How to Fit an Isolation Valve on Copper Water Pipe

Sdílet
Vložit
  • čas přidán 12. 12. 2018
  • Isolation valves are a wonderful thing and Roger loves fitting them wherever he can. You might recognise this boiler room, it's the fourth episode we've shot in here. This job takes a while so you'll also get a bit of Roger's insight, some gripes, plumbing history and general musings from a man that has much to share with the audience that he loves.
    Isolation valves or service valves are a life and time saver. We'll show you how to fit an isolation valve to copper water pipes so that your appliances can be disconnected from the main water supply quickly and easily.
    We prefer an isolating valve with a handle and the one used in our video is an Intaball Lever Ball Valve with red handle from Altecnic Plumbing and Heating Supplies.
    #plumbing #boiler #DIY
    ===================================================
    Don't forget to stay up to date with Skill Builder!
    Get in touch and send us your pictures and videos - skill-builder.u...
    See our Tweets - / skillbuilderuk
    See our Facebook Page - / skillbuilderchannel

Komentáře • 236

  • @neilphilip2320
    @neilphilip2320 Před rokem +4

    I'll give you a life supply of pipe cutters if you convince my wife that all she needs to do is select one (or more) of her multitude of jumpers when it get gold outside. I'll even provide you with suitable safety gear for your visit! Brilliant channel.

  • @leehotspur9679
    @leehotspur9679 Před 3 dny

    Just started doing a bit of Reno work here in NZ Thanks for all of your vids always instructional and interesting Thanks again Roger

  • @windspoint
    @windspoint Před 3 lety +20

    It might seem a bit obvious but to us less confident it would be nice to see an example of how best to measure the fitting for the amount of pipe to cut out to accommodate the valve!

    • @Paul_707
      @Paul_707 Před rokem +10

      Use a couple of pieces of off cut pipe, say 150mm long each. Insert them into the valve and measure the total length. The excess over 300mm is the figure you need.

  • @wetpaints8490
    @wetpaints8490 Před 5 lety +4

    Love watching skill builder vids. Taught me how to solder. Just fitted two new radiators in my extension, SDS chiseled my floor up, layed two new pipes, plumed everything together. Probably didn’t save money as had to take time off work to do it. But.....having a new (talent is the wrong word) talent is awesome 😎. Cheers big man. Have you got a “Patron? Account, you should get one.

  • @johnabbiss43
    @johnabbiss43 Před 14 dny

    Thanks 🙏 for sharing this with us 👍🏻

  • @paulross7204
    @paulross7204 Před 5 lety +5

    I sit behind a desk all day. That was like therapy I could watch you all day long, in fact most enjoyable thing I’ve seen today. Can you put those valves on potable supplies. I use ball valves but they tend to weep over time.

    • @djyul
      @djyul Před 5 lety

      It is a ball valve

    • @SkillBuilder
      @SkillBuilder  Před 5 lety +5

      Yes they are good for high pressure and potable supplies. The cheap ball valves are a liability but lots of people fit them just to tick a box. Then it is somebody else's problem.

    • @m.o.2085
      @m.o.2085 Před 4 lety +1

      @@SkillBuilder Amen! They should be outright banned, no wonder you can't find them anywhere in Europe. Is it another UK novelty? Utterly useless.

  • @chrisf5475
    @chrisf5475 Před 2 lety +1

    Found this to get some info… didn’t expect to be so entertained. Brilliant 😄

  • @harryham1
    @harryham1 Před 5 lety +5

    Love that Life of Brian reference that the cameraman managed to slip in there.

  • @StephenSmith-yy5xx
    @StephenSmith-yy5xx Před 2 měsíci

    I searched for how to fit a compression valve into a run of pipe. But with one end loose, its the same as fitting a valve onto new work - thanks for showing the PTFE tip, so I learned something. I'd really like to see how to fit one in a run of pipe where there is no play in one of the ends of piping.

    • @SkillBuilder
      @SkillBuilder  Před 2 měsíci +1

      we will do that, we have a solution

  • @flycow69
    @flycow69 Před 5 lety +4

    Greetings from New York City. Good work, love the accent.

  • @TheAudiostud
    @TheAudiostud Před 5 lety +4

    Roger! You wouldn't last five minuets on my site! You'd probably spend all day looking at my eclectic hoard of videos! Thanks for another cracking shorty Skill Builder Team Great Work Well Done!

  • @iameccles
    @iameccles Před 5 lety +4

    the cameraman questions are a nice twist from the norm. "hidden depths lol"

  • @berkayultraslan1
    @berkayultraslan1 Před 5 lety +2

    I love that ptfe technique around that olive

  • @Alan_Edwards
    @Alan_Edwards Před rokem

    I am adding isolation valves for my 1st floor shower in preparation for a bathroom remodel. I normally would sweat in a valve, but there is no way I will be able to fully stop the water flow so going with compression valves makes sense and it sure looks a lot easier. I have never seen anyone put Teflon tape on the compression ring, but since I am concerned about leaks I think I will give it a go. Thanks mate.

  • @tedfusco3472
    @tedfusco3472 Před rokem

    . Thanks, you just solved a problem . I didn't know they made ball values with compression fittings. Now I won't burn down my house trying to solder one in.

  • @williammcgrattan9583
    @williammcgrattan9583 Před 5 lety +1

    Good job Roger 👍

  • @zedman442
    @zedman442 Před 5 lety +5

    Little PTFE round an olive goes a long way. Lived by that for years. Like you believe in helping the next person out. I also put in a isolated loop with one radiator to a combi boiler so you can drain down but keep hot water on for the customer.

    • @williammcgrattan9583
      @williammcgrattan9583 Před 5 lety

      Or a little bit of Hawk White paste would be equally just as good. It's good stuff.

  • @Maker76
    @Maker76 Před 5 lety +1

    Guys, finding your channel really useful, easy to follow and I assume would offer the diy'er lots of confidence to tackle the simple stuff. Keep it up, I'm really enjoying your videos, working my way through the them.

  • @dannechita8577
    @dannechita8577 Před rokem

    something new learnt today. cheers

  • @robmarrin6720
    @robmarrin6720 Před 4 lety

    My name is robin and it means work's with water, and I was an alarm engineer and became a creator of exquisite bathrooms as yourself,, I'll send some pics to your link below 👍the irony is I've worked with water for 15 years now after 12 in alarms, and only two years ago did I discover what robin means😂😂

  • @jerrymcg3199
    @jerrymcg3199 Před 3 lety

    Great video.
    You are the only one on YT to show it being done on an installed pipe. All the videos on YT show valves and compression couplings being fitted onto loose pieces of pipe on a bench.
    A child could do that. The problem is where there is no give in the pipe.
    I have been trying to find how to insert a piece of copper pipe between two compression fittings to join two pipes with no give, without success.

    • @SkillBuilder
      @SkillBuilder  Před 3 lety +1

      You need a slip coupling. They are available as repair couplings solder or compression.

    • @jerrymcg3199
      @jerrymcg3199 Před 3 lety

      @@SkillBuilder Thank you for the reply. My problem is that my pipe diameter is 18mm and I've searched but never found slip couplings in that size.

  • @beneveleigh8840
    @beneveleigh8840 Před 3 lety

    Excellent plumber

  • @ratchriat1716
    @ratchriat1716 Před 5 lety

    in my opinion a lever ball valve they are the best easy and safe to use enjoyed the video.

  • @london_roubenl
    @london_roubenl Před 3 lety

    Really enjoyed this video, thanks for your knowledge and time.

  • @the-colonel9809
    @the-colonel9809 Před 5 lety +1

    Always enjoy the videos Roger keep up the good work

  • @stephenhodges4933
    @stephenhodges4933 Před 4 lety

    great stuff simple and straight forward but hints at problems others may get

  • @BHANGUVIDEOSUK
    @BHANGUVIDEOSUK Před 3 lety

    Great man! I learning lot from your videos. You are Clint Eastwood of "PLUMBWOOD".

  • @johndowney8713
    @johndowney8713 Před 3 lety

    Great videos.

  • @stephenhookings1985
    @stephenhookings1985 Před 3 lety

    Great tip on how to "flow" the PTFE onto pipe. And I always wondered how to fit the into existing pipework - now we know.

  • @chloehelliwell
    @chloehelliwell Před 3 lety

    Really enjoying these videos, Thanks Roger!

  • @nickcollins7568
    @nickcollins7568 Před 5 lety +7

    Those full bore lever ball valves are brilliant. I have long since given up fitting gate valves. They are way too unreliable as they invariably leak or let by!!!

  • @robmarrin6720
    @robmarrin6720 Před 4 lety +2

    Sheer class, if you don't have luck you need money ❤️👍

  • @alanmullock381
    @alanmullock381 Před 5 lety +2

    Oooohhhhh! Spanner envy!👍👍👍👍👍👍👍🤣🤣🤣🤣🤣🤣🤣🤣

  • @lovingitandlife
    @lovingitandlife Před 2 lety

    always enjoy your videos,as a carpenter i've always asked plumbers how to do things and they have been always helpful. i notice you put ptfe tape on the pipe,i always thought and done it on the thread,have i been doing it wrong,did like your way though.thanks, mark.

  • @paulashford7509
    @paulashford7509 Před 5 lety

    Good videos for someone like me, who knows very little....

  • @uffiserviceuk5377
    @uffiserviceuk5377 Před 2 lety

    Nice channel 👍

  • @mango3586
    @mango3586 Před 5 lety

    all your videos are interesting sir

  • @karimabdullah2925
    @karimabdullah2925 Před 5 lety

    love this guys videos. Highly entertaining guy

  • @240soundwave
    @240soundwave Před 5 lety

    PTFE tape, Truth to Power. Praise!

  • @grrinc
    @grrinc Před 5 lety +4

    Question Roger.... are there standards that need to be taken into account when fitting isolating valves onto central heating systems? Ta.

  • @Chanesmyname
    @Chanesmyname Před 5 lety +1

    Actually, now I've watched the whole video, the Aladin isolator would have made your life far easier. :)

    • @markroper6188
      @markroper6188 Před 5 lety

      Chanesmyname they are good when you have no other option- but £40 vs a fiver... plus the system was drained down

    • @Chanesmyname
      @Chanesmyname Před 5 lety +1

      @@markroper6188 I know that price difference is chunky but saving the trouble of draining down and for the speed of the fit and for a one off item, I like the ease of it and I think there is less than go wrong with the fit too - no undue pressure on pipe lengths to tweak at other joints when flexing them to fit into the pipe cut out...no pipe slice either. :) Lazy and lacking great skills I admit it and that aladin valve is best for me as an odd job and not a being a well-skilled plumber. :)

  • @carguillo1
    @carguillo1 Před 5 lety

    Hi Roger its kev love that spanner take care mate

  • @SuperTannoy
    @SuperTannoy Před 5 lety

    Very informative, very amusing, love it.

  • @gdfggggg
    @gdfggggg Před 5 lety

    Push fits mate, Bosh, owzya fava 👍🏻

  • @johnriggs4929
    @johnriggs4929 Před 3 lety +3

    PTFE tape on olives... "Nah, you don't need to do that..."
    You do if you buy 'em from Screwfix

    • @mr.d7372
      @mr.d7372 Před 3 lety +1

      Totally agree. PTFE very amateurish. But where does one buy good olives these days?

  • @dansmith436
    @dansmith436 Před 5 lety +13

    2:47 .. cant be the only one who saw the monkey in top left corner ? :O

    • @alwoolhouse6255
      @alwoolhouse6255 Před 4 lety +1

      Blimey Charlie but you’re right. SkillBuilder does Easter Eggs!

    • @markeverson1385
      @markeverson1385 Před 4 lety +1

      i can only see a one Monkey. Robin is better on his own.

  • @ThePhilandPam
    @ThePhilandPam Před 5 lety +3

    I used to use ptfe on the olives but now use Jet Lube V-2 Plus, never had a leak yet, any experience of this or thoughts?

    • @mp9748
      @mp9748 Před 4 lety

      TheP Jet lube is the way mate. PTFE on a olive is bad news

    • @roybennett206
      @roybennett206 Před 3 lety

      @@mp9748 why is PTFE bad news ?

  • @MontyVideo969
    @MontyVideo969 Před 5 lety +1

    I noticed you wound the PTFE tape (@3:30) the same way for both the left and right olives - doesn't that mean that the right hand tape is going to "undo" when you tighten your nut?

    • @SkillBuilder
      @SkillBuilder  Před 5 lety +1

      Hi Patrick
      The olive doesn't move as the nut is tightened so there is no tendency

    • @bigdavey69
      @bigdavey69 Před 3 lety

      Real plumbers don’t use ptfe on olives we use jet lube

  • @steveprice9462
    @steveprice9462 Před 5 lety +5

    Hi, how did you decide how much of the copper pipe to cut out? Thanks.

    • @88CBAUGH
      @88CBAUGH Před 3 lety

      I was wondering about that myself.

    • @broadwayFan28
      @broadwayFan28 Před 3 lety

      I'm at the same point. I need to know how much copper to remove from 3/4" copper pipe before installing the ball valve. Worse, it runs through joists that are 2 feet apart.

  • @roybatty2030
    @roybatty2030 Před 7 měsíci

    Ensure the valves are full bore and check if they have an arrow for flow direction.
    I usually tighten the fittings, loosen them off and apply PTFE then finally retighten.

  • @LewisCowles
    @LewisCowles Před rokem

    What do you think about the self-tapping Aladdin isolators?

  • @roberthatcher2773
    @roberthatcher2773 Před 5 lety

    Should I change all my 30 year old Gate Valves for Lever Valves on next drain down of Hot/Cold and CH? - Some Gate Valves stiff as hell to turn!

  • @bahopik
    @bahopik Před 5 lety +1

    How do you guys bend pipes like that? Never it seen it before, do you anneal s section or something? Nice pipe hangers by the way I wish these were available to me

  • @jamesdooley713
    @jamesdooley713 Před 4 lety

    Well Roger , im a carpenter with no plumbing experience but i want to learn, what videoes should i start watching of yours to learn as much plumbing as possibel off of you?

  • @declan3906
    @declan3906 Před 3 lety +3

    "In classical Greece, "speaking truth to power" was known as parrhesia. ... Noam Chomsky is dismissive of "speaking truth to power". He asserts: "power knows the truth already, and is busy concealing it"."

    • @grotekleum
      @grotekleum Před 3 lety

      I think Noam Chomsky is right.

  • @robmarrin6720
    @robmarrin6720 Před 4 lety +1

    Have you got a link to the nut spanner used on the lever valve's 👍❤️ great workmanship, or workpersonship but that sounds strange man, 😂👍❤️

    • @88CBAUGH
      @88CBAUGH Před 3 lety

      It's a split ring compression fitting spanner 15mm / 22mm. On Ebay for about £12, or Amazon for a couple of quid more.

    • @kevwade63
      @kevwade63 Před 2 lety

      Toolstation £8

  • @marcck5597
    @marcck5597 Před 5 lety +2

    Offset the valves. Use jointing compound. Mark the pipe before you cut. The full bore lever valve handles should always fall into the off postion, against the flow.
    If your gonna show someone how to do something, do it right. For there benifit.

    • @prplumbing7869
      @prplumbing7869 Před 5 lety

      If you are getting on your high horse then learn to spell right you illiterate troll

    • @ciaranamhain
      @ciaranamhain Před 2 lety

      Agreed except I don't think I'd want a valve falling to closed on a heating circuit.

    • @endurojimmy3109
      @endurojimmy3109 Před rokem

      @@ciaranamhain I've worked in boiler houses for about 30 years.
      All lever op valves must fall to close, any valve which has the potential to cause damage to a system would be lockshield or similar.
      In fairness there's so many safety interlocks nowadays that any closed valve would protect and stop the system anyway.

  • @samacochan
    @samacochan Před 4 lety

    At 1:35 you are cutting some pipe to install a ball valve, how much did you cut off ? What's the measurement ? Thanks

  • @pooleheating
    @pooleheating Před 5 lety +2

    The lever valve unlike a ballofix doesn't have a direction of flow as being a lever valve it should always fall to close.

  • @ianjonas7925
    @ianjonas7925 Před 2 lety

    Hi Roger, out of pure interest, and I know the unit is a fairly costly initial outlay, but why do many plumbers not use one of the lovely Rothenburger Pipe Freezers?
    I've used one a few times before to replace radiators and they are a godsend in terms of speed.

    • @SkillBuilder
      @SkillBuilder  Před 2 lety +1

      I have used the electric freezers but most of the time there are ways and means that are straightforward.

  • @espenklingsheim978
    @espenklingsheim978 Před 5 lety +6

    You would be welcome on my site.

  • @stakkerhmnd
    @stakkerhmnd Před 5 lety +1

    1st. Firsted. Fit an isolation valve on copper water pipes ! You know it makes sense !

  • @bigbadgaz1
    @bigbadgaz1 Před 3 lety

    8:35 Monty Python reference , nice :)

  • @unknownmale
    @unknownmale Před rokem

    I'm replacing the radiators on one floor and want to put some lever valves in so I can shut down the flow and return on that floor and have the heating for the rest of the house up and running while i modify the pipe work up to the new radiators, might take a week or so with the additional work to the walls/plaster etc. Is there any reason I can't use these valves for this purpose? It's a big house and takes a long time to drain down!

    • @SkillBuilder
      @SkillBuilder  Před rokem +1

      Hi David
      That is precisely what they are used for so long as the system is unvented

    • @unknownmale
      @unknownmale Před rokem

      @@SkillBuilder Thanks for the reply! It's a vented system

    • @unknownmale
      @unknownmale Před rokem

      @@SkillBuilder SHould I use gate valves for an F&E system

  • @WilliamSiggery-oq8lx
    @WilliamSiggery-oq8lx Před 3 lety

    Roger what do you know about cracks in walls on extension how to fix

  • @angelinthedocks3732
    @angelinthedocks3732 Před 5 lety +2

    P.T.F.E on the olive is fine but wrapped around the thread on a compression fitting is fairly pointless imo. Fernox LS-X and hawkwhite both have their place.

    • @SkillBuilder
      @SkillBuilder  Před 5 lety

      Swanseal is my favourite gunk

    • @whitacrebespoke
      @whitacrebespoke Před 5 lety

      I did a kitchen in the summer and client did their own plumbing all with compression fittings I think he must have used about 5 rolls of tape. Olives threads the whole works all taped up.

    • @williammcgrattan9583
      @williammcgrattan9583 Před 5 lety

      I'm a jet lube v2 man, coz I'm special. Lol

  • @bikerchrisukk
    @bikerchrisukk Před 5 lety

    great video again, i wonder what you think and what you've heard of about those isolating valves that clamp on and pierce the pipe? I know they're only supposed to be for jobs where you can't turn off the mains water but would still be interested in your thoughts. Cheers !

  • @chrisharries2463
    @chrisharries2463 Před rokem

    How wide is the gap between pipes then.

  • @Chanesmyname
    @Chanesmyname Před 5 lety +1

    Could you have fitted an Aladin isolator valve? You can use them on live feeds too.

    • @Razz60
      @Razz60 Před 4 lety

      They cost about £50

    • @800Viffer
      @800Viffer Před 4 lety

      @@Razz60
      How much would it cost for an engineer to drain down and refill the system with another dose of inhibitor?

  • @hectorheath9742
    @hectorheath9742 Před 3 lety

    what about the burrs your blunt pipe cutter leaves behind?

  • @ahinesbm9105
    @ahinesbm9105 Před 3 lety

    Hello Roger i have question when i put thw water on in the bathroom and turn the water on in the kitchen the pressure is droping can it be fix ?

    • @SkillBuilder
      @SkillBuilder  Před 3 lety

      You can only get out what you put in. If the pressure is low on the mains you won't get much out. Have you got a combi boiler?

  • @calsitup
    @calsitup Před 3 lety

    I noticed you put the ptfe tape on same way as the direction of nut on the left. Then did the same on the right olive opposite direction of the nut. Is this normal ?

    • @SkillBuilder
      @SkillBuilder  Před 3 lety

      It doesn't matter because it is on the olive and the olive doesn't turn

  • @MT_T991
    @MT_T991 Před 5 lety +1

    What's your main interest outside of plumbing

    • @SkillBuilder
      @SkillBuilder  Před 5 lety +8

      Cycling; since I was 11 I have ridden my bike all over the place.
      Reading. I probably only read around 20 books a year but would love to read more and have a lot stacked up for my retirement.
      Rock climbing but I do less than I used to.
      Travel. I love to go anywhere.
      Camper Bus We go away abroad in the camper bus about 5 times a year and that always involves a lot of cycling.
      Photography I take lots of pictures for magazines and i would love to be better at it

  • @1xstew
    @1xstew Před 3 lety

    I have to fit an external expansion tank to my combi boiler, so I know I need to put a Tee in the return pipe to the boiler to feed my new expansion tank.
    I don't want to drain the system.
    Can't I buy a freeze kit and freeze the pipe below the Tee and close off the isolator to the boiler above the Tee so only a small of water will spill out the bit of pipe below the isolator valve.
    Be easier to draw a diagram I know . . Tried to be as descriptive as I can!

    • @SkillBuilder
      @SkillBuilder  Před 3 lety

      You can buy a tee that is made for this very job. It makes a tiny hole in the pipe and that is plenty to allow the expansion vessel to work.

    • @1xstew
      @1xstew Před 3 lety

      @@SkillBuilder That will save me a lot of work . . What exactly do they call this Tee? Are they on eBay?
      Thanks for this.

    • @stewartc3954
      @stewartc3954 Před 3 lety

      @@SkillBuilder Hi again . . tried searching for thisTee but cant find it. Please help. Stewart

  • @fablan3308
    @fablan3308 Před rokem

    Can I use one of them instead of a mains tap

  • @letsgocamping88
    @letsgocamping88 Před 5 lety +5

    You’re sounding like an electrician.

  • @loafersheffield
    @loafersheffield Před 5 lety

    "Picking up the wrong end of the stick," is derived from Roman plumbing. They would have communal latrines with streams diverted through two channels. One for sitting over to flush through the poo etc and another into which they would dip a stick with a sponge tied to the end for washing ones derrière. Then the stick/sponge would be put back down for the next bloke to pick up... and then the next... and then the next and so on.

    • @JuiceBanger1
      @JuiceBanger1 Před 3 lety

      The rule of thumb comes from, don't use a stick thicker than your thumb, to beat your wife.....

  • @cskeise
    @cskeise Před 4 lety

    ROGER...💙👊😃🔧

  • @cglees
    @cglees Před 4 lety

    Roger, love your work. Quick question...I’ve been fitting isolating ball valves on all of my pipework during my bathroom refit that I’m doing. They work for me. Anyway I’ve been told that they will reduce the flow and I should have used full bore valves like you have in this video. Some of them are for my new bath, sink, toilet etc. Should I replace them all before it’s too late? Thanks in advance, Chris.

    • @SkillBuilder
      @SkillBuilder  Před 4 lety +2

      Hi Chris
      The problem with isolating valves is that they weep around the glands unless you spend a lot on them and when you spend a lot they tend to be full bore. Most plumbers I know wouldn't touch an isolating valve when carrying out a repair or service. You go in to service a tap and end up having to drain down and replace the valve.
      Now they are in I would leave them. If you have mains pressure they won't slow the flow much, if it is tank fed you might want to remove them on the shower and fit full bore.

    • @cglees
      @cglees Před 4 lety

      Thanks for the swift reply Roger! So far I have just removed the old suites and put the isolating ball valves on so that I could refill the system for the rest of the house. It’s not too late, I could drain down again and remove them when I fit the new suite. I’m going to fit the abacus wall mounted system and will have a gasket like in your video to individually control each service for future maintenance.
      I had no idea the ball valves were so unreliable.
      It’s not mains.
      What about if I drain down again and fit full bore gate valves on my hot and cold feeds?

  • @mansoorhussain1797
    @mansoorhussain1797 Před 4 lety

    Can you do a video on traps

  • @xxSweetStrangerxx
    @xxSweetStrangerxx Před 3 lety +1

    Do you need permits to do this job?

  • @THECARKUS
    @THECARKUS Před 5 lety

    Roger... Dude, that pipe slice is causing me anxiety :-) You need to change that wheel... And Bahco is my favourite. Their adjustable spanners are the kings! Love your work. Thanks yet again!

    • @SkillBuilder
      @SkillBuilder  Před 5 lety

      I slung it in the bin. Got a new one. Happy days

  • @RollCorruption
    @RollCorruption Před 3 lety

    Does the direction of the PTFE tape matter? I'd assume not given the olive is just compressed and not rotated? I'd assume you would want to avoid it backing up on itself?

    • @SkillBuilder
      @SkillBuilder  Před 3 lety +1

      Out of habit I run it clockwise but, as you say it only sits there and has no thread sealing function.

  • @craig5832
    @craig5832 Před rokem

    What's with the gorilla in the top left corner at 2:47 ? I thought I was seeing things 🤣🤣

  • @dhuryodhankaurav8487
    @dhuryodhankaurav8487 Před 9 měsíci

    The valve doesn't need any threading on the pipe?

  • @seanditch4419
    @seanditch4419 Před rokem

    Hiya, How did you know how much pipe to cut out please?
    thank you for this video.

    • @amg863
      @amg863 Před rokem

      He didn't. If you watch the video he plays with the pipe to give himself more room to fit the valve in. When it doesn't work, he cuts off a tiny bit more.
      Trial and error. Push the pipe as much as you can or cut off a bit more.

    • @seanditch4419
      @seanditch4419 Před rokem

      @@amg863 Exactly, so he must've known how much extra he needed to cut because he first lined the valve up to check, which is why i asked
      "How did you know how much pipe to cut out?" I'm guessing trial and error isn't something that you can do too often before you knackering the job up.

    • @amg863
      @amg863 Před rokem +1

      @@seanditch4419 it doesn't have have to be super precise. just cut a little and try again if you still don't have enough room. If you cut too much by accident you can always buy a length of 15mm copper pipe for less than a tenner and patch up the gap.
      Or if you're really worried about it, you can buy self-cutting isolation valves which are pretty much fool-proof but I don't think plumbers will recommend them because it's not the "proper" way to do it but it worked for a lot of diyers.

    • @seanditch4419
      @seanditch4419 Před rokem +1

      @@amg863 Ahhhh right, great stuff, i thought he was measuring an exact precise distance between two points on the valve.
      I've seen those Aladdin self cutting valves and was told that they themselves would only use them in an extreme emergency, because apparently they fail quite quickly.
      Thanks for your help clearing that up for me....👍👍👍👍👍👍👍👍

    • @amg863
      @amg863 Před rokem +1

      @@seanditch4419 I have a self cutting valve for an outdoor spigot that's been there since before I moved in and it hasn't leaked yet. It reduces the water pressure a little bit though. It's not as good but it's not bad either.
      Cheers

  • @djyul
    @djyul Před 5 lety +3

    Bacho in Holland is a Bacardi cola :)))

  • @yensabi
    @yensabi Před 5 lety

    Why not freeze the pipe Roger instead of draining a large system down and then having the hassle of bleeding a dozen rads , that's what I would do , I've got a couple of those open ring spanners and I agree they are brilliant also Kopex make the best pipe slices I have ever used
    Cheers mate....👍

    • @SkillBuilder
      @SkillBuilder  Před 5 lety +8

      Yensabi, I have done a bit of freezing in my time but I was removing the old towel rail and re-routing the supplies. I couldn't lift the floor so I did the whole job at arm's length with some push-fits. These jobs are stressful enough without putting myself under extra time pressure. The time I froze a mains pipe and went out to the van for the spare gas canister and the van had been towed away still lives in my memory.

  • @k20aa
    @k20aa Před 5 lety +4

    Christ by a new 22 slice lol

    • @SkillBuilder
      @SkillBuilder  Před 5 lety +2

      I have one but this one keeps surfacing. I know it is wrong but with me it is all about the hardship.

    • @k20aa
      @k20aa Před 5 lety +1

      I know the felling I can always find the crap one in my tool box . The new one always hides @@SkillBuilder

    • @SkillBuilder
      @SkillBuilder  Před 5 lety +3

      @@k20aa
      I binned the old one this afternoon, invested in a new Monument Pipeslice. I can't retire now. Onwards and upwards.

    • @k20aa
      @k20aa Před 5 lety

      Good work . Think of the extra years on your wrist lol@@SkillBuilder

  • @declansmith1692
    @declansmith1692 Před 2 lety

    Not put uni white on rings?

  • @vicventurini3786
    @vicventurini3786 Před 2 měsíci

    V2 plus on any compression fittings involves water! Not PTFE!

  • @RosskillbaneC
    @RosskillbaneC Před 5 lety

    Do you have the qualification for an unvented cylinder

  • @rimmersbryggeri
    @rimmersbryggeri Před 5 lety

    BAcho is now owned by Snap On.

    • @sadiqmohamed681
      @sadiqmohamed681 Před 5 lety

      And the other company, projectors and video monitors, is BARCO. I think they are Finish.

  • @redwarrior260
    @redwarrior260 Před rokem

    Don’t you have to deburr the ends of the pipes that are cut?

    • @SkillBuilder
      @SkillBuilder  Před rokem

      I never deburr and I don't know any plumber that does. Imagine the miles of pipe I have installed all wrong

  • @vistron888
    @vistron888 Před 5 lety

    On the original internet talkboards was a DIY group. Was a little clique that thought they ran the place & the usual forum sycophants. They would always bleat on about how you shouldn't use PTFE tape, it should be a cold weld..etc etc. Any other view was shouted down. Kind of people who would argue with a wall.

  • @stevendouglas3860
    @stevendouglas3860 Před 5 lety

    What brand was that, 15mm/22 spanner and how much (a must buy )...Roger ..
    And what brand is that isolation valve . Thank you

    • @letsgocamping88
      @letsgocamping88 Před 5 lety +1

      dirty girl also wanting to know

    • @SkillBuilder
      @SkillBuilder  Před 5 lety +1

      Today' Tools www.ebay.co.uk/p/Todays-Tools-Plumbers-Split-Ring-Compression-Fitting-Spanner-15mm-22mm-SCSR/1869330716?iid=253696564090

    • @stevendouglas3860
      @stevendouglas3860 Před 5 lety

      @@SkillBuilder looks long that spanner 😉 I wonder how long 😲

    • @pauladventure
      @pauladventure Před 5 lety +1

      THEY ARE £7.98 FROM TOOLSTATION

    • @stevendouglas3860
      @stevendouglas3860 Před 5 lety

      @@pauladventure the long spanner or valve .

  • @hinguyen9584
    @hinguyen9584 Před 3 lety

    What is the brand of this valve?

  • @GrahamOrm
    @GrahamOrm Před 5 lety +1

    PTFE always a good idea on brass olives, they're crap. I don't do it with copper olives. Buy a new pipe slice you old miser! EDIT: Ha! Still watching, just got to the comment about the pipe slice being worn out. Could have put a new system in waiting for it to cut!
    Putting the screw in your mouth: Fitting a loo for an old couple, floorboards soaked in piss. Drilled pilot holes for pan screws and switched drill bit for screw driver bit, put the drill bit in my mouth and thought, hmmmm that's salty! 30 Years ago, never forgotten it.

  • @weetamix7168
    @weetamix7168 Před 4 lety

    Bit of paste would of done the same job as the PTFE

    • @SkillBuilder
      @SkillBuilder  Před 4 lety

      some people like paste but I think it ends up in filters and the like.

  • @Tubekeny1
    @Tubekeny1 Před 5 lety

    Why not plan how you are going to lengthen the pipe before you cut it?