LG MultiV 5 / Recommissioning an LG VRF System

Sdílet
Vložit
  • čas přidán 24. 07. 2023
  • Went back to recommission the LG MultiV 5 VRF system after the new indoor cassette and BS Box were installed.

Komentáře • 27

  • @rez131
    @rez131 Před 11 dny +1

    Great job, keep up the good work 👍

  • @Rodj12341
    @Rodj12341 Před rokem +2

    There is a better way of judging the full load operation of the unit. What you need to do is to turn on Dip switch #5 at the ODU, go to "Fdd" mode using the arrow/confirm buttons, and go to "Fd8" for full cooling(or Fd9 for full heating), and then push the confirm button. After a few minutes after it initializes, it should display 6000(countdown from 60 minutes). Also, LG has specific functions in the ODU to measure the charge to let you know how much to add/remove(Fd1-4).

    • @hvacraustralia
      @hvacraustralia  Před rokem +1

      Thanks for that mate, great info to know! I had a flick through the service manual the day after and found the section that explains what all the functions do and how to get there haha great timing on my behalf 😂 I’ll know for next time.

  • @maheradous9257
    @maheradous9257 Před 2 měsíci +1

    Good job 👍

  • @NiiosaMensah-jo1ol
    @NiiosaMensah-jo1ol Před 2 měsíci

    Good job

  • @bradenramsell5848
    @bradenramsell5848 Před rokem

    Nice! What do you do refer to work on in terms of ease of work between Mitsubishi, Daikin or LG?

    • @hvacraustralia
      @hvacraustralia  Před rokem +1

      They all have their pros and cons. In terms of general work and getting information from the displays on the outdoor, I prefer Daikin. Their 7 segment display is very easy to use. For display and usability on the service tool, Mitsubishi for sure. The layout and information it gives you is the best for me by far. This was my first time working on an LG and it seemed nice. Once I had my heard around what I needed to do it was pretty easy. Shame about the poor access to the service valves. Can’t win them all 😂

  • @HVACR_VINYLS
    @HVACR_VINYLS Před rokem

    👑

  • @jonnyxcz125
    @jonnyxcz125 Před 5 měsíci

    The thing you did with the nitrogen when pulling the vac what does that actually do and help with.

    • @hvacraustralia
      @hvacraustralia  Před 5 měsíci +1

      The idea is to dislodge any tapped moisture in the system by raising the pressure/temperature. I usually do it when my micro reading stalls out.

  • @Louisyongcool2328
    @Louisyongcool2328 Před 8 měsíci

    Hi mate, I got a site that the brunch box low,high and liquid pipe all crap reduce pipe size do this reduces the cooling capacity? I think some cowboy doing this. Thanks mate

    • @hvacraustralia
      @hvacraustralia  Před 8 měsíci +1

      Hey mate. Yeah, absolutely. Due to less volume being present there will be less refrigerant at the indoors, resulting in less capacity.

    • @Louisyongcool2328
      @Louisyongcool2328 Před 8 měsíci

      @@hvacraustralia thanks what would you do if in this situation? Check gas pressure and add some more gas to increase the cooling ?

    • @hvacraustralia
      @hvacraustralia  Před 8 měsíci +1

      Adding more refrigerant won’t solve the problem. That’s a tough one, is it a recent install? If so the installer would need to come back and install the correct pipe sizes. If it’s older, could always suggest installing the new pipe sizes.

    • @Louisyongcool2328
      @Louisyongcool2328 Před 8 měsíci

      @@hvacraustralia is a school it been install around 2 year I think school only have 1 year warranty, that a tough one and I don't do LG much, so properly need to reconnect to right pipe size and recover all gas out and check if any leak. If I add some gas it won't do any cooling right? Thanka

  • @bradroesler7072
    @bradroesler7072 Před 11 měsíci

    Seeing you're a refrigeration technician, do you work on exhaust or ventilation systems? I know this has nothing to do with this video.

    • @hvacraustralia
      @hvacraustralia  Před 11 měsíci

      We do look after the exhaust fans, fresh air fans etc on most of our sites. They’re usually just a single or three phase direct drive motor so nothing fancy.

    • @bradroesler7072
      @bradroesler7072 Před 11 měsíci +1

      Can you please make some videos on maintaining exhaust fans, especially bathroom/toilet ones?

  • @J_D_Begins
    @J_D_Begins Před rokem

    How long did vacc take mate?

    • @hvacraustralia
      @hvacraustralia  Před rokem +1

      I think it was vacc for around 4h. It was really dragging with the 1/4 straws I was trying to pull through 😂

  • @maheradous9257
    @maheradous9257 Před 2 měsíci

    Please send all news videos to me. Thankyou

  • @HVACR_VINYLS
    @HVACR_VINYLS Před rokem

    My tool arived, now waiting for that rainy day i get an lg problem

    • @hvacraustralia
      @hvacraustralia  Před rokem +1

      It’s a tool that might get used every 1-2 years 😂 I don’t see many MultiV, but when we do we’re ready!

    • @HVACR_VINYLS
      @HVACR_VINYLS Před rokem

      @@hvacraustralia 100% broski