VLT® Drives: The drive is displaying an Alarm 14 or Alarm 45 Earth Fault

Sdílet
Vložit
  • čas přidán 28. 08. 2024

Komentáře • 53

  • @மண்புழு87

    Watching your video helps to improve my skills life.thank you very much sir

    • @Hi-CHOICE
      @Hi-CHOICE Před rokem

      எப்படி சரி செய்வது alarm 14 m

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před rokem

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @maxesamusements5202
    @maxesamusements5202 Před 2 lety +1

    Thank you very much for your help

  • @sudharathna
    @sudharathna Před rokem +1

    What’s the sensitivity or min earth leakage current for the vfd to cause earth fault alarm or trip

  • @stalinsubbiah3238
    @stalinsubbiah3238 Před 3 lety +2

    Sir: Put Video to install Dansfoss AC Drive, Parameter Settings and Troubleshoot it

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      Thank you for the suggestion, I have shared it with our training department.

  • @automesinmechatronic5206
    @automesinmechatronic5206 Před 10 měsíci +1

    Warning 66 low temperatur please solution?

  • @user-kz3re5ym7h
    @user-kz3re5ym7h Před 5 měsíci

    At 5:16, you spoke about high voltage frequency pulses that can find pass to ground through the smallest pinholes of insulation. How can we confirm this is the case? Will a Megger test or insulation resistance test be able to detect such minor pinhole leaks?

  • @WaseemAlhazm
    @WaseemAlhazm Před 2 měsíci

    FC102N showing the earth's fault,
    .
    During removing the cable it does not show the earth fault when we are connecting the motor cable it starts showing the earth fault.
    We checked the cable and motor and found it normal.
    Then what is the actual reason and what is the solution.

  • @jhonnybellohidalgo4417

    in the fc101 models they do not have common current sensors, apparently the measurement is taken through the dc bus, because in my case I have an fc101 and the alarm 16 short circuit persists, having already measured the igbt module correctly

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před rokem

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @Julhas1850
    @Julhas1850 Před 3 lety +1

    Please sir explain me:What is the causes of ground fault or earth fault(Alarm-:14)without load?this is a danfoss vlt 2800 and vlt 5000 series inverter....i am from bd supplier...

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      For additional information please visit www.danfossdrives.com. Or if you need immediate assistance contact Danfoss Drives:
      Phone: +1 888-DANFOSS (1-888-326-3677)
      or
      E-mail:
      Customer Service: Drives.CS.NA@danfoss.com
      Technical Support: Drives.TS.NA@danfoss.com
      After Sales Service: Drives.TS.Service.NA@danfoss.com

  • @suhailjamadar7267
    @suhailjamadar7267 Před 2 lety

    AL-048
    Gate drive voltage fault
    What's the solution for this alarm. Please help me out

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před rokem

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @tariqpervez8385
    @tariqpervez8385 Před rokem

    Dear Sir ,could you guide me regarding danfoss FC202 .Alarm earth fault 13 (A14),Sir how can resolve this fault .hope you will help me ,waiting your prompt response .

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před rokem

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @gajananr.maneshirol2710

    Sir on disply shows some frequency when start...But motor not start....what possibility ?

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 2 lety

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @jeffcuyos8454
    @jeffcuyos8454 Před 3 lety

    How about gate drive voltage fault
    It means. The supply of power card is out of range. Can you tell me how fix it fast?

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      For additional information please visit www.danfossdrives.com.
      * If you need immediate assistance contact Danfoss Drives: Phone: +1 888-DANFOSS (1-888-326-3677) or by E-mail:
      Customer Service: Drives.CS.NA@danfoss.com
      Technical Support: Drives.TS.NA@danfoss.com
      After Sales Service: Drives.TS.Service.NA@danfoss.com

    • @habeebolayinka6922
      @habeebolayinka6922 Před 2 lety

      Qe2s

  • @raoulboumi4043
    @raoulboumi4043 Před 2 lety

    I have an alarm on my danfoss vlt internal MCO error[A199]
    Please how can i solve it

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před rokem

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @thailottery1986
    @thailottery1986 Před rokem

    I have vlt microdrive this one running without motor when connected the motor shows alaram 16 pls send solution

    • @shashikumar3113
      @shashikumar3113 Před rokem

      Replaced IGBT module ......

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před rokem

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @ducnghiabk2007
    @ducnghiabk2007 Před 2 lety

    Dear Sir. We have one drive fc 302 earth fault 2 when it starting. We have checked earth connection motor cable ok. But we can not reset this fault? ( Please help or bypass this fault?)

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 2 lety

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

    • @shashikumar3113
      @shashikumar3113 Před rokem

      Replaced motor out put CTs

  • @RajeshKumar-uh7mr
    @RajeshKumar-uh7mr Před rokem

    Hello sir vlt 2900 Run command after Err 14

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před rokem

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @Julhas1850
    @Julhas1850 Před 3 lety

    Please sir tell me.there is any component problem in the inverter,showing error -earth or ground fault...how to check in the in inverter there is any component...please sir,i need a help...i am from bangladesh

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      For additional information please visit www.danfossdrives.com
      * If you need immediate assistance contact Danfoss Drives: Phone: +1 888-DANFOSS (1-888-326-3677)
      or
      E-mail:
      Customer Service: Drives.CS.NA@danfoss.com
      Technical Support: Drives.TS.NA@danfoss.com
      After Sales Service: Drives.TS.Service.NA@danfoss.com

    • @user-pb3hi2ho3o
      @user-pb3hi2ho3o Před 10 měsíci

      ​@@DanfossdrivesNA
      0:54

  • @ShriHariPrabhuBhakt
    @ShriHariPrabhuBhakt Před 2 lety

    Sir vfd not run in AUTO mode
    And alarm
    show U 12
    Please Urgently for me

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 2 lety

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @hvacandvrvspecialvedoindus7891

    Sar my denforse alarm continue bilinking and warning light aup 🙏

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 2 lety

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)

  • @savewater53
    @savewater53 Před 3 lety

    Sir showing boot during turn on and it not gone...

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      For tech support information please visit www.danfoss.com/en-us/service-and-support/fix-and-troubleshooting/drives-support/

  • @rameshpawar1412
    @rameshpawar1412 Před 3 lety

    AL 13 please solution

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      For additional information please visit www.danfossdrives.com
      * If you need immediate assistance contact Danfoss Drives: Phone: +1 888-DANFOSS (1-888-326-3677)
      or
      E-mail:
      Customer Service: Drives.CS.NA@danfoss.com
      Technical Support: Drives.TS.NA@danfoss.com
      After Sales Service: Drives.TS.Service.NA@danfoss.com

  • @willykristanto9957
    @willykristanto9957 Před 3 lety

    Please help, vlt5000, alarm 15

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      For additional information please visit www.danfossdrives.com
      * If you need immediate assistance contact Danfoss Drives: Phone: +1 888-DANFOSS (1-888-326-3677)
      or
      E-mail:
      Customer Service: Drives.CS.NA@danfoss.com
      Technical Support: Drives.TS.NA@danfoss.com
      After Sales Service: Drives.TS.Service.NA@danfoss.com

  • @carlosbonilla3497
    @carlosbonilla3497 Před 3 lety

    fault internal 2068 (a38)

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 3 lety

      For additional information please visit www.danfossdrives.com
      * If you need immediate assistance contact Danfoss Drives: Phone: +1 888-DANFOSS (1-888-326-3677)
      or
      E-mail:
      Customer Service: Drives.CS.NA@danfoss.com
      Technical Support: Drives.TS.NA@danfoss.com
      After Sales Service: Drives.TS.Service.NA@danfoss.com

  • @hvacandvrvspecialvedoindus7891

    Helap

    • @DanfossdrivesNA
      @DanfossdrivesNA  Před 2 lety

      For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
      or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)