Siemens TIA Portal Tutorial (S7-1200 PLC_Hardware Overview)

Sdílet
Vložit
  • čas přidán 7. 09. 2024

Komentáře • 52

  • @PeteVree
    @PeteVree  Před rokem

    Full Siemens TIA Portal PLC Programming Course available here: petevree.thinkific.com/courses/siemens-tia-portal-plc-programming

  • @arbjful
    @arbjful Před 3 lety

    I bought the kit without the HMI, it was cheaper. However I also bought the CB-1241 RS485 comm module. I didn't need the HMI. as I plan to use a kinco HMI. I need to develop a motion control system to control a MODBUS TCP based stepper.motor. Thanks for posting, this is a really useful video

  • @PeteVree
    @PeteVree  Před 5 lety +7

    Before you go out an spend a lot of cash on a PLC and HMI, remember that you can Simulate your programs and HMI using PLC SIM. If you are working from home, this will provide you everything you need to learn the software at a fraction of the price.

    • @davinder794
      @davinder794 Před 4 lety

      Hello Sir S7-1200+KTP400 Basic starter kit. In windows 10 we can download this TIA portal program from that kit.

  • @uditsaxena3844
    @uditsaxena3844 Před 8 měsíci

    Sir if i think correctly does relay output also has 24V supply to the outputs. Our outputs are usually actuators like solenoid valves and so on . INputs can be sensors and switches

  • @oladimejiyusuf8345
    @oladimejiyusuf8345 Před rokem

    nice video

  • @techsolver9347
    @techsolver9347 Před 3 lety

    Great video 👍🏻👍🏻

  • @shaik-jp1vr
    @shaik-jp1vr Před 3 lety

    Hello Thaks For The Videos.I have S7-1200 Plc With Cpu 1214C DC/DC/DC
    While My Plc Is In Running Mode In Production Suddenly One Day It's Stopped The RUN/ STOP led Status Went In Orange Colour.
    I'm trying to ping with plc it's pinging with Pc. and while am trying to upload program From Plc it's showing error of NO NODE WERE FOUND.What Will be the root cause.

  • @sonephethkenkeo2487
    @sonephethkenkeo2487 Před 2 lety

    Good

  • @jsg8803
    @jsg8803 Před 3 lety

    Hello pete does the memory card come with this kit if not where can I get the same and how much would it cost??

  • @mohamadhady1518
    @mohamadhady1518 Před 4 lety

    Thant u for your explanation

  • @michaelcostello6991
    @michaelcostello6991 Před rokem

    If you use a resistor and a 4 to 20 mA is that ok. Is this done often to get an analog voltage input ? I have seen resistors in panels and it can be confusing

    • @PeteVree
      @PeteVree  Před rokem

      A 250 ohm resistor across the analog input terminals would provide 1-5 V DC when 4 - 20 mA is flowing though it. This is a crude way of making something work when you're too cheap to purchase the appropriate input card.

    • @michaelcostello6991
      @michaelcostello6991 Před rokem

      @@PeteVree Thank you. I have seen these resistors used on small PLC's used on sump pumps that have hydrostatic sensors

  • @jonnyrobotix
    @jonnyrobotix Před 3 lety

    How are you supposed to connect the HMI, PLC and Progamming Laptop ?? Only one outgoing Ethernet port

    • @PeteVree
      @PeteVree  Před 3 lety

      You'll need either a standard router or an ethernet switch

  • @user-rl8yb7tb1k
    @user-rl8yb7tb1k Před 6 lety +1

    thank you a lot

  •  Před 6 lety

    great videos, I want to learn PLC programming and troubleshooting

    • @PeteVree
      @PeteVree  Před 6 lety +1

      The Siemens PLC is a great product to learn, and is widely used in industry. I can highly recommend Rajvir Singh's course on Udemy.

    • @tarkoayanawo4735
      @tarkoayanawo4735 Před 5 lety

      K P

  • @jigargosar7044
    @jigargosar7044 Před 5 lety

    How to access or edit the program which is already there in the cpu? Thank You!

  • @marchmonkey7768
    @marchmonkey7768 Před 2 lety

    where did you buy the hardware and software?

  • @thomassaook7787
    @thomassaook7787 Před 6 lety

    Thank you, would please discuss connecting to S7-1200 via router from remote places?

    • @PeteVree
      @PeteVree  Před 6 lety +2

      I'll add it to my list of topics to cover. Thanks Thomas.

    • @thomassaook7787
      @thomassaook7787 Před 6 lety

      Thank you again.

  • @hvaceee
    @hvaceee Před 5 lety

    seems dont have Ethernet connector, need separate TCP/IP card to connect or factory IO? thanks

    • @PeteVree
      @PeteVree  Před 5 lety

      This model of the S7-1200 comes with an Ethernet Connector. The Factory IO does not need a physical connection.
      It is simply an animation program that looks at I/O values above the number of physical inputs of the PLC.
      czcams.com/video/kmlx4Sq94hQ/video.html&list=PLyL0ResmI4Q38NVKLzouUJdNMu7bA2mH5&index=7

  • @anoop22march
    @anoop22march Před 5 lety +1

    What does DC/DC/Rly means

    • @PeteVree
      @PeteVree  Před 5 lety +2

      DC is DC Power Supply
      DC is 24V DC Inputs
      RLY is Relay Outputs

  • @harry81gr
    @harry81gr Před 5 lety

    Hi Pete , great video! i purchaced the plc but i have a fault.. is it mandatory to have a sd card so i can download a program or run the plc?

    • @PeteVree
      @PeteVree  Před 5 lety

      No. The SD card is not required for downloading a program. Perhaps you chose the wrong PLC when downloading?

  • @priyansh3303
    @priyansh3303 Před 4 lety

    can you please explain about RLY ouput conncction , about 1L

    • @PeteVree
      @PeteVree  Před 4 lety

      Take a look at Rajvir Singh's diagram here: forums.mrplc.com/uploads/monthly_2017_12/Introduction-to-S7-1200.jpg.0d5c7d2aaa91906fa7b01b24bc34cbec.jpg
      The 1L is the common connection for the outputs

  • @chrisfisichella6659
    @chrisfisichella6659 Před 3 lety

    How long does the S7-1200 take to start up?

    • @PeteVree
      @PeteVree  Před 3 lety

      Couple seconds... depends on how many bananas you fed it last night.

  • @YOSRI1990
    @YOSRI1990 Před 6 lety

    thank you
    i have a question the PLC 1214C DC/DC/DC need a power sopply or have a internal transformer

    • @PeteVree
      @PeteVree  Před 6 lety

      It contains a power supply that takes the 120/240V and provides 24VDC.
      mall.industry.siemens.com/mall/en/WW/Catalog/Product/6ES7214-1AG40-0XB0

    • @engineerSalih
      @engineerSalih Před 6 lety

      I could be wrong Mr. Pete but : 1st/2nd/3rd
      1st is for the supply voltage, not the power Supply. meaning it takes in 24 DC NOT 120/240V, and it provides also 24DC for inputs. Refere to system manual chapter " Technical specification/ CPU wiring"

  • @electricaltech4u45
    @electricaltech4u45 Před 5 lety

    My plc run stop so not working

    • @PeteVree
      @PeteVree  Před 5 lety

      Sorry to hear that. Have you tried turning the PLC on and off on the menu on the top left of the TIA Portal?

  • @laminetheory5563
    @laminetheory5563 Před 4 lety

    Hi i had question i want buy plc s7 1200 with Aliexpress it is original or it's copy for only 130 dollars ?

    • @PeteVree
      @PeteVree  Před 4 lety +1

      Probably a scam. I had some really bad experiences with EBay, so I only purchase from reputable suppliers now.

    • @laminetheory5563
      @laminetheory5563 Před 4 lety

      @@PeteVree ok thank you

    • @PeteVree
      @PeteVree  Před 4 lety

      @@laminetheory5563 In this ad they show the warehouse and it is a photo of boxes of potatoes and pineapples =)
      www.aliexpress.com/item/4000259078726.html?spm=a2g0o.productlist.0.0.49267bc0Mi1sHN&algo_pvid=2ce7e05d-c1d5-40b2-a4fe-c34198219d6a&algo_expid=2ce7e05d-c1d5-40b2-a4fe-c34198219d6a-11&btsid=4111fa29-aa94-42f3-a33f-ee6f864e8169&ws_ab_test=searchweb0_0,searchweb201602_5,searchweb201603_55

  • @DAVIDALVARADO-xw5km
    @DAVIDALVARADO-xw5km Před 5 lety

    Hi Pete, great videos, thanks for them! I only have a question for you, which S7 1200 PLC model includes analog input (4 to 20 mA) ?? any advice? Which is the HMI model in this video? I want to buy one the same as yours ... Thanks you for your help!

    • @PeteVree
      @PeteVree  Před 5 lety

      I bought the KTP400. It is quite small and limits your workspace. If you are working from home you can always add a PC HMI and then just Simulate with PLC SIM... saves you a lot of cash and you get the same result.
      4 to 20 mA inputs are available through additional modules. The SM1234 AI/AQ would be an example.
      Also the 1214C PLC allows for the SB1232AQ which fits right on the front of this model.

    • @DAVIDALVARADO-xw5km
      @DAVIDALVARADO-xw5km Před 5 lety

      @@PeteVree Thanks for the advice. So, is it possible to use the analog module you said: SM1234 AI/AQ in the PLC you used in your video (CPU 1212C AC/DC/RLY)??

    • @PeteVree
      @PeteVree  Před 5 lety

      Best to check with a supplier to confirm. www.plc-city.com/shop/en/siemens-simatic-s7-1200-analog-modules.html

  • @chuchuokeke
    @chuchuokeke Před 6 lety

    Almost bought an analog input from plc city...dollar price got too high in my country

    • @PeteVree
      @PeteVree  Před 6 lety

      Prices are climbing here in Canada as well as our dollar has dropped to 0.77 USD

    • @nnewinnewi169
      @nnewinnewi169 Před 4 lety

      Okeke nwanne looking for same .

  • @oweshali9831
    @oweshali9831 Před 4 lety

    i think this is non-expandable model