How to do Goose for ABB relay in PCM600 | ABB Goose system | Goose on PCM 600

Sdílet
Vložit
  • čas přidán 28. 08. 2024
  • Goose between ABB and Other relay
    • How to do Goose betwee...
    how to make goose between Siemens relay
    • how to make goose betw...
    How to do Goose for ABB relay in PCM600 ?
    Goose is done for over Current protection block.
    Condition :
    when bus Tie is in close position during that time if over current protection occurs that should not trip incomer suddenly wait for bus tie to trip if its fail to trip then only incomer has to trip for that
    I have Two high stage protection one PHHPTOC1 and PHHPTOC2 both have same current setting but time is till high for PHHPTOC2.
    for Norma fault PHHPTOC1 will operate on Incomer but if Bus tie is connected with incomer during that time incomer detected fault current and bus tie also detected fault current then the fault occur's on other bus not due to his own bus. so incomer over current protection PHHPTOC1 should block but if Bus tie fail to trip then PHHPTOC2 will operated which will have little high timing then PHHPTOC1
    This blocking is taken from Bus tie over current and give for Block to Incomer over current.
    Goose:
    Goose between REF620

Komentáře • 42

  • @MohanRaj-hz9jj
    @MohanRaj-hz9jj Před 5 lety +4

    Before I never seen ABB goosing..but today I learn how to do that...keep uploading guys

  • @priyankshekhar2454
    @priyankshekhar2454 Před 4 lety +3

    Very nicely compiled and good videos in channel too. Thanks for sharing knowledge..

  • @m3mys3lf85
    @m3mys3lf85 Před 4 měsíci +1

    Hi, thank you so much, for the upload. It help me a lot.

  • @pokemon13333
    @pokemon13333 Před 3 lety +2

    Thank you so much for this video.

  • @azmidasman2465
    @azmidasman2465 Před 3 lety +2

    thank you so much

  • @nandoperu100
    @nandoperu100 Před 2 lety +1

    Hi nice Video , colud you shared this project...Thanks FG

    • @baranitech1026
      @baranitech1026  Před 2 lety +1

      thank you . this project i have to check in harddrisk if i get i will share

  • @bharatlalmali8695
    @bharatlalmali8695 Před rokem +1

    Very nice and informative...may you prepare same video with two IED only one is sending and other is receiving IED so that it may be understand more easily?
    You are also requested to prepare a video to explain important logical nodes, their class and attributes.

    • @baranitech1026
      @baranitech1026  Před rokem +1

      Yes, sure

    • @bharatlalmali8695
      @bharatlalmali8695 Před rokem

      @@baranitech1026 sir I configured a GOOSE message to operate Master trip of REF from RED Tripping but it was not worked and it may be due to serial communication between both relays. So want to ask that can i use front port for LAN communication? There is no LAN rear port available in REF615.

  • @clintonthangaraj4250
    @clintonthangaraj4250 Před 4 lety +1

    You covered in all videos how the GOOSE message is send from ABB,Micom,Siemens relays and GOOSE message is received to ABB, Siemens but GOOSE receiving in Micom relay is not available in any other videos. If possible teach us how to receive GOOSE message in Micom relays.

  • @haiderzafar6200
    @haiderzafar6200 Před 4 lety +1

    Kindly make a video on creating the scd file for the entire project in pcm600 that can be exported for scada

  • @haiderzafar6200
    @haiderzafar6200 Před 4 lety +1

    Is IET600 not needed at any step for abb goose? Can we do goosing in pcm600 itself like shown here

  • @NOVASOLITUDE
    @NOVASOLITUDE Před 3 lety +1

    "GOOSERCV_BIN" 2nd output "valid" signal signal must be connected via "And gate" logic. for better communication and trouble shooting purpose.

  • @adnanjayousi9140
    @adnanjayousi9140 Před rokem

    Thanks sir, can you please tell where we can find the GOOSE data description for logical nodes ?

    • @baranitech1026
      @baranitech1026  Před rokem +1

      for full details of goose data description can be find in manual , Thank you

  • @captainmercy87
    @captainmercy87 Před 3 lety +1

    Can you also do sampled value subscription configuration?

    • @baranitech1026
      @baranitech1026  Před 3 lety

      What sample value bro

    • @captainmercy87
      @captainmercy87 Před 3 lety

      @@baranitech1026 some ABB relays have the capability to publish IEC61850 Sampled Values and subscribe to it. IEDs such as REF615. So I was wondering if you could do a video showing how to configure sampled value subscription configuration on something like REF615.

  • @cbsuresh5631
    @cbsuresh5631 Před 3 lety +1

    B/c fault..should not blck.. Incomers?
    Reason pl..

    • @baranitech1026
      @baranitech1026  Před 3 lety

      fault on b/c first b/c has to trip if its not tripping then incomer has to trip for that fault. ( so in incomer i use two o/c setting one with low time set and other with high time set - only this low time set was blocked)

  • @haiderzafar6200
    @haiderzafar6200 Před 4 lety +1

    I have a question regarding pcm600
    How do we add logic for scada command
    And if the breaker , disconnector command is given through hmi button does one has to build logic for it or is it internal
    If it's internal.. Does it check the conditions for close enable (CBXCBR1) automatically before executing the command
    Any clarity regarding this would be helpful

    • @baranitech1026
      @baranitech1026  Před 4 lety +2

      it has internal and CBXCBR1 block will check internal for close enable

    • @haiderzafar6200
      @haiderzafar6200 Před 4 lety +1

      @@baranitech1026 thank you so much..... Can you point me towards where I can configure for scada command

    • @baranitech1026
      @baranitech1026  Před 4 lety +1

      @@haiderzafar6200 in CTRL you have to take CBCSWI1.Pos.ctlOperOff
      point on data sheet.

  • @souvikdasgupta6363
    @souvikdasgupta6363 Před 3 lety +1

    PCM showing low memory, can u help me solve it.

    • @baranitech1026
      @baranitech1026  Před 3 lety

      Just restart your laptop. This is due to graphic issues

  • @chanchanchandru705
    @chanchanchandru705 Před 5 lety

    Nanba tamil version kedaikuma