Video není dostupné.
Omlouváme se.

ABB TZIDC Positioner I/P adjustment

Sdílet
Vložit
  • čas přidán 13. 05. 2021
  • adjustment of I/P to reduce hunting of the valve,

Komentáře • 17

  • @worldinstrumentationengineer

    BAHUT ASSA JI

  • @worldinstrumentationengineer

    BAHUT ASSA GURU JI🙏🙏

  • @HaungAdam
    @HaungAdam Před 6 měsíci +1

    sir i ues auto adjust and run 20 outlet no have any air come out how to do ?? can repair or no??

  • @udayachaithanyanath
    @udayachaithanyanath Před 4 měsíci +1

    Positioner is not taking Setpoint/ demand from remote DCS... Able to operate locally... What can be the issue

    • @instrumentationandsolution5013
      @instrumentationandsolution5013  Před 4 měsíci

      Keep positioner operating mode to 1.1 ..
      Check the feedback cable and current mA cable once ... Sometimes cable can be interchanged ...

    • @udayachaithanyanath
      @udayachaithanyanath Před 4 měsíci +1

      @@instrumentationandsolution5013 checked in 1.1 it's working fine and also able to operate in local mode. Only in remote mode it's not operating. ps. it's a profibus PA device

    • @instrumentationandsolution5013
      @instrumentationandsolution5013  Před 4 měsíci

      Check the address in the positioner ..

  • @shaktisingh4793
    @shaktisingh4793 Před 3 lety

    Sir how can we overcome haunting problem in ABB positioner ?

    • @instrumentationandsolution5013
      @instrumentationandsolution5013  Před 3 lety

      U can reduce hunting (permanently) by calibrate I/P ... plz check my I/P calibration video. And u can reduce hunting through parameters, go to parameters no 7 and reduce deadband to 0.1 and u can do PID adjustment in parameters increase (7, 7.1,) parameters.... hunting will reduce

    • @shaktisingh4793
      @shaktisingh4793 Před 3 lety +1

      @@instrumentationandsolution5013 deadband and gain of abb is already done but still there is a hunting .
      I tell u if we close or fully open there is no hunting but if we do 25%,50% or 75% hunting start .help me plz sir

    • @AnilKumar-xo7ot
      @AnilKumar-xo7ot Před 3 lety

      @@shaktisingh4793 for how many seconds it's hunting or continuously hunting, generally if u give command 0 to 25 to 50 to 100 its will hunt for 2 to 3 seconds, if it's hunting more that 2 to 3 seconds then plz check following 1. Any play in Feedfack link , 2. did u checked I/P passing or not, 3. Check any leakage in actuator, 4. Check gland tightness, 5. U can reduce hunting by changing P 7.8 deadband approach fast to medium etc ....

    • @shaktisingh4793
      @shaktisingh4793 Před 3 lety

      @@AnilKumar-xo7ot more than 3 sec it do hunting .feedback link is checked,deadband parameter is reduced to 0.1 ,gland tightness is also checked ,there is no leakage .
      What else i do sir ?

    • @AnilKumar-xo7ot
      @AnilKumar-xo7ot Před 3 lety

      @@shaktisingh4793 how much % hunting and what about I/P....