An VRV air conditioning breakdown | Compressor gas leakage R410a | Daikin

Sdílet
Vložit
  • čas přidán 25. 08. 2024
  • Brand : Daikin VRV3
    model : RXQ10PAY1, RXQ12PAY1
    Symptoms : power trip (RCCB) + not cold
    Cause : inverter compressor grounded and gas leakage.
    Solution: replace inverter compressor and standard compressor .
    Action : By pass the main CU for temporary use.
    #bonmj #daikin #airconditioner

Komentáře • 53

  • @jrbfyp7065
    @jrbfyp7065 Před rokem +1

    What I always did Sir Bon when there is problem with master unit is make the slave unit as master by transferring the F1 and F2 communication wire but in this video you just bypass the master unit by settings.
    I learned another things from you.
    Next time I won't do what i did.
    I will just simply bypass the master unit.

  • @robinsonguanzon8092
    @robinsonguanzon8092 Před rokem +2

    You're The Best Sir Bon MJ❤️❤️❤️

  • @matinshaikh1762
    @matinshaikh1762 Před rokem +1

    Bhai ko jackpot lag gya 😂

  • @royallan3717
    @royallan3717 Před rokem +1

    Never seen that before on Mitsubishi compressor,I’ve learnt something thanks

  • @onlyinkenyan
    @onlyinkenyan Před rokem +1

    From syd australia ,good job

  • @seymourbutts4463
    @seymourbutts4463 Před rokem +3

    Never stand in front of the terminal if it has a gas leak. I know someone that lost an eye doing that.

  • @andyreyes6464
    @andyreyes6464 Před 9 měsíci +1

    great video, do you think you could make a video about each of the vrv boards and their operations, thanks

  • @nazimsaifi2742
    @nazimsaifi2742 Před rokem +1

    Hello sir I am also vrv technician your videos it's very helpful

  • @Marcoguima45
    @Marcoguima45 Před rokem +1

    New compressor !
    Very good!!

  • @yewannahtay8949
    @yewannahtay8949 Před rokem +1

    You are the best bro i hd learn from u a loteven though im working in chilled water sys in sg.. vry appreciated.

  • @noside8469
    @noside8469 Před rokem +1

    Thank you for always sharing knowledge...
    I hope someday i/we are going to be as good as you❤👍🇵🇭

  • @IMRANKHAN-rr5ut
    @IMRANKHAN-rr5ut Před rokem +1

    Your all videos helpfull bon sir....👌🏻

    • @BonMj
      @BonMj  Před rokem

      Thanks

    • @IMRANKHAN-rr5ut
      @IMRANKHAN-rr5ut Před rokem +1

      @@BonMj. I will get the setting list from vrv 3 to vrv x

  • @muruganantham595
    @muruganantham595 Před rokem +1

    All your videos are very helpful to solve the issues for the VRV Models , can you please upload the one video for pump down method in VRV 4 System settings ..

  • @ahmad78ist
    @ahmad78ist Před rokem +1

    Thanks Sir it helps a lot

  • @somchaitachasansakool6682

    Thank U ❤❤

  • @kevinescaros8348
    @kevinescaros8348 Před rokem +1

    This is very helpful. Thanks for this.. can you please upload a tutorial how to bypass main cu or slave cu thanks sir

  • @carlocurotto7555
    @carlocurotto7555 Před rokem +1

    Nice job

  • @air-condriaservices2915
    @air-condriaservices2915 Před rokem +1

    i very 2 happy lock your video

  • @asangajayalath1665
    @asangajayalath1665 Před rokem +1

    Nice job, Mr Bon can you send compressor reading of main compressor and slave unit

  • @epicone2449
    @epicone2449 Před rokem +2

    Bon you closed the service valves in master unit right?
    And let it run in emergency mode?

  • @jonathanlarosa3279
    @jonathanlarosa3279 Před rokem +1

    Thank you master idol👍🏾👍🏾👍🏾👍🏾👍🏾👍🏾
    I have a question ⁉️ after the by pass...only one unit running...how to return the normal

    • @BonMj
      @BonMj  Před rokem

      Deactivate after repair.

    • @jonathanlarosa3279
      @jonathanlarosa3279 Před rokem +1

      @@BonMj thanks master 👍🏾👍🏾👍🏾👍🏾👍🏾👍🏾

    • @jonathanlarosa3279
      @jonathanlarosa3279 Před rokem +1

      Master I need a video how to deactivated ⁉️🙏🙏🙏 thank you

  • @daikinvrv34xallvideos80
    @daikinvrv34xallvideos80 Před rokem +1

    Good morning sir

  • @ritonsk1188
    @ritonsk1188 Před rokem +1

    How to program reset

  • @truthmatters6719
    @truthmatters6719 Před rokem +1

    Great video sir. What caused this leak?

    • @BonMj
      @BonMj  Před rokem +1

      Thanks.
      Not sure .my be high usage

  • @mymusic-tp1bh
    @mymusic-tp1bh Před rokem +1

    Sir, whether the by-pass is set after fill up refrigerant and test run completed?

    • @BonMj
      @BonMj  Před rokem

      Yes.but only slave cu is working.60%

  • @merajahmad8976
    @merajahmad8976 Před rokem +1

    I need job I have 5 year experience lg or daikin vrv 4 x

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 Před 2 měsíci +1

    Bon sir Vrv x outdoor low amp problem gas ok please tell me sir

    • @BonMj
      @BonMj  Před 2 měsíci +1

      Check gas pressure

  • @royallan3717
    @royallan3717 Před rokem +1

    What’s the electric drill gun Bon?

    • @BonMj
      @BonMj  Před rokem +1

      Let me check first.will update u.
      This is my friend tools.

  • @karaors8970
    @karaors8970 Před rokem +1

    👻👻👻👻👻🤑