HVAC TROUBLESHOOTING LG MULTI V 5

Sdílet
Vložit
  • čas přidán 7. 09. 2024
  • LG MULTI V 5 NO AC SERVICE CALL
    HVAC TROUBLESHOOTING ON
    LG Multi V 5 error code 116 oil level sensor error, actual error code 116 1 (C2) master compressor 2 oil level sensor error. After replacing the sensor system ran fine.
    #d2dnyac
    #heatingventilationandairconditioning

Komentáře • 54

  • @andyjones7836
    @andyjones7836 Před 3 lety +3

    Thanks for uploading!
    Very interesting, I assume if you could swap the dodgy oil module over to C1 compressor - the fault would shift to 116 1 C1.
    That is a pain though unwrapping the tape to get to it, especially with one hand✋.
    It's amazing how many youtubers only have one hand🖐️ - what are the odds 😂😂😂😂
    Keep up the good work 👍👍

    • @D2DNYAC
      @D2DNYAC  Před 3 lety

      Thanks for stopping by

  • @jameshandshy
    @jameshandshy Před 2 lety +4

    You should be able to pull the leads off the oil sensor and short them together and watch LGMV service tool to see if the oil indicator goes green. If it does and you put it back on and it goes off again then it's a good indication you are low on oil. If tho when you short them out and the green light doesn't go green then it's a faulty oil level sense and cable. Order it for inv2 so the plug colors are the correct ones. Then as alway watch it and make sure it does go green if not you'll need to run oil recovery mode and follow other comments abovevas you might have another issue with valves

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      @James Handshy very nice 👍 sounds good I will definitely be testing this out ! Thank you 🙏and thanks for stopping by

  • @davidbrown7423
    @davidbrown7423 Před 3 lety +2

    Usually oil return is a fault of the indoor units needing to be reset. Sometimes the outdoor unit will lose an indoor units address or HR boxes could have failed eev. It's hard to troubleshoot without using their service checker LGMV

  • @Syedpir
    @Syedpir Před 3 lety +1

    Hello brother good job.

  • @MarkCarpenterHVAC559
    @MarkCarpenterHVAC559 Před 7 měsíci +1

    Thank you sir

    • @D2DNYAC
      @D2DNYAC  Před 7 měsíci

      Thank you for stopping by

  • @alikhalid76dxb
    @alikhalid76dxb Před 3 lety +2

    Pls post next vdo also what was actual problem thanks

    • @D2DNYAC
      @D2DNYAC  Před 3 lety +5

      I replaced that oil sensor board/ module and the system ran error did not return and client haven’t called back since!

  • @NC-it6im
    @NC-it6im Před rokem +1

    Thanks for the info!

  • @Zavrian12
    @Zavrian12 Před 9 měsíci

    LG Indonesia hadir

    • @D2DNYAC
      @D2DNYAC  Před 9 měsíci

      Thanks for watching

  • @percyfranco8360
    @percyfranco8360 Před rokem

    Very interesting troubleshoot..good job...
    you know ,how to fix error code same unit LG multi V.5 ..error code 1042?

  • @robertmedina9267
    @robertmedina9267 Před 3 lety +1

    Hello sir, I am having trouble on slave and master multi v.5 vrf, both accu are not running but no error is being displayed. I have also tried LGMV but all parameters are normal. Hope you can help. Thank you!

    • @D2DNYAC
      @D2DNYAC  Před 3 lety

      Does the compressors starts or runs?

  • @killslveslowly
    @killslveslowly Před 2 lety

    Hello, I have a Multi Vs system and I I have 2 thermostats one works fine connected to one ducted unit and the other is daisy chained between 3 units, I keep getting error 53-1, when the system starts to blows cool but then stops on the 3 units. Help if you can

  • @dimaslespier2688
    @dimaslespier2688 Před 3 lety

    Curious 🧐 is there a vale to oil level from the compressor thermistor? Some way of checking to see if you are getting the proper value from within the compressor? Just sayin

    • @D2DNYAC
      @D2DNYAC  Před 3 lety +1

      Good question! perhaps 🤔 I will check for that the next time I have the service checker/tool hocked up to the system and add a comment regarding.

  • @nikopineira6001
    @nikopineira6001 Před rokem

    Thanks

  • @yaqoobk2
    @yaqoobk2 Před rokem +1

    Sir vrv multi v s some time ch05 some time run any solution pls

    • @D2DNYAC
      @D2DNYAC  Před rokem

      Can someone with knowledge of LGMV systems help please?

  • @ganeshmotiram2847
    @ganeshmotiram2847 Před 2 lety

    Lol it’s funny I did that job at 65 bleecker at core yoga at the last company I worked

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      @Ganesh Motiram what are you talking about friend?

  • @marksimpson4122
    @marksimpson4122 Před rokem

    So I’m on a Multi V with 2 HRUs and have a 200-1 Fault. Can u post step by step APD Auto pipe detection instructions plz. Something is lost in the Korean to English translation on the HRU panel

    • @D2DNYAC
      @D2DNYAC  Před rokem

      I will see what I can do

  • @HungNguyen-kd6kb
    @HungNguyen-kd6kb Před 11 měsíci

    Máy nén tuyến tính công nghệ của LG nay ứng dụng trên VRF luôn rồi.

  • @vusalmmmdov4204
    @vusalmmmdov4204 Před 2 lety

    we have error code C2 1 CH-116 in our Multi V5 air conditioner. Do we need to remove and re-install the oil sensor or measure its voltage to fix this problem?

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      After replacing the sensors on the jobsite I went the error never came back

  • @yousoufabbas3577
    @yousoufabbas3577 Před 3 lety +1

    Hello what does the code 571 vrf LG multi4 mean?

    • @D2DNYAC
      @D2DNYAC  Před 3 lety

      I believe that's a lost of communication between indoor and outdoor units

  • @MerajAhmad-ni8re
    @MerajAhmad-ni8re Před rokem

    I need job I have good experience of lg from Bahrain

  • @merajahmad8976
    @merajahmad8976 Před rokem

    I am from middle east I need job pls help me I have 9 year experience in vrf system daikin vrv lg Toshiba like that

    • @D2DNYAC
      @D2DNYAC  Před rokem

      I am in the USA my friend

  • @jamessaeger8113
    @jamessaeger8113 Před 2 lety

    Does anyone realize that they put the sensors on for a reason. Just because you get an error doesn't mean the sensor is bad. Just sayin

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      @james Saeger I agree ☝️my friend however sensors do go bad and if you are the one providing service for the equipment and you know it’s history then it’s easier for you to make the decision to replace sensor or chase it’s diagnostics

  • @MerajAhmad-ni8re
    @MerajAhmad-ni8re Před rokem

    Only vrf exp in daikin lg Hitachi Samsung

  • @cdefreit1
    @cdefreit1 Před 2 lety

    If any indoor unit or HR/Branch selector box loses power, can the entire system shut itself down? Has anyone ever experienced that?

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      On this site 1 indoor unit had no power and the rest of system stayed online

    • @mwdub02
      @mwdub02 Před 2 lety

      System would still run even if you lose one or two indoor units, unlike daikin crap

    • @AtalaTheGreat
      @AtalaTheGreat Před 2 lety

      @@mwdub02 Does the system bypass the faulty addressible unit then? (the faulty fan coil or branch box with no power in this case)

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      @chris Def still runs

    • @mwdub02
      @mwdub02 Před 2 lety

      @@AtalaTheGreat yes it’ll pass it.

  • @yousoufabbas3577
    @yousoufabbas3577 Před 3 lety +1

    Hello what does the code 241 vrf LG multi4 mean?

    • @D2DNYAC
      @D2DNYAC  Před 3 lety

      I will check and get back to you