Daikin VRV3 | PUMP down | Chemical cleaning | 大金冷气/药水清洗

Sdílet
Vložit
  • čas přidán 26. 08. 2024
  • This video show how to pump down Daikin VRV3 and dismantle down ducted unit evaporator coil for chemical cleaning.PLS like and share my video and SUBSCRIBE my YOU TUBE Bon Mj.请多多指教/请给我LIKE鼓励我拍更多的视频/同时按SUBSCRIBE我的YOU TUBE Bon Mj.谢谢收看。
    #daikin #bonmj #vrv

Komentáře • 95

  • @robinsonguanzon8092
    @robinsonguanzon8092 Před 2 lety +2

    We Technicians love you Sir Bon Mj
    God bless you more 🙏🙏🙏

  • @hvac2157
    @hvac2157 Před 6 měsíci +1

    All indoor should be power on.... Or not... Please clarify.. I think it should be

  • @expvlv2464
    @expvlv2464 Před 5 měsíci +1

    Apakah bisa kangsung tutup katup valve tanpa setting mode recovery pak?

  • @robinsonguanzon8092
    @robinsonguanzon8092 Před 2 lety +1

    Thanks for the share Sir Bon Mj ❤️❤️❤️

  • @riquesalvador
    @riquesalvador Před 3 lety +4

    Is there any setting to do when pumping down a VRV unit or just run the unit & close the valve like a ordinary split A/C unit

  • @dineshkumar-sn9tm
    @dineshkumar-sn9tm Před 7 měsíci +1

    Hi Bon,Any vacancy for Aircon Technician job in singapore,I have already working Experience in singapore and Gulf

  • @arifbabulotapalkatti7643
    @arifbabulotapalkatti7643 Před měsícem +1

    Please tell pump down settings bon

    • @BonMj
      @BonMj  Před 29 dny

      Daikin not allow pump down.

  • @LC-qi5ff
    @LC-qi5ff Před rokem +1

    Is there a way to pump refrigerant out of just one indoor unit to work on it?

  • @kashibaba521
    @kashibaba521 Před rokem +1

    Bon sir which setting are you enter in the system please Answering And also these settings are both for single or double module

  • @doninovithendrianto1269
    @doninovithendrianto1269 Před 3 lety +1

    Hi Mr.Bon,why mode pump down VRV IV and additional refrigerant.Tks

  • @ajithamarasekara627
    @ajithamarasekara627 Před 3 lety +1

    Thanks

  • @j26a24d
    @j26a24d Před 2 lety +1

    new air conditioning system with more efficiency than it was before

  • @arunramachandrana1025
    @arunramachandrana1025 Před 2 lety +1

    nice work

  • @user-bq7hs2qy2p
    @user-bq7hs2qy2p Před rokem +1

    How to vrv3 pump down mode please tell me Sir

  • @AljunParco
    @AljunParco Před 2 měsíci +1

    How to pump down sir ?? What botton to push..

    • @BonMj
      @BonMj  Před 2 měsíci

      Daikin not allow pump down

  • @sonukurmi305
    @sonukurmi305 Před 2 lety +1

    Sir aap ne settings nhi bataya kausa settings h

  • @hossainarif6032
    @hossainarif6032 Před 2 lety +1

    Do u use sunyo sticker lorry🤔

  • @hinlawkok5318
    @hinlawkok5318 Před 3 lety +1

    Hi Mr bon, can you conduct multi condensing pump down.

  • @angreentachairconditioning4687

    Sir what is the seting pumpdown

  • @mdmohiuddin6549
    @mdmohiuddin6549 Před rokem +1

    I don't understand how can pump down in setting

  • @WORLDBOSS00
    @WORLDBOSS00 Před rokem +1

    How did you connect the Evaporator back to the Main System.. Did you braze it in or was there some kind of quick connect line set??? Did you vaccum lineset???

    • @BonMj
      @BonMj  Před rokem

      Just connected the joint, of course must do vaccum .

  • @pappykwabee5296
    @pappykwabee5296 Před 3 lety +1

    Sir is it two pipe SYSTEM???

  • @sotirisgrig1406
    @sotirisgrig1406 Před 3 lety +1

    Ωραία δουλειά!!!

  • @BurhanSOG
    @BurhanSOG Před 3 lety +1

    nice clenn..

  • @BERESHIDA2008
    @BERESHIDA2008 Před rokem +1

    Trabajo de chinos quitar ese evaporador , buen trabajo

  • @allanfernando5358
    @allanfernando5358 Před 3 lety +2

    Sir I am working in abu dhabi, I want to have proper training in vrf installation and maintenance, can you advise me where is the best place. I have 30 years experience In chilled water systems and in high rise building. I will wait for your reply. Thanks 😊

    • @BonMj
      @BonMj  Před 3 lety

      Mitsubishi or Daikin

  • @peramaraj2763
    @peramaraj2763 Před 2 lety +1

    Hi sir ,i have one doubt before pump down what is the set the system to prepare for system pump down ?

    • @BonMj
      @BonMj  Před 2 lety

      Better normal pump down.just lock the valve

  • @teohszetat8089
    @teohszetat8089 Před 3 lety +1

    Hi Mr Bon, Can share the setting or method to conduct pump down for VRV 3 and 4 ? thanks in advance

  • @satechengineeringservices31

    Hello Bon Sir! Am your big fan..... And I also want to work with you!

  • @tora_100
    @tora_100 Před 3 lety +1

    How about vrv A need set mode?

  • @henntan5979
    @henntan5979 Před 3 lety +1

    hi mr bon may i know we must do tis setting before pump down?

    • @BonMj
      @BonMj  Před 3 lety +1

      You can lock the valve direct pump down more easy.

    • @henntan5979
      @henntan5979 Před 3 lety +1

      @@BonMj may i know tis 20 times setting is for what purpose thks

    • @BonMj
      @BonMj  Před 3 lety

      @@henntan5979 pump down vrv3

  • @yenaing3764
    @yenaing3764 Před 3 lety +1

    Sir . It is setting mode 1 or 2 for pump down VRV system . Thanks sir

    • @BonMj
      @BonMj  Před 3 lety

      Do you do emergency setting before

    • @yenaing3764
      @yenaing3764 Před 3 lety +1

      @@BonMj yes, now I see your video but I see you pump down is single outdoor only if multi outdoor system how going to do ? Sir thanks you 🙂🙂🙂

    • @BonMj
      @BonMj  Před 3 lety +1

      @@yenaing3764 same

    • @yenaing3764
      @yenaing3764 Před 3 lety +1

      @@BonMj thanks sir

  • @hvacandvrvspecialvedoindus7891

    Pumdon settings sar🙏

  • @mommyyen4537
    @mommyyen4537 Před 2 lety +1

    嗨,你们好,我们买了一架daikin,冷气2,3年龄 现在问题解决不了,其实去年已经有了问题我们不知道就以为没gass,叫人来洗和进gass 问题改善了一点现在又严重了,自动关机,我已经是60多岁了,一晚关机几次现在天气太热,没冷气怎样睡,真是上火了,才那么新的机就这样,我的运气不好,如果daikin,的人看到请教教我要怎么做???

    • @BonMj
      @BonMj  Před 2 lety

      你好,谢谢你观看我的视频。
      最近天气的确很热,根据你说的很有可能冷气机发生故障或有其它原因。
      如果是真的之前冷媒不足而造成故障,或许这次是同样问题。
      如果是真的冷媒不足,那需要测漏。
      我不是大金员工,但是我了乐意给你提供意见。

  • @aselajayasundara1669
    @aselajayasundara1669 Před 2 lety +1

    Sir may a/c uinit vrv 3 error ua help me

    • @BonMj
      @BonMj  Před 2 lety

      Do you replace outdoor cu PcB?

  • @janshaw5472
    @janshaw5472 Před 3 lety +2

    圣淘沙游艇俱乐部啊(⊙o⊙)

  • @pappykwabee5296
    @pappykwabee5296 Před 3 lety +1

    Also how do you release the gas out once you have finished??do you do another settings?please

    • @BonMj
      @BonMj  Před 3 lety

      Just do normal pump down

    • @pappykwabee5296
      @pappykwabee5296 Před 3 lety +1

      @@BonMj sir I mean how do you release the gas into the whole system for the system to run

    • @BonMj
      @BonMj  Před 3 lety

      @@pappykwabee5296 pump down

  • @user-jj7de7wl2o
    @user-jj7de7wl2o Před rokem +1

    Bon sir,請問pumpdown mode怎樣set?

    • @BonMj
      @BonMj  Před rokem

      早安。
      其实我问了Daikin.
      Daikin VRV不能pump down.
      其实是recovery mode.

    • @Wilsonchan31
      @Wilsonchan31 Před rokem

      @@BonMjrecovery mode 是什么意思呢?就是说不需要setting,直接锁valve 像普通pump down就好了吗??

  • @hermanfung5437
    @hermanfung5437 Před 2 lety

    How to pump down ? Can not see clearly.

  • @cheenengloo8965
    @cheenengloo8965 Před 3 lety +1

    hi.,this vrv 3 Press with button to pupm down the system?thx

    • @BonMj
      @BonMj  Před 3 lety

      Set button

    • @cheenengloo8965
      @cheenengloo8965 Před 3 lety

      @@BonMj thx..so set with button😭

    • @BonMj
      @BonMj  Před 3 lety +1

      @@cheenengloo8965 BS2

    • @cheenengloo8965
      @cheenengloo8965 Před 3 lety +1

      @@BonMj Okok..can I learn with you how to set,thx

    • @BonMj
      @BonMj  Před 3 lety

      Do you pump down the system before,

  • @sachinshettyacwork1102

    How to pump dom vrv

  • @vijayanathanstephen9308
    @vijayanathanstephen9308 Před 2 lety +1

    Teekhey bhai !

  • @muhdamin754
    @muhdamin754 Před 3 lety

    Vrv 3 boleh pump down ke ?

    • @BonMj
      @BonMj  Před 3 lety +1

      Boleh bro

    • @muhdamin754
      @muhdamin754 Před 3 lety

      @@BonMj apa code setting ye ?

    • @BonMj
      @BonMj  Před 3 lety

      @@muhdamin754 set 20 kali

    • @muhdamin754
      @muhdamin754 Před 3 lety

      @@BonMj ohh code in code out sama saje kan ?

    • @BonMj
      @BonMj  Před 3 lety

      @@muhdamin754 ya,u tahu cara setting kan.sama saja.

  • @pawankumar-er3rr
    @pawankumar-er3rr Před 3 lety +1

    🙏 🙏 जय श्री राम 🙏 🙏

  • @carlosdavila9486
    @carlosdavila9486 Před 3 lety +2

    U did not really teach nothing ... dont wear jewelry working on a high voltage unit where gloves atleast

    • @BonMj
      @BonMj  Před 3 lety +2

      Thank you for remind.

    • @pappykwabee5296
      @pappykwabee5296 Před 3 lety

      Sir please provide glooves for your guys

  • @shoyabahmed2652
    @shoyabahmed2652 Před 3 lety +1

    Sir it's set mode 2 and set 20 times then what should I do bcoz I never did before this system when you have time pls massage and thanks again for your important video

    • @BonMj
      @BonMj  Před 3 lety +3

      Mode x1
      Set x20
      Return x1
      Set x1
      Return x2
      Mode x1

    • @MR_RC88
      @MR_RC88 Před rokem +1

      @@BonMj im your subsciber how many times i press and what i press when i bypass master cu thanks.

    • @BonMj
      @BonMj  Před rokem

      @@MR_RC88 by pass master cu
      1)press mode button more than 5second
      (Until led H1P on)
      2)press set button 38 times
      3)press return button once
      4)press set button once
      5)press return button twice
      6)press mode button once to exit