HVAC TROUBLESHOOTING LG MULTI V 5
Vložit
- čas přidán 7. 09. 2024
- LG MULTI V 5 NO AC SERVICE CALL
HVAC TROUBLESHOOTING ON
LG Multi V 5 error code 116 oil level sensor error, actual error code 116 1 (C2) master compressor 2 oil level sensor error. After replacing the sensor system ran fine.
#d2dnyac
#heatingventilationandairconditioning
Thanks for uploading!
Very interesting, I assume if you could swap the dodgy oil module over to C1 compressor - the fault would shift to 116 1 C1.
That is a pain though unwrapping the tape to get to it, especially with one hand✋.
It's amazing how many youtubers only have one hand🖐️ - what are the odds 😂😂😂😂
Keep up the good work 👍👍
Thanks for stopping by
You should be able to pull the leads off the oil sensor and short them together and watch LGMV service tool to see if the oil indicator goes green. If it does and you put it back on and it goes off again then it's a good indication you are low on oil. If tho when you short them out and the green light doesn't go green then it's a faulty oil level sense and cable. Order it for inv2 so the plug colors are the correct ones. Then as alway watch it and make sure it does go green if not you'll need to run oil recovery mode and follow other comments abovevas you might have another issue with valves
@James Handshy very nice 👍 sounds good I will definitely be testing this out ! Thank you 🙏and thanks for stopping by
Usually oil return is a fault of the indoor units needing to be reset. Sometimes the outdoor unit will lose an indoor units address or HR boxes could have failed eev. It's hard to troubleshoot without using their service checker LGMV
👍
Hello brother good job.
Thank you sir
Thank you for stopping by
Pls post next vdo also what was actual problem thanks
I replaced that oil sensor board/ module and the system ran error did not return and client haven’t called back since!
Thanks for the info!
Thanks for watching
LG Indonesia hadir
Thanks for watching
Very interesting troubleshoot..good job...
you know ,how to fix error code same unit LG multi V.5 ..error code 1042?
Do you have double condensers?
Twined ODU?
Hello sir, I am having trouble on slave and master multi v.5 vrf, both accu are not running but no error is being displayed. I have also tried LGMV but all parameters are normal. Hope you can help. Thank you!
Does the compressors starts or runs?
Hello, I have a Multi Vs system and I I have 2 thermostats one works fine connected to one ducted unit and the other is daisy chained between 3 units, I keep getting error 53-1, when the system starts to blows cool but then stops on the 3 units. Help if you can
Curious 🧐 is there a vale to oil level from the compressor thermistor? Some way of checking to see if you are getting the proper value from within the compressor? Just sayin
Good question! perhaps 🤔 I will check for that the next time I have the service checker/tool hocked up to the system and add a comment regarding.
Thanks
Thanks for watching
Sir vrv multi v s some time ch05 some time run any solution pls
Can someone with knowledge of LGMV systems help please?
Lol it’s funny I did that job at 65 bleecker at core yoga at the last company I worked
@Ganesh Motiram what are you talking about friend?
So I’m on a Multi V with 2 HRUs and have a 200-1 Fault. Can u post step by step APD Auto pipe detection instructions plz. Something is lost in the Korean to English translation on the HRU panel
I will see what I can do
Máy nén tuyến tính công nghệ của LG nay ứng dụng trên VRF luôn rồi.
Nice
we have error code C2 1 CH-116 in our Multi V5 air conditioner. Do we need to remove and re-install the oil sensor or measure its voltage to fix this problem?
After replacing the sensors on the jobsite I went the error never came back
Hello what does the code 571 vrf LG multi4 mean?
I believe that's a lost of communication between indoor and outdoor units
I need job I have good experience of lg from Bahrain
USA 😂 my friend
I am from middle east I need job pls help me I have 9 year experience in vrf system daikin vrv lg Toshiba like that
I am in the USA my friend
Does anyone realize that they put the sensors on for a reason. Just because you get an error doesn't mean the sensor is bad. Just sayin
@james Saeger I agree ☝️my friend however sensors do go bad and if you are the one providing service for the equipment and you know it’s history then it’s easier for you to make the decision to replace sensor or chase it’s diagnostics
Only vrf exp in daikin lg Hitachi Samsung
Nice
U did not reply me about the job
If any indoor unit or HR/Branch selector box loses power, can the entire system shut itself down? Has anyone ever experienced that?
On this site 1 indoor unit had no power and the rest of system stayed online
System would still run even if you lose one or two indoor units, unlike daikin crap
@@mwdub02 Does the system bypass the faulty addressible unit then? (the faulty fan coil or branch box with no power in this case)
@chris Def still runs
@@AtalaTheGreat yes it’ll pass it.
Hello what does the code 241 vrf LG multi4 mean?
I will check and get back to you