How to do earth electrode resistance test/ and reduce resistance to earth

Sdílet
Vložit
  • čas přidán 2. 11. 2022
  • This video is a demonstration of two important aspects of electrical earthing.
    1. How to test for earth electrode resistance to earth with an earth tester.
    2. how to improve(reduce) the earth electrode resistance to earth.
    • BEST WAY TO DO INSULAT...
    • Why TT systems Must be...
    • GROUNDING
    • How to perform Insulat...
    • How to troubleshoot an...
    • Types of earthing syst...
    • How to do insulation r...
    • How to check for open ...
    • How to Use a Multimete...
    • HOW TO USE MULTIMETER ...
    • How to measure electri...
    • How to check a faulty ...
    • How to troubleshoot an...
    czcams.com/users/shorts1hR89aDRVx
    • How to Repair Industri...
    • BEST WAY TO DO INSULAT...
    • How to interlock two c...
    • How to differentiate b...
    • #1 Contactors explaine...
    • How to check a faulty ...
    • How to do earth electr...
    please, if you find this useful, kindly comment, like, share and SUBSCRIBE .
    / @obloni_electrical

Komentáře • 81

  • @kingdommaxwell2603
    @kingdommaxwell2603 Před rokem +2

    I love your explanation, very easy and straightforward

  • @danielteyehuago1633
    @danielteyehuago1633 Před 7 měsíci +1

    I'm here again. Thanks for sharing it with us

  • @jimkimbrell4878
    @jimkimbrell4878 Před 4 měsíci +1

    Thank you, great video

  • @igwemoses6301
    @igwemoses6301 Před rokem +1

    Nice one, very educative.

  • @njchris1048
    @njchris1048 Před 6 měsíci +1

    Good job

  • @30mAkills
    @30mAkills Před 11 měsíci +3

    Very useful demo. My humble suggestion:
    For multiple rods the minimum spacing distance should be twice or more that of the depth, to overcome zone of influence effect. Eg: if the depth of one rod is 1.5m then the parallel rod should be placed 3m away.
    Then current spike should be placed at a minimum distance of 8 to 10 times the depth. Suppose rod is 1.5 meter depth then current spike distance to be at least 15m away in order to avoid influence. For array the diagonal is taken as depth for calculations. These are thumb rules we follow here in India for Fall of potential method. Thanks.

  • @yahayamasanja1849
    @yahayamasanja1849 Před 11 měsíci +1

    Good work my dear

  • @30mAkills
    @30mAkills Před 11 měsíci +1

    Good you choose 500V, which will also save thermistor if present. Here in India line to line is 415V and theoretically we have to inject 1000V. But to be on safer side we use only 500V practically.

  • @eugeneugochukwu2173
    @eugeneugochukwu2173 Před rokem +1

    Thanks. Very elaborate tutorial.

  • @Ibrahimsaheed-bn2ph
    @Ibrahimsaheed-bn2ph Před rokem +1

    Nice Tutorial I love your explanations keep it up sir

  • @Enkayjay0
    @Enkayjay0 Před 3 měsíci +2

    Thank you, sir. Please can multimeter be used for the testing?

  • @nandamgk
    @nandamgk Před 11 měsíci +1

    nice video click. thank you

  • @munyemanaferdinand1112
    @munyemanaferdinand1112 Před 9 měsíci +1

    Thank you so much for your session,it is clear and helpful. BTW would you like to tell me how to measure the resistance once the installation is complete? bref ,should I have to disconnect the cable from the building or I have to test while the cable is connected.thank you

    • @obloni_Electrical
      @obloni_Electrical  Před 9 měsíci

      Yeah, ideally the cable should be disconnected before the test.

  • @danielteyehuago1633
    @danielteyehuago1633 Před 7 měsíci

    Please what should be the distance from the main rod to the second rod.

  • @HopeGamor
    @HopeGamor Před 5 dny

    What is name of the chemical used to treat the soil around the electrol

  • @danielteyehuago1633
    @danielteyehuago1633 Před 7 měsíci

    Please what value are we expecting in the testing.
    What chemical is use to treat the soil and how is it done

  • @essienjackson1081
    @essienjackson1081 Před 8 měsíci +2

    Thank you for your video class .but I was once told that earth resistance test should be less than 0.5oh down is a good homic value.

    • @obloni_Electrical
      @obloni_Electrical  Před 8 měsíci

      Sure, if you get 0.5Ohm that's great. In this type of test, the lower the resistance value, the beter

  • @emmanuelflomo8823
    @emmanuelflomo8823 Před 11 měsíci

    How much for an electrode resistance tester in your country? I also had an interest as well.

  • @user-qk4oj6wk9i
    @user-qk4oj6wk9i Před 10 měsíci +1

    Gostei

  • @yusufhaliluzakari
    @yusufhaliluzakari Před rokem +2

    Good job again. Please:
    1. What is the standard measurement for the resistance or threshold (I can see that yours is above 6ohms but less than 7ohms [6.4ohms])?
    2. What is size for the cable that would be used in connecting the earth rod to the house?
    3. How do you determine the length of the rod to use, i.e., is there a way of determining how long the rod (which is buried in the ground/soil) should be beforehand?

    • @obloni_Electrical
      @obloni_Electrical  Před rokem

      Well. There is an acceptable range but it differs from one jurisdiction to another. You have to refer to the electrical code of your country.
      Meanwhile, the lower the resistance to earth the better. You can even get as low as below 1ohm depending on the area and the type of soil
      Please contact me through WhatsApp. +2339323669

    • @obloni_Electrical
      @obloni_Electrical  Před rokem

      Refer to the electrical code of your country.
      Meanwhile, in most cases it should be of the same size as the supply cables

    • @obloni_Electrical
      @obloni_Electrical  Před rokem

      It depends on the water table of the area.

    • @yahayamasanja1849
      @yahayamasanja1849 Před 11 měsíci

      @@obloni_Electrical Exlent my dear which country you Available

    • @30mAkills
      @30mAkills Před 11 měsíci +1

      @@yahayamasanja1849 Earthing system design is based on results obtained from Wenner's 4 pole soil testing method.
      But as thumb rule we in India use 32 dia (nominal bore) GI pipe buried to a depth of 2.5 meter. This holds good for normal soil. The final result/value should be 5 or below.
      During summer pit has to be wetted by pouring water. This reduces the resistance. Here the earthing system is TT. We use RCCB for leakage fault.
      Mcb/fuse takes care of shorts and overloads. Hope this helps.

  • @dumobriggs7933
    @dumobriggs7933 Před 11 měsíci

    What is the required minimum reading

  • @miezankacou3455
    @miezankacou3455 Před 27 dny

    Good morning
    Please I want to know for the third rod are you extending the cable from the main rod or the second rod to the rod?
    Thanks

  • @ahiagbleseth9500
    @ahiagbleseth9500 Před rokem

    Thank you sir for the lesson, my question is not related to this topic though. The question is, what could cause light bulb to still give light when you put the switch off? In this case, the illumination becomes low, compared to when the switch is on? What could be the problem pls?

    • @obloni_Electrical
      @obloni_Electrical  Před rokem +5

      Alright Seth, so there are two things:
      1. Most of the time it has to do with the quality of the LED light. Poor quality LED lights behave like that.
      2. Problem with the electrical circuit.
      *Make sure the neutral is NOT used as the switch wire
      **That could also happen as a result of small pick-up of electricity from a cable running along the LED light cables due to electromagnetic induction (we say leakage in simple terms)
      Note:
      *If you are not sure of the quality of your LED light (s) , replacing them with quality ones could solve the problem.
      If you are very sure you are using high quality LED lights and the problem is still there, then check the circuit (wiring) as I indicated above.

  • @quadrieyitayo5580
    @quadrieyitayo5580 Před rokem +1

    I did installation of earth once. From my understanding, the earth system depends on the sizes of the building, e.g, factory or house, etc.
    For me, i would prefer to put all the 3 rods in a hole. Build a chamber and create a square shape one terminal lead outside for all 3 rods. That was what I did in my last earth installation.
    Sir, i love your output explanation. Reducing the resistance on earth it means the building is not that so BIG?.

  • @noxmayondi6135
    @noxmayondi6135 Před 6 měsíci +1

    This is wonderful my lecturer, can I still use multimeter to test earth resistance?

    • @obloni_Electrical
      @obloni_Electrical  Před 4 měsíci

      A multimeter can be used to perform certain types of earthing tests in a residential setting, but it's not ideal for measuring actual earth resistance.

    • @noxmayondi6135
      @noxmayondi6135 Před 4 měsíci +1

      This is helpful and education I'm going to encourage my fellow students to subscribe to this channel

    • @obloni_Electrical
      @obloni_Electrical  Před 4 měsíci

      @@noxmayondi6135
      Wow! That's great to hear. Thanks

  • @danielteyehuago1633
    @danielteyehuago1633 Před 7 měsíci

    Please always try to list your tools, brand and their model what you are using in the video at comment section so if we have wanna buy it, it can be easy for us

  • @ishekuenerobinson1218
    @ishekuenerobinson1218 Před 3 měsíci

    Good morning instructor, please what is the deght of earth rod.

    • @obloni_Electrical
      @obloni_Electrical  Před 3 měsíci

      please use this link czcams.com/video/Kp0a3jFHjiE/video.html for a detailed explanation to your question. thanks czcams.com/video/Kp0a3jFHjiE/video.html

  • @yahayamasanja1849
    @yahayamasanja1849 Před 11 měsíci +1

    And also exchoose I want to now when the reading 6.4 ohms is good or bad

    • @obloni_Electrical
      @obloni_Electrical  Před 11 měsíci

      The supply authority earthing system is TT but I am using an Rcd (main) so it's okay

  • @TonnieMureti-qs7hj
    @TonnieMureti-qs7hj Před měsícem +1

    What are the significance of performing earth test

    • @obloni_Electrical
      @obloni_Electrical  Před měsícem

      Yeah, you will get it clear from my videos on earthing. Use these links:
      czcams.com/video/wWO2Z-gm-HA/video.htmlsi=firyiskWsvbWbcNR
      czcams.com/video/Njr3LXOyEyI/video.htmlsi=BBPKT-113blb7xYD
      czcams.com/video/Kp0a3jFHjiE/video.htmlsi=t8s4ZJ81_vQ8SG_Y
      czcams.com/video/QQ4leh3wXso/video.htmlsi=otp0O0WoQQ7DkYqE

  • @mbabaalifrank2557
    @mbabaalifrank2557 Před 6 měsíci +1

    Which instrument did you use for the test

  • @joesephaniekwe2768
    @joesephaniekwe2768 Před rokem

    What if the resistance is not good enough, what are the symptoms? Does the current get low once put load?

    • @obloni_Electrical
      @obloni_Electrical  Před rokem

      In case there's a leakage in the circuit, you will pay more electricy Bill and a small leakage can also cause electrical shock etc.

  • @JerryMartins-vh9vc
    @JerryMartins-vh9vc Před 4 měsíci

    What is the normal ohms for earthing a residential home??

    • @obloni_Electrical
      @obloni_Electrical  Před 4 měsíci

      it depends on several factors and there isn't a single "one size fits all" answer.
      1. Local regulations: Different countries and regions have their own specific regulations governing minimum earth resistance values for electrical installations. These regulations often define the required range, sometimes referencing 5 ohms but not always.
      2. Soil conditions: The conductivity of the soil where the earth/grounding electrode is installed significantly impacts resistance. Dry, rocky soil offers higher resistance than moist, clay-rich soil.
      All these factors will affect what you will call "normal ohms for earthing a residential home??" in a particular location.
      here are some general guidelines:
      Many countries and regions set a maximum allowable resistance, often ranging from 5 ohms to 25 ohms for residential buildings. However, lower values are always preferred for enhanced safety.
      Find the relevant electrical code or standard applicable in your area to determine the required earthing resistance value that is acceptable in your country/region
      If you are in Ghana, you can contact me for assistance. WhatsApp +233242809918

    • @JerryMartins-vh9vc
      @JerryMartins-vh9vc Před 4 měsíci

      @@obloni_Electrical
      Im not in ghana
      I wish u have tutorials online not only on youtube.
      Where we can interact with on video

    • @obloni_Electrical
      @obloni_Electrical  Před 4 měsíci +1

      @@JerryMartins-vh9vc
      Good idea. So I will plan and schedule a time for that. Thanks 👍

  • @anthonyfindlay466
    @anthonyfindlay466 Před rokem +1

    Good stuff my brother, but you need a new tester.

  • @SAMUELAkakpoAmeble
    @SAMUELAkakpoAmeble Před 4 měsíci

    So that can reduce the speed of a meter

    • @obloni_Electrical
      @obloni_Electrical  Před 4 měsíci

      if there is a leakage in the wiring and the earthing is bad, your meter will read more. until there is a leakage in the wiring, earthing does not play a role in how your meter works

  • @jerryabai3581
    @jerryabai3581 Před 8 měsíci

    Can someone use multimeter for the test?

  • @engineermwaruwa.-mc3yy
    @engineermwaruwa.-mc3yy Před 2 měsíci

    How can i get that insulatio resistance tester sir

    • @obloni_Electrical
      @obloni_Electrical  Před 2 měsíci +1

      Please which country?

    • @engineermwaruwa.-mc3yy
      @engineermwaruwa.-mc3yy Před 2 měsíci +1

      Kenya

    • @engineermwaruwa.-mc3yy
      @engineermwaruwa.-mc3yy Před 2 měsíci

      Does it serve you better

    • @obloni_Electrical
      @obloni_Electrical  Před 2 měsíci

      @@engineermwaruwa.-mc3yy oh oh okay, you can get some at a local electrical shop. Though they are not common. You can also try shopping online.

    • @obloni_Electrical
      @obloni_Electrical  Před 2 měsíci

      @@engineermwaruwa.-mc3yy
      Sure, but there are equally better or even more better brands in terms of durability and robustness. Prices also vary from brand to brand.

  • @hidayatrahman2553
    @hidayatrahman2553 Před 6 měsíci +1

    Hi 👋 brother wher r u we want work with u

  • @Mastermind24256
    @Mastermind24256 Před 29 dny

    It's worth trying, but then I will not obtain positive results.

  • @dumobriggs7933
    @dumobriggs7933 Před 11 měsíci

    What is the required minimum reading

  • @dumobriggs7933
    @dumobriggs7933 Před 11 měsíci

    What is the required minimum reading

  • @dumobriggs7933
    @dumobriggs7933 Před 11 měsíci +1

    What is the required minimum reading

    • @obloni_Electrical
      @obloni_Electrical  Před 11 měsíci +2

      That depends highly on what the Electrical code of your local jurisdiction(or country) says. The IEE regulation says anything below 200 Ohms is okay. But Practically, you should be looking for a reading below 10 Ohms. with RCD protection (in a TT system).
      Note: the lower the better. if you can get 0.0 ...value that would be great.