Mr Bon.Thank you for all your guide.You are the best instructor. Would you help me please.I have the VRV Classic Inverter and in my case I have that issue: the H2P and H8P is blinking and H5P is ON.The compressor and fan does not working. Thermostat display indoor units shows Error button Menu of three of them and for other 2 units: Clean filter. Can I make the same steps as you showed in this video to bypass the Standard Compressor 1 or is different in my case? Is there a problem or mean some error?I thing the compressor does not have refrigerant,can also run the compressor and fan for this VRV Classic without refrigerant?.In the compressor 2 does exist refrigerant?Thank you!
@@BonMj Hi Mr Bon,the model for this VRV is: RXYCQ12A7Y1B DAIKIN EUROPE N.V. MFG DATE 2014.01 DAIKIN VRV CLASSIC INVERTER. 1) External single DAIKIN unit. When I start the VRV the master PCB model SEB11050(D) has: H2P and H8P blinking The H5P is ON.The other lights is off.The PCB does not have display.The PCB it looks like a VRV III. It is single external unit.Also the fan and compressor not working(is there a problem as long the gas is insufficient or not at all?the compressor and fan can work only if the PCB detect pressure and/or refrigerant?) 2) Internal units On the Thermostat(remote controllers display i mean) from indoor units shows: ERROR BUTTON MENU I didn't press the Menu button because I didn't know.Now I know what I have to do to show the error in this display. Maybe the next 2 weeks can I tell you what error show in display from indoor units.Thank you!
How to by pass standard 2 compressor at set button press same 19 times or 20 times because I look for your video for standard 2 compressor by pass but none, Sir Bon Mj
@@BonMj that's right.. then if there is a problem with CU Slave 1, it means that vrv 3 multi outdoor unit can only by pass. which can be turned on CU main and slave 2. for CU slave 1 off (by pass) like that kah?
Bon Sir If the standard Compressor 1 is Defective we press the Set button 19 times for the by-pass setting But sir if the standard Compressor 2 is Defective then how many times press the set button??
Please like and share + Subscribe.
Please leave your comments.
Thanks🙏🙏
Bon mj u didn’t tell about bypass standard compressor 2 and inverter compressor for single outdoor in this video.
Please explain
Good Bon sir well-done
Thanks
Tq அண்ணா ✌️
Thanks
Thank you so much Sir
Most welcome
Mr Bon.Thank you for all your guide.You are the best instructor.
Would you help me please.I have the VRV Classic Inverter and in my case I have that issue: the H2P and H8P is blinking and H5P is ON.The compressor and fan does not working.
Thermostat display indoor units shows Error button Menu of three of them and for other 2 units: Clean filter.
Can I make the same steps as you showed in this video to bypass the Standard Compressor 1 or is different in my case?
Is there a problem or mean some error?I thing the compressor does not have refrigerant,can also run the compressor and fan for this VRV Classic without refrigerant?.In the compressor 2 does exist refrigerant?Thank you!
Hi.thanks watching my video.
1)What is the outdoor unit model
2)what is the error
@@BonMj Hi Mr Bon,the model for this VRV is: RXYCQ12A7Y1B DAIKIN EUROPE N.V.
MFG DATE 2014.01
DAIKIN VRV CLASSIC INVERTER.
1) External single DAIKIN unit. When I start the VRV the master PCB model SEB11050(D) has: H2P and H8P blinking
The H5P is ON.The other lights is off.The PCB does not have display.The PCB it looks like a VRV III.
It is single external unit.Also the fan and compressor not working(is there a problem as long the gas is insufficient or not at all?the compressor and fan can work only if the PCB detect pressure and/or refrigerant?)
2) Internal units
On the Thermostat(remote controllers display i mean) from indoor units shows:
ERROR BUTTON MENU
I didn't press the Menu button because I didn't know.Now I know what I have to do to show the error in this display.
Maybe the next 2 weeks can I tell you what error show in display from indoor units.Thank you!
God job ,ijin Belajar 😊
Thanks
Tq sir🙏
Thanks
Please tell me vrv3 u4 alarm
All whole building all units same
Good video bon 🧿🛠️🤳🇹🇷👍
Thanks bro
How to by pass standard 2 compressor at set button press same 19 times or 20 times because I look for your video for standard 2 compressor by pass but none, Sir Bon Mj
Nice👍👍👍
Thanks
Hi sir Daikin KRP928BBS Adaptor card how to install the change over panel please thanks
Sir how we know if the std 1 or 2 compressor is already bypassed?
Check emergency settings
Good video Bon! If I have VRV4 master and slave 1, can I bypass CU slave 1 and have master CU run? Thanks
Can
@@BonMj thank you sir.
@@brandonle4930 welcome
Hy mr. Bon, I want to ask, how about multi outdoor emergency settings for the compressor?
Multi outdoor unit only can by pass the cu for vrv3(main,or slave 1 or 2)
@@BonMj that's right.. then if there is a problem with CU Slave 1, it means that vrv 3 multi outdoor unit can only by pass. which can be turned on CU main and slave 2. for CU slave 1 off (by pass) like that kah?
@@hidayaturrokhman3538 yes
@@BonMj thank you ..
@@hidayaturrokhman3538 welcome
Hi mr don ,how to contact u?
Bon Sir If the standard Compressor 1 is Defective we press the Set button 19 times for the by-pass setting But sir if the standard Compressor 2 is Defective then how many times press the set button??
In an other case if the Inverter compressor is Defective then What should we do?
If both compressor down,mean the system cant work .
This is single module?
Later i check.
Standard compressor 2 a bit different
@@BonMj yes its Single module system
Hi bon
After change new standard Compressor still high amp 9++
What is the reason??
Check cu EEV
@@BonMj 👍
Please tell me u4 alarm for vrv3
All building all units
@@amirhvaccenter5967 check communication wire, CU main pcb or indoor pcb
Sir i need inverter comp
Model JT1GCVDKYR@B
once nos. In Bangladesh
Chittagong
Please...
Sorry dun have
@@BonMj
Sir,Thank you
For your suggestions.
I change Compressor and fill gas with vacuum. Now VRV run smoothly. So many thanks again
Sir Multy unit Daikin vrv3 18hp inverter compressor bay paas codes pls help
Multo outdoor unit cant by pass compressor.
Only can by pass the cu
Hi, master
Daikin vrv 3 error L5
what was the problem, boss
Check inverter pcb and inverter compressor
@@rahulramesh9735 you replace inverter pcb?
Do you check compressor terminal?
CU meaning
Condensing unit