a system you can bypass only a unit. Tech me Mr bon mj 😉

    • @peramaraj2763
      @peramaraj2763 Před 3 měsíci

      @@ronaldoxotza9145 Mitsubishi city multi (VRF) unit how to bypass including connected by CRC system

  • @yudhistira5209
    @yudhistira5209 Před 6 měsíci +1

    Siir , fan 2 running but fan 1 not running ,commpressor 1 running &compressor 2 runinng, we done reset fan 2&1working but 5 minute fan 1 not working again 'but nothink code error what's problem siir ?

    • @BonMj
      @BonMj  Před 6 měsíci

      Pressure ok?

  • @salamsaloom2477
    @salamsaloom2477 Před 9 měsíci +1

    👍👍👍👍👍👍👍

  • @amirulmirul730
    @amirulmirul730 Před měsícem +1

    Boss. I want ask. Vrv error code l5-14 what problam?

    • @BonMj
      @BonMj  Před měsícem

      Check inverter pcb or inverter compressor

  • @geovannialcoriza588
    @geovannialcoriza588 Před rokem +1

    Mr.Bon how to bypass for vrv 2 if sleve 1 compressor is broken?

    • @mahalakshmimaha9739
      @mahalakshmimaha9739 Před rokem

      For activate and deactivate both same ....Mode 2 and press set button39 time and press return 1 time and press set button 1 time ,again press return button twice

  • @hidayaturrokhman3538
    @hidayaturrokhman3538 Před rokem +1

    Is this the case of single outdoor, Mr. Bon?

  • @ibrahimqiqi5761
    @ibrahimqiqi5761 Před rokem +1

    ما هو سبب كود خطأ U3-02

    • @BonMj
      @BonMj  Před rokem

      Test run or indoor got error

  • @yerayrm83
    @yerayrm83 Před rokem +1

    hello bon what solution do you have the change of compressor 1

    • @BonMj
      @BonMj  Před rokem +1

      Compressor 2 and inverter pcb

    • @yerayrm83
      @yerayrm83 Před rokem

      @@BonMj ok friend 👍

    • @adeelashraf5141
      @adeelashraf5141 Před rokem

      Hello bon sir how r u.sir I want to came thir and work with u. ilove this work to much.allready I have a ac repairing work shop in Saudi Arabia.but I want to came thir and work with u.whats a process plz can u guide me or can u help me

    • @adeelashraf5141
      @adeelashraf5141 Před rokem

      Iam waiting for your answer

    • @adeelashraf5141
      @adeelashraf5141 Před rokem

      Help me plz

  • @jpmyname5724
    @jpmyname5724 Před rokem +1

    sir...numpang tanya kode error E2 -02 utk ac central daikin RXQ14AY14.. 1 sistem 2 outdoor...masalahnya apa sir? xie2

    • @BonMj
      @BonMj  Před rokem

      Check sub cu high low pressure sensor dulu atau compressor tak baik

    • @jpmyname5724
      @jpmyname5724 Před rokem +1

      @@BonMj siap sir...xie2

  • @vijaygani1179
    @vijaygani1179 Před rokem +1

    Vrf puhy p200 yhm mitsubishi error code can't show. run few minutes and off.pls can give some ideas

    • @BonMj
      @BonMj  Před rokem

      Do you check error at cu

    • @vijaygani1179
      @vijaygani1179 Před rokem +1

      Cu side no error code.

    • @BonMj
      @BonMj  Před rokem

      @@vijaygani1179 use wire remote check indoor error

  • @shepherdmutambiranwa4251
    @shepherdmutambiranwa4251 Před 7 měsíci +1

    I'm having LC 02 on cassette

    • @BonMj
      @BonMj  Před 7 měsíci

      Check inverter pcb and control pcb

  • @Mentri76
    @Mentri76 Před 5 měsíci +2

    with codes L5-5 and JA-9, please help, Mr Bon?

    • @Mentri76
      @Mentri76 Před 5 měsíci +1

      Model RXQ12AY14

    • @BonMj
      @BonMj  Před 5 měsíci +2

      L5-5 check slave 1 inverter pcb and compressor
      JA-9 check slave 1 high pressure sensor

    • @Mentri76
      @Mentri76 Před 5 měsíci

      @@BonMj thank you mr bon

  • @VincentChali-ny6hi
    @VincentChali-ny6hi Před 3 měsíci +1

    None a zad

  • @ataufikqurrahman7450
    @ataufikqurrahman7450 Před rokem +1

    Sir, i need solutions, inverter compressor 1 cable connected to grounding, 400 ohm, is teh compressor ,
    code error e2-01, please reply🙂

  • @Mangashraf02
    @Mangashraf02 Před 11 měsíci +1

    Sir mau tanya kode eror e2 -81 fan idup kompresor gak mau hidup

    • @BonMj
      @BonMj  Před 11 měsíci

      Check inverter pcb

    • @Mangashraf02
      @Mangashraf02 Před 11 měsíci

      Kpna ya sir awalnya eror e2 trus u4 sekrang e5 ganti2

  • @akashshaw214
    @akashshaw214 Před rokem +1

    Compressor 2 was in good condition then why change both inverter pcb&compressor

  • @joelnoumesi4
    @joelnoumesi4 Před 4 měsíci +1

    I ei I want to join your team I work on Daikin In Cameroon

  • @peramaraj2763
    @peramaraj2763 Před rokem +1

    I have a doubt sir system-4 ,03 nos of FCU is running as normal but 01 nos of FCU set point-23 the thermistor reading is 00-26.4C,01-24C, 02-07C, 03-10C the room thermistor can't decrease so what is the problem could you give me some tips sir ?

    • @BonMj
      @BonMj  Před rokem

      If 02=7
      03=10
      Mean is ok.no problem

    • @peramaraj2763
      @peramaraj2763 Před rokem +1

      @@BonMj but customer i ask why haven't decrease room temperature always stable 26 to 26.7 like this bro

    • @BonMj
      @BonMj  Před rokem

      @@peramaraj2763 air flow ok?

    • @peramaraj2763
      @peramaraj2763 Před rokem

      @@BonMj air flow ok bro

    • @peramaraj2763
      @peramaraj2763 Před rokem +1

      3 .2 m/s

  • @akashshaw214
    @akashshaw214 Před rokem +1

    Hlw sir i have a problem there is 3 vrv system 12 hp 12 hp 12 hp at one site they are showing error L5-03.

    • @akashshaw214
      @akashshaw214 Před rokem +1

      Vrv x

    • @BonMj
      @BonMj  Před rokem

      Check compressor and inverter pcb

    • @akashshaw214
      @akashshaw214 Před rokem +1

      Compressor is good

    • @akashshaw214
      @akashshaw214 Před rokem +1

      But i have about inverter pcb

    • @BonMj
      @BonMj  Před rokem

      @@akashshaw214 check the master unit inverter pcb and compressor

  • @satbirsingh88171
    @satbirsingh88171 Před rokem +1

    Sir vrv 4 error L5 After 1hour ronning

    • @BonMj
      @BonMj  Před rokem

      Check inverter pcb.

  • @ubongu1149
    @ubongu1149 Před rokem +1

    E English

  • @chungwhasan
    @chungwhasan Před rokem +1

    Please don't put ay back ground music! very annoying!!