Power system lightning impact

Sdílet
Vložit
  • čas přidán 28. 07. 2024
  • To use the background simulator yourself go to www.ecsp.ch. Turorial about the impact of a lightning strike on a power system and the required protection strategy. Watch more videos: / @georgschett801
  • Věda a technologie

Komentáře • 33

  • @nickbaker1716
    @nickbaker1716 Před 4 lety +3

    Awesome video! clearly explained with direct simulation results. well done!

  • @riccardomaggioli9578
    @riccardomaggioli9578 Před rokem

    Very informative. Thank you very much.

  • @bhaskararaoguruvelli3641

    Nice video sir.Clearly explained

    • @georgschett801
      @georgschett801  Před 4 lety

      Thanks for your kind feedback. Share it with your contacts for increased visibility.

  • @phamquyen0201
    @phamquyen0201 Před 2 lety

    sir, did u make any video regarding to Generator, excitation system,

  • @scottvidler1023
    @scottvidler1023 Před 3 lety

    Hi Georg and thankyou for this. As a system operator we were always aware of the affects of the lightning strike (CB's trip and reclose) but not necessarily the physics behind it. So if lightning is conducted from the shield wire to ground there isn't a phase OV so no trip? When the phase insulator flashes over and the wave front hits the SA at the station and it then conducts the current to ground would the protection scheme still detect the phase OV and trip the line? Does the impedance of the SA increase as it heats up to limit the current to ground? Thanks. BTW I was at Lucerne for my honeymoon in 1987. Beautiful place.

    • @georgschett801
      @georgschett801  Před 3 lety

      Thanks for your kind feedback. If the lightning hits the shield wire without subsequent backflash across the line insulation at the tower, there is no short circuit and thus no trip. The trip happens because of the short circuit and not because of the overvoltage. The lightning overvoltage is too short for tripping an overvoltage protection relay. The current impulse at the SA is also very short and thus I guess there will be no major heat up. The resistance of the SA may vary a little in function of temperature but the major impact on the resistance comes for the current amplitude through the SA and its none-linear characteristics. Nice to hear that you enjoyed Lucerne, definitely a beautiful place.

  • @extremelycreativeusername

    How does lightning affect power in high rise buildings? Here in Singapore, our power grid is entirely underground but lightning still causes power trips in apartments. It quite common during heavy thunderstorms and a trip even fried my bloody laptop once

    • @georgschett801
      @georgschett801  Před 2 lety

      There can be many reasons. If lightning hits a building for example, very high currents flow along the building grounding system which can induce overvoltages in the building power supply system. These overvoltages can well initiate a spark leading to a short circuit which will be cleared by a fuse. Thus the local blackout.

  • @chctham
    @chctham Před 2 lety

    Hi Georg, may I ask if you can explain what it means by limit coupling between lightning protection and power system earth mat to 100V when a discharge of 100KA from lightning strike? Will you program able to study this? Thank you

    • @georgschett801
      @georgschett801  Před 2 lety

      I do not get your question. What position in the video are your referring to?

    • @chctham
      @chctham Před 2 lety

      @@georgschett801 hi, i am asking a general question. Lightning and earthing system isolated from esch other, when lightning strike, how can i check the conductive coupling voltage between two independent system? Can you system simulate? Tks

    • @georgschett801
      @georgschett801  Před 2 lety

      To some extent. A very precise simulation requires many details. However most of the time this is not really needed. The program enables you to model the impact of a lightning strike close to a substation to a great level of details and there is plenty of literature which can support you accordingly.

  • @andrewng602
    @andrewng602 Před 4 lety

    Can the shield wire handle the lightning current if it is directly hit by a lightning strike?

    • @georgschett801
      @georgschett801  Před 4 lety

      Hi Andrew, yes, that is what it is built for. The shield wire conducts the current to the next tower where it is grounded.

    • @andrewng602
      @andrewng602 Před 4 lety

      @@georgschett801 I see, it looked thin compared to the live conductors. Thanks ;)

  • @spikes1529
    @spikes1529 Před 4 lety

    Anyway to down load these files i cant find them?

    • @georgschett801
      @georgschett801  Před 4 lety

      to your first question: the line starts if you put the mouse cursor on the connector, then the red circle should appear. Then click left and then the line should appear. Then you can double click to end it or you click once to re-direct or you click on another connector to stop it.
      The second question: the files are available if you click on the images at the bottom. You may have to wait a few seconds until it loads.

  • @imeprezime1285
    @imeprezime1285 Před rokem

    What about wood pole power lines? Wood is relatively good insulator.

    • @georgschett801
      @georgschett801  Před rokem

      I am not sure if this changes much because lightning can strike a tower but between towers as well. And the shielding wire must be grounded at the pols and thus even wooden poles would be conducting.

    • @imeprezime1285
      @imeprezime1285 Před rokem

      @@georgschett801 The shielding wire is not installed on 20 kV power lines. In my country there are still some 10 kV and 20 kV power lines with wood poles

  • @sarahebal4391
    @sarahebal4391 Před rokem

    Thank you very much for the video, it is great, sir how we can avoid congestion in power systems (in the distribution level)?

    • @georgschett801
      @georgschett801  Před rokem

      Hello. I am not sure I get your question right. Normally cables and lines are protected for example by overcurrent relays. During the planning phase you have to make sure that the maximum loads possible are not exceeding the distribution system ratings. There are special software packages which enable a proper system design based on local standards.

    • @sarahebal4391
      @sarahebal4391 Před rokem

      @@georgschett801 Thank you sir for your response, but how we can avoid it in case we have a peer-to-peer energy trading system?

    • @georgschett801
      @georgschett801  Před rokem

      @@sarahebal4391 Maybe this article is of interest for you:www2.deloitte.com/nl/nl/pages/energy-resources-industrials/articles/peer-to-peer-energy-trading.html
      You have a very valid question and this is a key topic for power systems. I guess it is addressed quite well in the linked article.

  • @johnrockstone089
    @johnrockstone089 Před 4 lety

    Sir , please make a vedio in Hindi language , bc i could not get this in English

    • @georgschett801
      @georgschett801  Před 4 lety

      Sorry, I do not speak Hindi language, but you may know somebody who could translate it for you.

    • @johnrockstone089
      @johnrockstone089 Před 4 lety

      @@georgschett801 Sir , are you a teacher at any University

    • @georgschett801
      @georgschett801  Před 4 lety

      @@johnrockstone089 Just part time, in Switzerland by Lucerne

  • @imacprousersam7306
    @imacprousersam7306 Před 2 lety

    In India they will just trip off the entire grid when there is lighting they don't want to take any risk

    • @georgschett801
      @georgschett801  Před 2 lety

      This cannot be the case for the entire grid, it would take hours to re-synchronize all the generation. It might however be correct for some small remote segments of the rural distribution grid where the protection may not be adequate yet. I have spent lots of time in India discussing protection with local utility experts and I have never heard this.