HVAC - Cooling coil + Calculations ❄️❄️❄️

Sdílet
Vložit
  • čas přidán 20. 08. 2024

Komentáře • 68

  • @EngineeringMindset
    @EngineeringMindset  Před 7 lety +8

    ⚠️ *Found this video super useful?* Buy Paul a coffee to say thanks: ☕
    PayPal: www.paypal.me/TheEngineerinMindset

    • @masterchef6694
      @masterchef6694 Před 7 lety

      The Engineering Mindset I would like to buy you a coffee....but in my country pay Pal is not available

  • @EngineeringMindset
    @EngineeringMindset  Před 5 lety

    Learn *COOLING LOAD CALCULATIONS* here: czcams.com/video/0gv2tJf7nwo/video.html

  • @robertingersoll5289
    @robertingersoll5289 Před 3 měsíci

    Good lesson. Small correction - the condensate water term should be negative.
    energy in = energy out
    h ent air = Q coil + Q condensate + h lvg air
    Q coil = Delta air h - Q condensate

  • @kingkongtiger
    @kingkongtiger Před 7 lety +6

    Thanks for the great video. Please make more videos on HVAC system designs with calculation in different buildings. (May be start with something like single zone design with cooling load & fresh air requirement etc)

  • @00ABBITT00
    @00ABBITT00 Před 11 měsíci

    A better teacher than the $3200 class my union provides.

  • @tiagoferreira6713
    @tiagoferreira6713 Před 7 lety

    Hi! Thank you for your great job! You really understand a lot of things about hvac systems and their components! Please don't stop and continue the great job!
    Just gonna suggest some themes that I find interesting to understand better so you can maybe had to your list, if you find them interesting:
    - the various psychometrics evolutions of the air passing through the coils and other components (water cooling and heating coil, dx heating and heating coil, just an electrical resistance, humidification and dehumidification, and maybe others)
    - how a boiler works and main components (domestic ones (traditional and condensation ones) and industrial ones as you show in one of the videos)
    - how other type of cooling towers works
    - the tabs systems (thermo active building systems)
    Thank you once again and sorry for possible bad english
    Best regards

  • @congthinh3979
    @congthinh3979 Před 7 lety +1

    you teached me, HVAC and English. thank you!

  • @imiuli1304
    @imiuli1304 Před rokem

  • @JayMehta60
    @JayMehta60 Před 7 lety +3

    Hi, thanks for the video!
    How do you select a coil to be used in order to achieve a desired cooling capacity? In other words I would like to understand how must I design the coil geometry to achieve certain cooling capacity, with the water inlet & outlet temps. known, air entering temp known etc.

    • @EngineeringMindset
      @EngineeringMindset  Před 7 lety

      Coil geometry and design gets very complex. It takes hours of calculations, you should google the formula Q=U*A*DT as a starting point

  • @basilhamdy542
    @basilhamdy542 Před 5 lety +1

    Please can you tell us what is the next step after calculate the cooling coil capacity , how to select the correct coil for your application

  • @ramamanikantadondapati1043

    Sir you are saying the relative humidity is 100 persent. But human comfort is 50-55 percent. And also please make an video about relative humidity, specific humidity, dewpoint.

  • @mohammadalshaikhhasan5091

    Perfect and useful.
    I wish new videos about cooling coil water pressure drop and air pressure drop.
    but for the latent heat cooling load calculation, you assumed hw = hf ( heat of vaporization vs heat of saturated liquid)..why?

  • @trisafesales9392
    @trisafesales9392 Před 7 lety +5

    Hi Paul, superb illustrations and explanations..Just one small doubt Do we have to get RH of 100% for air coming out from the cooling coil in order to achieve the desired cooling effect...

    • @Hum4292
      @Hum4292 Před 2 lety

      I was also thinking of the same matter. Unless we use to humidify the cool air after evaporator coil, the RH will not rise to 100% RH.

    • @jeffreyfontenot8803
      @jeffreyfontenot8803 Před rokem

      Yes, you want it to "rain" on the coil, wringing all that water out of the air. That way when you warm 55 F 100% RH air up to 75 F it is at 50% RH.

  • @wojtek_sanitarnik
    @wojtek_sanitarnik Před 6 lety +1

    Do you have video about BF & CF fsctors of cooling coil. That would be interesting video. Thanks!

  • @bhushanpawar8855
    @bhushanpawar8855 Před 5 lety +1

    Sir water inlet temp.to.the cooling coil in ahu is same as chiller set point temperature for calculating kw of cooling coil

  • @amitstorm500
    @amitstorm500 Před 3 lety

    can you give calculations steps for immersed helical coil in a stationary water tank carrying hot air?

  • @babaksp4235
    @babaksp4235 Před 7 lety +1

    Beautiful, excellent

  • @ismailmasoodshaikh7757

    Thanks for this very useful information, can you please let me know the water side pressure drop of cooling coil and the refrigerant required in DX coils for 1 TR of cooling

  • @kuleyedi
    @kuleyedi Před 4 lety

    Could you also explain heating coil capacity? As far as ı know , at heating capacity we should not add humidity counts to Q and Other hand When we cool room , sometımes ıt concludes excessive humidity problems, how we get rıd of it technically. Thanks for efforts🙏🏻

  • @nse08
    @nse08 Před 2 lety +1

    Hi, I believe that your formula for Q should not include mw*hw, because this latent heat is included in ma*(h2-h1), am I wrong?

  • @jeffreyfontenot8803
    @jeffreyfontenot8803 Před rokem

    What about coil efficiency? Are we assuming 100% efficient heat transfer? What is a typical cooling coil efficiency?

  • @jasonanderson7343
    @jasonanderson7343 Před 7 lety +1

    Great stuff. Hope to see more about HVAC calculations in the coming videos. Well done

  • @kylevencer7709
    @kylevencer7709 Před 5 lety +1

    hello. how to get the cooling water mass flow rate?

  • @NadeemKhan-lh6vv
    @NadeemKhan-lh6vv Před rokem

    How did you find water out temp 15c

  • @mohammadalshaikhhasan5091

    Thanks for the great video.. so helpful
    In case we have AHU designed and the evaporator coil sized to specific capacity, can we increase the airflow to achieve higher capacity?
    A chiller designed to specific capacity and connected to AHU to achieve a certain indoor temperature and air change rate, whats could happen if the AHU coil changed to another one smaller with the same high air flow?
    The face velocity will be higher?
    The effects on sensible capacity?
    The effects on latent capacity?
    Thanks again

  • @user-fl5ri3oi9m
    @user-fl5ri3oi9m Před rokem

    hi..i have a question in different subject if you can help
    in evaporative cooling...is it useful to decrease the temp of water spry or water washer
    ex: if out air 36c,60%rh..on psy with 90% evaporative efficiency.h ll get a 28c db and 90%rh..
    so if i enter a 7c cold water to the washer .will i get a cold air temp....with knowing that in 100%humidity the db is about 27c
    thanks

  • @keithwo1
    @keithwo1 Před 2 lety

    good day kind question for this group, i just want to know if there is a formula for cooling capacity which fcu is converted from dx to chilled water or how many percent does of cooling load will be lost if converted?, thank you who ever answers,

  • @engineersingulf6968
    @engineersingulf6968 Před 6 lety

    here you subtract latent heat why? in the equation above it is adding

  • @jayhaantharumugam6703
    @jayhaantharumugam6703 Před 6 lety

    How to calculate the Airout Temperature? How did you arive at 15 Deg C. Please provide calcs?

  • @rezanoormohammadi6914
    @rezanoormohammadi6914 Před 3 lety

    How can we calculate cooling water mass flow?

  • @ravikumarginne1125
    @ravikumarginne1125 Před 4 lety

    i want to calculate my cooling coil capacity for adding condensing unit more.

  • @zeegohar8352
    @zeegohar8352 Před 2 lety

    Does the relative humidity affect the enthalpy?
    According to the air properties i find 99 kJ/kg for h1. But paul uses 78 kJ/kg. What is the reason for this?

  • @malikshehryar7145
    @malikshehryar7145 Před 6 lety +1

    Pual my question is when three way valve is activated then in this situation how much water enters into the cooling coil ? Or water completely bypass the cooling coil and goes back in to return line.

    • @EngineeringMindset
      @EngineeringMindset  Před 6 lety +1

      depends on the system, you can check the valve manufacturers documents to see the correlation between position and flow rate

  • @alimarzooq5051
    @alimarzooq5051 Před 5 lety

    Thanks for this helpful video. I have a question about the air pressure drop, how to calculate it? If you can provide me with some sources it will be better

  • @chriscoop9
    @chriscoop9 Před 4 lety +1

    0.9m3/kg entering? not 0.887m3/kg? confused....

  • @Aznd007
    @Aznd007 Před 7 lety +1

    Our Indoor design will be 23*C , RH - below 60 % .
    in this case the air which coming out from coil air having almost 100% RH !!! Here how will you control this RH Level??

    • @EngineeringMindset
      @EngineeringMindset  Před 7 lety +1

      It's just an example. You can sub cool it and then reheat but a more efficient way is to use a Desiccant
      Dehumidification unit.

    • @Aznd007
      @Aznd007 Před 7 lety

      The Engineering Mindset Thanks for your advice!

    • @moneeshs8127
      @moneeshs8127 Před 6 lety

      The air off the coil will be 100% rh , on entering the room i.e air off the grill it will mix with the room condition to make 60%rh i.e 13dec will mix with room condition so it will make 23dec c..since the dbt increase simultaneously the rh tends to reduce

    • @moneeshs8127
      @moneeshs8127 Před 6 lety

      The Engineering Mindset for maintaining 50-60 rh any ancillary is not required for comfort application

  • @ZeeshanKhan-fg7ry
    @ZeeshanKhan-fg7ry Před 5 lety

    Can u tell me about coil in ahu..
    Meaning of 4/6 row coil..
    When we'd day this ahu is 4 row or any row???

  • @butchruelos4070
    @butchruelos4070 Před 5 lety

    The specific humidity unit in the condensate water mass flow rate calculation is wrong. It should be in kg/kg.

  • @mathewsvarghese6146
    @mathewsvarghese6146 Před 7 lety +1

    Can you please upload the duct installation videos based on shop drawings

  • @partha636
    @partha636 Před 6 lety

    In the cooling load calculation , Q_dot should be negative i.e. -78.5 KW. Why have you taken it positive?

    • @EngineeringMindset
      @EngineeringMindset  Před 6 lety

      partha sarathi Das over time engineers find short cuts and this is one of them, in the real world no one asks for a negative 75kW heat exchanger. You're right it is a negative value though.

  • @mohammedowais4793
    @mohammedowais4793 Před 7 lety +1

    Hii sir....... Waiting for new videos

  • @jfasjfas
    @jfasjfas Před 7 lety +1

    esp calculation pls

  • @dantheman9909
    @dantheman9909 Před 6 lety +2

    How come you have 100% RH when the air has been conditioned through the cooling coil? Keep up the good videos 👍

    • @LM_25_11
      @LM_25_11 Před 3 lety

      At lower temperatures vapour gets saturated even at lower partial pressure. So for a vapour it's easy to attain high relative humidity ,since relative humidity is the ratio of partial pressure of vapour and partial pressure of vapour at saturation.

  • @lukeallison6618
    @lukeallison6618 Před 6 lety

    Dont you need the Dt to be able to ascertain the 4.67kg/s? How would you have this info without knowing the delta to begin with?

  • @ibrahimosman3393
    @ibrahimosman3393 Před 7 lety +1

    Never stop

  • @Mateoshful
    @Mateoshful Před 6 lety

    Hello The engineering mindset. I would like to study more about HVAC system. And planning to study abroad. Is there any recommendation which is good university or course? Hope you will reply asap Thank you

    • @EngineeringMindset
      @EngineeringMindset  Před 6 lety

      Depends where you would like to study. Try courses approved by CIBSE and ASHRAE, which cover building services.

  • @levierdragon
    @levierdragon Před 7 lety +3

    You sound Aussie. I assume you're a mech engineer working in HVAC. How's the HVAC job market? I'm planning on heading back to uni to study engineering.

    • @EngineeringMindset
      @EngineeringMindset  Před 7 lety +5

      Hey Roy, I'm not Aussie, but I have a mixed accent that often confuses people. I'm a dual mechanical and electrical engineer, working in building services consultancy. In my opinion HVAC is a great career path. You will likely be a mobile engineer and move around different sites meeting very interesting people, plus a lot of equipment is on the roof so you get great views over cities. It's also a job which will be less affected by the automation revolution, and it's in growing demand. No matter how the financial markets affect the world, there will always be the need for an engineer in a building.

  • @SubhamCreative.613kviews

    ok

  • @honestman276
    @honestman276 Před rokem

    We can make industries but the citizens, politicians and bureaucrats are utterly corrupted in Bangladesh. So I don't dare to make and to run the business on it. Thanks from Bangladesh.

  • @elliotmott1869
    @elliotmott1869 Před 6 lety

    what if you have a building with hundreds of FCU's in, there must be a quicker way then this