Powerflex 525 Controls In Studio 5000 V32 | Start & Stop Commands With Speed Controls

Sdílet
Vložit
  • čas přidán 27. 07. 2024
  • Adding Powerflex 525 Start/Stop controls with speed reference using a speed pot with eh drive speed commanded through ethernet is exactly what is shown in this video.
    Building off of the last three videos, now we start to program the Powerflex 525 drive for a simple control set-up of start & stop logic using our finite state machine.
    Video Content:
    Minute: 0:00 Adding a New Task in Studio 5000
    Minute: 2:24 Adding our Main Routine
    Minute: 3:00 Adding our Powerflex 5252 routine
    Minute: 4:00 adding Powerlex 5252 logic controls on ladder logic
    Minute: 9:30 Powerflex start/stop bits explained
    Minute: 10:20 Adding Powerflex 525 speed controls in ladder logic
    Minute: 13:10 Adding Speed Monitoring logic
    Minute: 15:00 System testing using FactoryTalk SE HMI app
    Minute: 17:35 Why we use the drive active bit for speed controls
    I hope you enjoyed the video.
    Thank you for watching the video.
    Learn, Implement, Succeed
    If you are interested in getting serious about your knowledge & learning how to better your career then check out our training center.
    Visit:
    allen-bradley-plc-training.te...
    #Powerflex525 #Poweflex525LadderLogic

Komentáře • 18

  • @ShaneWelcher
    @ShaneWelcher  Před 3 lety +1

    Join Us & Learn More:
    allen-bradley-plc-training.teachable.com

    • @johnathonsummers2135
      @johnathonsummers2135 Před 3 lety +1

      Could you please explain why you have to multiply the speed input by 100?

    • @ShaneWelcher
      @ShaneWelcher  Před 3 lety

      ​@@johnathonsummers2135 It's based on the parameter file of the VFD you are using.
      Or in other words, the parameter file of the Powerflex drive that is being used in the system.
      Sorry if I missed that in the video but I know I cover this in this series of videos.
      I understand that watching videos can be interesting at times & not so at others, with that said, it is important to watch all of my videos because I do cover details of whatever I talk about throughout.
      Also, note that I will be adding timelines to the videos in the future to better help anyone trying to find what they are looking for.
      I hope that helps...have a great day.

  • @jonathonlock361
    @jonathonlock361 Před 3 lety +1

    your videos are great thank you for your time and doing these videos i am just learning studio 5000 and these are great

  • @autoworks.design5668
    @autoworks.design5668 Před 3 lety +1

    Do you have an example of control speed using high/low limit switches and timers? Such that if the low level is on and speeds up for every second it is on? Slows done when at the high level. Thanks

    • @ShaneWelcher
      @ShaneWelcher  Před 3 lety

      That is fairly simple to do if you would like for me to make one.
      I have similar logic controls in my training courses at
      www.allen-bradley-plc-training.com/

  • @SCADAExperts
    @SCADAExperts Před 10 měsíci +1

    Hello sir, I am facing one issues we have dam gate control application using PF 525 VFD. While gate opening we don't get any fault but when we start down operations VFD gives Overvoltage F005 alarm after 1 to 2 feet down from actual position. There are two cases 1 decelation time is 1 sec. Second 120Ohm 2.5kW DBR is used DBR Parameter is also selected Normal duty cycle also I checked with different duty cycle . Still problem is there so please guide me. Thank you.

    • @ShaneWelcher
      @ShaneWelcher  Před 10 měsíci

      Sounds like you need to decrease the decel and if that doesn't help then you need to add a braking module to burn off any regeneration power from what you described.

  • @keeponwalking_2024
    @keeponwalking_2024 Před 3 lety +1

    Is it possible to control the powerflex without plc? Only Modbus tcp?

    • @ShaneWelcher
      @ShaneWelcher  Před 3 lety

      It's possible to control a Powerflex 525 with no plc controls.....yes
      You can use push button controls wired to the digital inputs or just use the keypad

  • @jrdz009
    @jrdz009 Před 2 lety +1

    Hi Prof, do you have an email address I can contact you? I need some quick help with a PF525 on LogixDesigner 32.11

    • @ShaneWelcher
      @ShaneWelcher  Před 2 lety

      Hello, thank you for your support.
      I have a one-on-one coaching program I made to help with custom things that anyone has trouble with.
      Mainly because of demand, I have limited time so if you are interested then please visit the link below for a one-on-one coaching session.
      www.allen-bradley-plc-training.com/p/factorytalk-view-studio-site-edition-training-live-with-q-a

    • @jrdz009
      @jrdz009 Před 2 lety +1

      Thanks prof, I checked your website yesterday, but couldn't find on it what I needed.
      My problem is I have 4 VFDs running and I need to read the current, I'm using LogixDesigner 32.11 and I changed the device definition so I can read the current, but when I downloaded the program to the PLC, the drives got faulty and can't connect to PLC, I can't find the buttons and tabs LogixDesigner 30 and 31 have to download the changes to the drive configuration tab, because no tab for drive in version 32, and can't download it online cause drive isn't connecting

    • @ShaneWelcher
      @ShaneWelcher  Před 2 lety

      @@jrdz009 If you need to read current then either add it to the drive configuration on the PLC IO for yh drives then download so the tags are used or just use that message instruction in the current program to read information front he drives.

    • @ShaneWelcher
      @ShaneWelcher  Před 2 lety

      @@jrdz009 The link I providing is for personal one-on-one training via a zoom meeting, you are aware of that correct?

    • @ShaneWelcher
      @ShaneWelcher  Před 2 lety

      @@jrdz009 I just made a video if you want to see it.
      For the message instruction setup.
      Email me at Shane@OnlinePLCSupport.com