LGMV HAVC TROUBLESHOOTING LOW REFRIGERANT

Sdílet
Vložit
  • čas přidán 15. 07. 2023
  • Hvac troubleshooting no cooling LGMV system, using LG service tool and smartphone app, no error codes. LG multi V 5 , LG MULTI V 4 and LG MULTI V 3 same solution.
    #d2dnyac #hvac #hvactech
  • Jak na to + styl

Komentáře • 55

  • @MarkCarpenterHVAC-me2jg
    @MarkCarpenterHVAC-me2jg Před rokem +3

    Regardless of the likes, the information you are sharing is very important.

  • @Rob0243
    @Rob0243 Před rokem +6

    That hissing noise you noticed quieting down was not the eev’s they are located on the indoor units individually. That was was the hot gas bypass shutting be cause you had put enough gas in that they weren’t need to prop up the suction pressure any longer.

    • @D2DNYAC
      @D2DNYAC  Před rokem

      This is awesome 👏 thank you

  • @Rodj12341
    @Rodj12341 Před rokem +7

    Just setting the setpoints lower isn't the best way to put the system into a full load operation. What you need to do is to turn on Dip switch #5 at the ODU, go to "Fdd" mode using the arrow/confirm buttons, and go to "Fd8" for full cooling(or Fd9 for full heating), and then push the confirm button. After a few minutes after it initializes, it should display 6000(countdown from 60 minutes). Also, LG has specific functions in the ODU to measure the charge to let you know how much to add/remove.

    • @D2DNYAC
      @D2DNYAC  Před rokem +1

      Sounds like you have some experience with these systems good info

    • @D2DNYAC
      @D2DNYAC  Před rokem

      Thanks for sharing

    • @vadims284
      @vadims284 Před rokem +1

      Does LGMV app show the charge and how much to add/remove?

    • @coachjaypoole
      @coachjaypoole Před 7 měsíci

      Can I get your number and 10 mins of Knowledge? Lol

  • @MarkCarpenterHVAC-me2jg
    @MarkCarpenterHVAC-me2jg Před rokem +2

    It is my understanding that discharge superheat (discharge pressure temperature - discharge temperature) should also give you a good indication of charge. Below 60F flooding back, above 90F low charge or bad windings. I believe the the system sets compressor speed from this reading.

  • @user-oe1cz1wo7p
    @user-oe1cz1wo7p Před rokem +1

    Great info on the LG!

    • @D2DNYAC
      @D2DNYAC  Před rokem

      Thank you for stopping by

  • @davidvargas2533
    @davidvargas2533 Před 6 měsíci +1

    Good stuff. Like the explanation.👍🏼

    • @D2DNYAC
      @D2DNYAC  Před 6 měsíci

      Thanks for watching

  • @keovongvilaykeo4799
    @keovongvilaykeo4799 Před rokem

    Always great 👍 thanks 🙏 you for sharing 😊

  • @vadims284
    @vadims284 Před rokem

    I thumb up this video because there isn't much info on LGMV. What I would like to see is thorough review of the features and and explanation of troubleshooting steps using this app.

  • @eyazyusuf276
    @eyazyusuf276 Před 2 měsíci

    جميللللللللللللللللللللللللللللللللللللللللل

  • @97gtman
    @97gtman Před 14 dny

    Thanks man.

    • @D2DNYAC
      @D2DNYAC  Před 12 dny

      Thank you for stopping by

  • @eyazyusuf276
    @eyazyusuf276 Před 2 měsíci

    عظيمممممممممممممممممممممممممم

  • @eyazyusuf276
    @eyazyusuf276 Před 2 měsíci

    رائع

    • @D2DNYAC
      @D2DNYAC  Před 2 měsíci

      Thanks for watching

  • @l.crossjr
    @l.crossjr Před 4 měsíci

    Great content. Where do you commonly find the most leaks on these units?

  • @trayq9694
    @trayq9694 Před rokem

    Good job

  • @Zeroboyz87
    @Zeroboyz87 Před rokem

    Yes yes 🙌🏾

  • @SKINIOX
    @SKINIOX Před 6 měsíci

    I’m using the same module but can’t get it set up any way you could give feedback? Can’t find anyone to call. When I hook it up it says I’m missing a key, but I don’t see a driver key and it didn’t come with the usb version I see online.

    • @D2DNYAC
      @D2DNYAC  Před 6 měsíci

      czcams.com/users/shortsalzxiA_nrHc?feature=share

  • @nosnim2207
    @nosnim2207 Před 11 měsíci +1

    Didn't you have a Veto bag a while ago?

    • @D2DNYAC
      @D2DNYAC  Před 11 měsíci

      Still do

    • @nosnim2207
      @nosnim2207 Před 11 měsíci +1

      @@D2DNYAC ah okay. I believe I caught it once in one of your videos and then never again afterwards. You didn't like it?

  • @crashbandit9949
    @crashbandit9949 Před 5 měsíci

    lol, I got a 2 pipe system in my house using the same mounting tool, Can you leave the tool plugged in all the time or should you remove it when not in use?

  • @desieranks
    @desieranks Před rokem

    Was it locking out on any error. I had a lg multi v low on gas giving an ch 36 error high discharge temp

    • @D2DNYAC
      @D2DNYAC  Před rokem

      Yes this is good information, because definitely this error will most likely pop up in these circumstances with these types of systems

  • @sultanfathelrahman3042

    Can you please make video about the best brand for the tools and how we can use it

  • @PhamChienHuu
    @PhamChienHuu Před 2 měsíci

    I also use iPhone, can you give me the link to download this LG MV application?

    • @D2DNYAC
      @D2DNYAC  Před 2 měsíci

      I don't have the link I have the file

    • @D2DNYAC
      @D2DNYAC  Před 2 měsíci

      I could potentially share it over what's app

  • @jasamba
    @jasamba Před 10 měsíci

    When low and high pressure okay but some indoors not cooling what could be the problem

    • @D2DNYAC
      @D2DNYAC  Před 10 měsíci +1

      With no error it's most likely under charged

    • @jasamba
      @jasamba Před 10 měsíci

      @D2DNYAC plz ideas how to check the indoors

    • @serdarkaraca2459
      @serdarkaraca2459 Před 10 dny

      İç ünite walf kablolarını kontrol ediniz

  • @yogeshchauhan6762
    @yogeshchauhan6762 Před 8 měsíci

    Can I purchase lgmv tool?

  • @JDT738126
    @JDT738126 Před rokem

    Did you get that MV module for free?

    • @D2DNYAC
      @D2DNYAC  Před rokem

      🤣🤣 certainly not however they are relatively cheap though

  • @HungNguyen-kd6kb
    @HungNguyen-kd6kb Před 10 měsíci

    Can I buy this device