LG - Troubleshooting Common Multi V Error Codes

Sdílet
Vložit
  • čas přidán 7. 09. 2024

Komentáře • 61

  • @jg3775
    @jg3775 Před 3 lety +1

    I only get CH53 or CH05 when I connect more than one indoor unit, the auto addressing says "1" and there's 2 units connected. the outdoor unit is MULTI Vs and can connect up to 16 units.

    • @GlacierSupplyGroup
      @GlacierSupplyGroup  Před 3 lety +1

      A CH53 is an outdoor unit communication fault and a CH05 is an indoor unit communication fault. Also, LG requires a minimum of 2 connected units and minimum 40% capacity. The error code you mentioned has to do with your daisy chain communication wiring. You also need to run an auto addressing and then run a hot pipe.

    • @jg3775
      @jg3775 Před 3 lety

      @@GlacierSupplyGroup thanks for replying, I get no errors but it says "pre heating is running" and it doesn't change until I disconnect all the units and only wire one and then it says "ODU is running". I've double, triple and quadruple checked the daisy chain and even replaced the entire line ands I ran the power away from the communication so there isn't any interference but to no avail. im kinda lost

    • @anwarhussain7887
      @anwarhussain7887 Před 2 lety

      Dear sir
      Multi v 4 ch 53 error occurred.
      What's possible error.
      Thanks

  • @miguelroman4479
    @miguelroman4479 Před 2 lety

    I am experiencing a CH 62 indicates a sink error how do I trouble shoot ?

  • @thewannabemartialartist4613

    I keep getting CH 26, and after replacing about 10+ compressors over the past 2 years is there something that im missing here?

  • @imonevBG
    @imonevBG Před 3 lety

    Do you know what might be the cause of Error 73 and what is the eventual fix.

  • @AK-yu3cu
    @AK-yu3cu Před rokem

    Please share link for testing &commissioning

  • @vusalmmmdov4204
    @vusalmmmdov4204 Před 3 lety

    What is Ch-150? How can this problem be solved?

  • @jorgeuribe4512
    @jorgeuribe4512 Před 2 lety +1

    Ch21?

    • @dlanyc168
      @dlanyc168 Před 2 lety

      Ch21 C 1 1 is what I have. Need answers!! Lol

  • @smartboy1489
    @smartboy1489 Před 4 lety

    Please help me.i bought lg dual inverter 5star ac . After 3 days. In night the temp is set for 27celcius and enegy control in 60% when we wake up on the morning the room is not cooled but blower is running and the compressor is off. Then after restarting it shows a error code of CH21 and then again restarted the error code became vanished. But the compressor is not turning on after some hours again restarted the compressor runs and cools .Is there any problem?

    • @upsidezium1
      @upsidezium1 Před 3 lety

      Inverter compressor run current high. Check compressor windings all equal 1 to 4 OhmsCheck to earth 50 MOhm minimum, check run current

    • @user-dx4bp8rf1l
      @user-dx4bp8rf1l Před 6 měsíci

      Ch21 problemas con la tarjeta pcb La que le lleva tensión al compresor haga el cambio de pasta térmica al disipador de calor revise que él ventilador forzador esté trabajando bien y por supuesto revise el compresor

  • @Samima823
    @Samima823 Před 4 lety

    Sir.. Pless help... LG smart inverter model ABUQ60LM3T0... Ch 35 error code in outdoor panel... Compressor run but not cooling.. Please answer me

    • @Samima823
      @Samima823 Před 4 lety

      24000 BTU

    • @upsidezium1
      @upsidezium1 Před 3 lety

      Excessive low pressure drop under 1 Bar at LP sensor. Check pressures, and check service valves open

  • @Doels_Channel
    @Doels_Channel Před 2 lety +1

    How to solve eror 211, C11 please..

    • @dlanyc168
      @dlanyc168 Před 2 lety

      Did you ever find this out?

  • @Samima823
    @Samima823 Před 4 lety

    Discharge line work but not cooling

  • @FirojAlam-ec3su
    @FirojAlam-ec3su Před 2 lety

    Sir guidance plz 211error plz help me

  • @edercardoso9259
    @edercardoso9259 Před 3 lety

    olá!
    pode me informar o cód 237?

  • @tompastian3447
    @tompastian3447 Před 4 lety

    This video is more for an LG technician, not the average home owner. When the narrator talks about checking the fan motor, what fan motor is he referring to ? The fan motor in the air handler or the fan motor in the compressor unit? What would be much more helpful is an LG trouble shooting video that addresses specific problems. I have one of the larger mini split AC units with the heat pump. The inside unit started hissing, and then the smell of something electrical overheating. Unfortunately it looks like the mini split systems are too complicated for anyone but an experienced LG technician. Very disappointed with mine failing, considering what it costs to have the Freon lines hooked up (rip off). Before I had the LG system, I had a Fredrick mini split system (no longer available) and the technicians from Brandsmart could not figure out what was wrong with it. I got a refund since I bought a 5 year extended warranty, and had to return the entire unit. Friedrich ac units were once top of the line, but not so with the newer ones I've seen.

    • @jahblessyourmom
      @jahblessyourmom Před 3 lety

      That's because only a trained technician should be working on these units. These are large commercial units. A homeowner shouldn't be working on any high voltage equipment and a manufacturer isn't going to tell you how due to liability for when some dummy fries themself because they didn't let the inverter board discharge its capacitors.

    • @tompastian3447
      @tompastian3447 Před 3 lety

      @@jahblessyourmom Thanks for the reply Chris. I took a few days, but I did figure out what happened with the electrical burning smell and the hissing. Both were not related to the mini split system. The burning smell was from an Ace Hardware power strip on the back porch which is fairly close to the air handler inside the house. I had several items plugged into this power strip, and something caused the strip to short out. It could have been some water dripping from above, or a bad cord on the grinder. The cord melted on the grinder where it plugged into the power strip. The smell made it's way into the house, and my wife was thought it was coming from the air handler.
      I do think however, it would be helpful if companies would give an explanation of what the various codes are.

  • @acmohamed9935
    @acmohamed9935 Před 2 lety

    CH44 what problm

  • @fazliey3783
    @fazliey3783 Před 3 lety

    Ch 03 and ch 25

  • @coolcoolaircondition9005

    Vrf Lg 30 min coling but stop after not runing

  • @jitendrasah2668
    @jitendrasah2668 Před 3 lety

    How to solve CH51

  • @tipuzheaven6317
    @tipuzheaven6317 Před 4 lety

    CH 242.Please tell me solution

  • @fiona9912
    @fiona9912 Před 4 lety

    What if it just says ch

  • @coolcoolaircondition9005

    COOLCOOL

  • @richardibarra3641
    @richardibarra3641 Před 4 lety

    Have you got a ch150 code

    • @upsidezium1
      @upsidezium1 Před 3 lety

      Sub 2 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB

  • @adilgamra6039
    @adilgamra6039 Před 2 lety

    Ch 180 plzzz

  • @techyvlog5455
    @techyvlog5455 Před 4 lety +1

    Ch 51

    • @upsidezium1
      @upsidezium1 Před 3 lety

      Unit mismatch. Check model number of units do not exceed maximum. Multi V - also check Sub outdoor unit dipswitch settings

  • @salma23tariq
    @salma23tariq Před 5 lety

    Error CH 15 plz

  • @prasannankollam8948
    @prasannankollam8948 Před 3 lety

    CH 15

  • @jorgecanoaburto1135
    @jorgecanoaburto1135 Před 4 lety

    My is ch 27 help please!

    • @jayrae17
      @jayrae17 Před 4 lety

      It’s the inverter

    • @HeavyHookSet14
      @HeavyHookSet14 Před 4 lety

      Care to elaborate a little more on this? Have the same on a lmu36chv

    • @upsidezium1
      @upsidezium1 Před 3 lety

      Inverter current irregularity. Check inverter PCB and reactor

  • @ericyeboah6340
    @ericyeboah6340 Před 4 lety

    Please my ch 621

  • @ahmedjawad9767
    @ahmedjawad9767 Před 5 lety

    Ch52 😥

    • @GlacierSupplyGroup
      @GlacierSupplyGroup  Před 5 lety +1

      That's a communication error between main Micom and Sub Micom.

    • @upsidezium1
      @upsidezium1 Před 3 lety

      Communication error between inverter PCB and main outdoor unit PCB. Check wiring fuses and LEDs . If OK either inverter or main PCB defective

  • @ValValiantThor216
    @ValValiantThor216 Před 5 lety

    Mine is ch50

    • @GlacierSupplyGroup
      @GlacierSupplyGroup  Před 5 lety

      It's probably a CH05. I don't see a CH50 in the error code list. If it IS a CH05, that's a communication error.

    • @mmademusic3836
      @mmademusic3836 Před 4 lety

      @@GlacierSupplyGroup CH50 is in this video, what are you on about?

  • @jasonzabala7992
    @jasonzabala7992 Před 4 lety

    Error code 54

    • @upsidezium1
      @upsidezium1 Před 3 lety

      Reverse or open phase. Check all 3 phases are present and correct. If correct voltage appears at all three phases, swap any two to cure the fault

  • @josealfredovelazquezmartin8025

    Multi v plus ch 50

  • @luisvaquero3452
    @luisvaquero3452 Před 4 lety

    CH237??

    • @beergo99les
      @beergo99les Před 3 lety

      Any update?

    • @jg3775
      @jg3775 Před 3 lety

      @@beergo99les I get CH237 when the auto addressing isn't done correctly.

  • @chiragrana2733
    @chiragrana2733 Před 5 lety

    How to solve 28 2 error