HOW TO PREFORM EARTH RESISTANCE TEST

Sdílet
Vložit
  • čas přidán 4. 08. 2020
  • This tutorial show how to carry out earth resistance test for commercial and resident building . Proper setting is importance for getting the better and accurate test result .

Komentáře • 229

  • @fje1948
    @fje1948 Před 9 měsíci +2

    The video I was looking for! Excellent explanation of the test. Thank you so much!
    Ps: The background music is pleasant and appropriate!

  • @salumhongo3955
    @salumhongo3955 Před 10 měsíci

    You demonstrate this critical task to look easily, Thank you very much a learn a lot through your video.

  • @muhdyunus3894
    @muhdyunus3894 Před 3 lety

    Video paling sng difahami...tq sgt2

  • @MrSyahryzal
    @MrSyahryzal Před 2 lety

    Mudah untuk difahami... Lama mencari video earthing test untuk menambah ilmu. Terima kasih boss

  • @castertroycabillar2863

    Thanks for this very informative vedio. More power.

  • @kalamsa7445
    @kalamsa7445 Před rokem

    Without much noise around, explained in a simple practical way...Thanks Rictor

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @o-techtips3871
    @o-techtips3871 Před 2 lety +1

    Thank you very much for your sharing very informative tips☺️

  • @foonglikwei3913
    @foonglikwei3913 Před 2 lety

    This teaching very useful and very easy to understand. Thanks and appreciate it 😊

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @kirotomato7316
    @kirotomato7316 Před 3 lety

    easy to understand,thank you sir for wharing the information for us

  • @ohhappyday1548
    @ohhappyday1548 Před 2 lety

    thanks to your efforts, it is very helpful .. thank you..

  • @ofwj-ddah
    @ofwj-ddah Před 11 měsíci

    Thanls for sharingbthis video. It helps me a lots

  • @MrOner07
    @MrOner07 Před 2 lety

    very easy to follow... you earned a subscriber!❤️😊

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @yghiduppastimatikelak8854

    Good job ...thanks for sharing..

  • @manjunathamanju6204
    @manjunathamanju6204 Před 3 lety +2

    Thank you Sir this video very useful for all Electrical engineers

  • @PbaY.
    @PbaY. Před 3 lety

    mantap tutorial nya .👍👍🌟🌟🌟

  • @marchomeautorepairs
    @marchomeautorepairs Před 2 lety

    Keep up the good work

  • @sanjeevraghav3700
    @sanjeevraghav3700 Před rokem +2

    Very nice vedio 👌👌kudos to your effort 🙏🙏👌

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @CrisBoy410
    @CrisBoy410 Před 11 měsíci

    video excelente parabens , abraços do Brasil .

  • @electroboy3607
    @electroboy3607 Před 9 měsíci +1

    Good job..🎉 im practical test

  • @kanthasamymuthusamy739

    Simple explainations.Easy to underdstand

    • @30mAkills
      @30mAkills Před rokem +1

      Shifting potential spike towards right and left is wrong.

  • @fazrulchanneltv9157
    @fazrulchanneltv9157 Před 2 lety

    Tq Sir. Clear and easy to undrstand. This place is like "Bukit Bendera" 😅

  • @sanjeevraghav3700
    @sanjeevraghav3700 Před rokem

    Appreciate 👌👌you have done share gr8 experience with kyoritsu instrument 💐
    This is sanjeev raghav from kyoritsu

  • @joselitodupaya2092
    @joselitodupaya2092 Před 3 lety

    Thank you sir sa video

  • @william5624
    @william5624 Před 2 lety

    Very good👍🏻

  • @redbirdgaming7905
    @redbirdgaming7905 Před 3 lety

    Thank you very much sir Many Thanks

  • @vlogsidah89
    @vlogsidah89 Před 3 lety

    Mantap tuan,done support ya,maaf lewat.. 🙏🙏

  • @nathan37141
    @nathan37141 Před rokem

    Thank you Engineer

  • @akilagayan6533
    @akilagayan6533 Před rokem

    Good work 👍

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @ahmedbelazi2318
    @ahmedbelazi2318 Před rokem

    Thank you for the effort made in the video.... I have a question... Is it true that the yellow wire is supposed to be an extension of the red wire, meaning on one line to give the reading... Why change in yellow only and should it be changed in red? ??

  • @angelosrcayabyab6952
    @angelosrcayabyab6952 Před 2 lety

    thanks for sharing

  • @gabus1956
    @gabus1956 Před rokem

    Thank
    from Hungary

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @anthondiy
    @anthondiy Před rokem +1

    Thank you sir sa video another learning for earthing system

  • @sahayaxaviersahayaxavier3217

    Salute sir

  • @user-ic5re6so6e
    @user-ic5re6so6e Před 2 lety

    Thank you, sir

  • @jillferrer6135
    @jillferrer6135 Před 2 lety

    thank you sir..

  • @iranweranga225
    @iranweranga225 Před 11 měsíci

    Is there a specific number of times that earth resistance testing should be done for a specific area? (like number of times per meter squard)

  • @arturotakuma4742
    @arturotakuma4742 Před rokem

    excelent ¡¡¡

  • @muhdsolihin2641
    @muhdsolihin2641 Před rokem +10

    should be disconnecting earth cable from house to ground chamber first. so you will get the purest ground resistance.

    • @pankajmishra43
      @pankajmishra43 Před rokem

      Hiiii...
      You mean, first disconnect the earth cable from earth pit??
      OR
      Can we shutdown the entire system before measuring earth resistance??
      Pls guide

    • @Sim_Tiby
      @Sim_Tiby Před rokem

      Disconnect the earth cable.

    • @DiReal_Donclassy
      @DiReal_Donclassy Před rokem

      Of course he must have done that before starting the test otherwise the resistances of home equipment will distort the result

  • @pankajraina4832
    @pankajraina4832 Před rokem

    Good sir 👍

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @francisrayang805
    @francisrayang805 Před 2 lety +2

    Hi sir. You did a very informative video thanks. I've a question for you.In the video you did the test on a big compound. I'm in a terrace house and the compound is very limited. I can't pull the yellow and red cable that long..only 3-4 meters to the nearest soil. Will it affect the reading? Please advice thks.

    • @rictorrictor888
      @rictorrictor888  Před 2 lety

      In that situation ..You can try nearest area to ground the spike ..

    • @rictorrictor888
      @rictorrictor888  Před 2 lety

      in that situation ..yes..

    • @30mAkills
      @30mAkills Před rokem

      You have to maintain distance. Please read my other comments. Get permission from neighbours.

  • @svh6195
    @svh6195 Před 2 lety

    Thanx!!

  • @igorsmirnoff8578
    @igorsmirnoff8578 Před rokem

    Будьте любезны,выложите такое же видео с прибором KEW 4106,спасибо!!!

  • @bundaajhalah
    @bundaajhalah Před 3 lety +1

    Hadir nyimak 👍

  • @dakwahislamcn6390
    @dakwahislamcn6390 Před 3 lety

    Lanjutkan

  • @solomonnyaga7018
    @solomonnyaga7018 Před 8 měsíci

    Does it mean now the earth resistance is perfect?

  • @siralexivan2006
    @siralexivan2006 Před 3 lety

    well done

  • @yusufsupyan9940
    @yusufsupyan9940 Před 3 lety

    Luar biasa kawan Videonya.
    Sudah saya kirim Bungkusan komplit dan,paten, durasipun Aman. Sesuai undangan.
    Ditunggu Amanahnya ya..

  • @matsetizar65
    @matsetizar65 Před měsícem

    when lightning strikes the earth doesn't the surge enter the house via the earth wiring? If so isn't it dangerous, probably better not to have any earthing system at all?

  • @anthonykihanga2881
    @anthonykihanga2881 Před rokem

    Thanks alot

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike towards right and left is wrong.

  • @bornstar9897
    @bornstar9897 Před 2 lety

    thanks

  • @fauzibafana9089
    @fauzibafana9089 Před 2 lety +1

    Can i know whether before the individual earth rod being tested you have to remove the connection of the earth rod from the rest.

    • @gniraj8501
      @gniraj8501 Před rokem

      I am also have same question.

    • @30mAkills
      @30mAkills Před rokem

      Yes it should be disconnected from service. If the voltage is more than 10 it will destroy the meter and also give false reading. Please read the user manual reg the max voltage limit that the meter will work safely in energised service without disconnection.

  • @wazzer5293
    @wazzer5293 Před 6 měsíci +1

    Sir, how 1). If earth got voltage, what is the next action.. 2). When to use the setting mode 200 & 2000? Apprecite ur answer

  • @fidelcatsro6948
    @fidelcatsro6948 Před rokem

    if we had no access to such equipment will adding more grounding rods to the ground all connected together potentially reduce the earth resistance?

  • @surendrakverma555
    @surendrakverma555 Před rokem

    Good 🙏🙏🙏🙏🙏

    • @30mAkills
      @30mAkills Před rokem +1

      Shifting potential spike towards right and left is wrong.

  • @dumindathusuth2026
    @dumindathusuth2026 Před rokem

  • @loveandpeace594
    @loveandpeace594 Před rokem

    thanks :)

    • @30mAkills
      @30mAkills Před rokem

      Shifting potential spike in perpendicular ( left and right)direction is not correct.

  • @gohpoikheng6030
    @gohpoikheng6030 Před 2 lety +1

    May i know why the cable for current is longer than the voltage?

    • @raemondbradford1629
      @raemondbradford1629 Před rokem +1

      When current is injected into the earth, then the voltage will change around the location of injection. The voltage reference cable spike needs to be some distance from the points where current is injected or removed, in order to try and find a location with minimal disturbance of earth voltage potential.

  • @neilblenkinsop2613
    @neilblenkinsop2613 Před rokem +2

    To individually test the earth rod disconnect tape from earth rod

  • @RandomThoughts2020
    @RandomThoughts2020 Před rokem

    Conclusion of 1.62 ohms? Meaning of that value? Is there a range passing value? I'd like to know.

    • @sanjeevraghav3700
      @sanjeevraghav3700 Před rokem +2

      It means your earth grounding is perfect, anything less than 5ohm always consider perfect earthing as per indian standard 🙂

  • @niezam1729
    @niezam1729 Před 2 lety

    Jika persekitaran rumah tamn agak sukar nk ambil bacaan,sb permukaan tanah @ berturap simen Dan jalan tar.
    1- minutes 6.15 mase kita clamp wayar di electrod bumi.yg seeloknya copper tape @ cable incoming perlu ditanggalkan @ tidak semasa nak ambil bacaan.klu sye lihat Tuan x buka ..

    • @nasrulhelmeihalimppksistem7432
      @nasrulhelmeihalimppksistem7432 Před 2 lety +1

      kalau kawasan tar @ bersimen, boleh guna metal screen @ earthing mat. letak pada jarak yg ditetapkan & siram dgn air jd blh buat measurement

  • @DaBlackTradesMan
    @DaBlackTradesMan Před rokem

    I have to perform this same test but outside of the building is all concrete, a shower room will be built in the basement but first the neutral to earth voltage needs to be tested, so how would I go about this?

    • @frankkennedy7831
      @frankkennedy7831 Před rokem

      you silly person. what sort of system are you on?

    • @30mAkills
      @30mAkills Před rokem +1

      Check with normal clamp or multimeter in volts mode between earth and neutral of any 3 pin socket connected to that service. The voltage value should be below 2. Hope this helps.

    • @fje1948
      @fje1948 Před 9 měsíci

      @@frankkennedy7831
      Perhaps you are the silly person making such an inappropriate comment! 🤢

  • @prabhus4137
    @prabhus4137 Před 2 lety

    Hi sir I have a doubt. Could you please tell me the difference between 2 point, 3 point method. In megger it has 4 terminals C1, C2, P1, P2. how to measure earth pit resistance?

    • @30mAkills
      @30mAkills Před rokem

      Short C1 and P1 and connect to electrode under test. P2 is for potential and C2 is for current spike. This is known as 3 point or Fall of Potential method.
      4 terminals method is for testing soil as per Wenner method. This is for civil guys and not for electrical guys.
      Reg 2 point earth pit resistance testing: In India we don't/cant use this method because our public water supply is thru PVC pipes which is non conductor. Hope this helps.

  • @KGL101293
    @KGL101293 Před 2 lety

    Hi, I have a Kyoritsu 4105A unit too, and I am getting "1. . ." reading at 20 ohm dial, who do you think is the problem, and how to fix this? Thank you.

    • @deutroitcity
      @deutroitcity Před 2 lety

      It's over limit. U need to dial up the limit. Cannot use 20ohm. Because the reading is above 20 ohm

    • @nasiadomary4893
      @nasiadomary4893 Před rokem

      How about if the reading is 25ohms
      What can i do to get less than 5Ohms?

    • @30mAkills
      @30mAkills Před rokem +2

      @@nasiadomary4893 1. If possible increase the depth of electrode.
      2. Insert another electrode at a distance of at least twice the buried depth of 1st electrode and link both at top. Eg.: If 1 st electrode buried depth = 3 M then second electrode should be installed at a distance of minimum 6 M away and both should be linked with wire or strip at the top.
      3. Wet the pit by watering because dry earth is a bad conductor.
      Note : Chemical electrodes are fraud work. Hope all this helps.

    • @nasiadomary4893
      @nasiadomary4893 Před rokem +1

      @@30mAkills
      Thanks🙏🙏

  • @lonedragon4410
    @lonedragon4410 Před 2 lety +5

    Below 5ohm is acceptable right?

  • @azleeman
    @azleeman Před 3 lety

    Saya nak tanya, bukankah testing dibuat semasa pemasangan rod sahaja (sebelum kita sambungkan dengan earth DB atau sebelum sambung ke perlindungan kilat)

    • @rictorrictor888
      @rictorrictor888  Před 3 lety

      Kedua2 nya boleh ..sebelum dan selepas ..Sebenarnya Cooper tape itu bukan utk pelindung kilat..

  • @leomarbecilla2785
    @leomarbecilla2785 Před 2 lety

    hi sir. how do you perform it in a building where there is no earth ground to put the spike?

  • @japhethm6103
    @japhethm6103 Před 4 měsíci

    What readings should tell me that the resistance is not okay please

    • @rictorrictor888
      @rictorrictor888  Před 4 měsíci +2

      depend on local regulation ..as lower as possible. .below 10ohm

  • @castertroycabillar2863

    Sir what is the porpuse for higher ohms setting.is it same result as 20ohms setting.thanks

  • @muhammadaresyamilbinazman7935

    Tumpang tanya, kan ada 20ohm, 200ohm, dan 2000ohm. Yang tu nak laraskan berdasarkan faktor apa ye?

  • @yosuaabimo9379
    @yosuaabimo9379 Před 5 měsíci

    Test ini apakah harus saat listrik off?

  • @wtnyambizi9876
    @wtnyambizi9876 Před rokem

    What about the distance btn the spikes does it matter !?

    • @anthonykihanga2881
      @anthonykihanga2881 Před rokem

      5 meters up to 10 meters it depends on soil type

    • @30mAkills
      @30mAkills Před rokem +1

      Thumb rule for current spike distance from electrode = Minimum 8 to 10 times the buried depth of earth electrode. Eg., If earth electrode is 3 M long then C spike should placed about 24 to 30 M distance. This is to avoid '"zone of influence"' factor. Most manufacturers wont tell this because the distance will affect their tester sales in city and town areas where space is congested. So they suggest 5 M and 10 M which will not yield correct value. I challenge Kyoritsu in this matter.

    • @fje1948
      @fje1948 Před 9 měsíci

      @@30mAkills
      Thank you for this comment - can you please provide some formal references to confirm y you our comment - Thank you!

  • @stanleyozoilo1587
    @stanleyozoilo1587 Před rokem

    What is the accurate value for best low resistance using Megger machine

    • @rictorrictor888
      @rictorrictor888  Před rokem +1

      0 ohm

    • @30mAkills
      @30mAkills Před rokem

      @@rictorrictor888 Practically not possible. Is earth full of gold?

    • @fje1948
      @fje1948 Před 9 měsíci

      @@rictorrictor888
      I wish 😂

  • @AutodidactEngineer
    @AutodidactEngineer Před rokem +2

    The test should be done preferably during the driest season to prevent moisture from ruinning your values!

    • @File-Transfer
      @File-Transfer Před 2 měsíci

      I have a question, engr. Why is it required in the earth resistance tester manual to damp the surroundings?

    • @AutodidactEngineer
      @AutodidactEngineer Před 2 měsíci

      @@File-Transfer I don't know about that

  • @wilsonloo8576
    @wilsonloo8576 Před 3 lety

    Hi Rictor , may i know how to know the result is good or bad? Many Thanks

    • @rictorrictor888
      @rictorrictor888  Před 3 lety +4

      low in reading is the batter .must below 10ohm.some time we can get 0 ohm. that the best..

    • @octaviohurtado2779
      @octaviohurtado2779 Před 3 lety +2

      It depends on your country standards. But the Best is the nearest to 0 ohms which is imposible to get 0 ohms. Also there are many methods to make the measurraments, it depends on your country standards too.

  • @Bwelz2010
    @Bwelz2010 Před rokem

    Good, Thanks

  • @GUDANGLAMPUSURYA
    @GUDANGLAMPUSURYA Před 2 lety +1

    Om untuk mengetahui brp kedalaman grounding rod yg di tanam bagaimana ya ? 🙏

    • @GUDANGLAMPUSURYA
      @GUDANGLAMPUSURYA Před 2 lety

      Apakah bisa di test dgn ohm meter tersebut

    • @rictorrictor888
      @rictorrictor888  Před 2 lety

      Kedalam nya sehingga rod gak bisa masuk lagi..baru di uji..jika masih tidak mendapat kan bacaan yg dikehendaki..buat point baru sehingga mendapat bacaan yg paling rendah

  • @ericmunkanta2964
    @ericmunkanta2964 Před 2 měsíci

    Why is the leads in the same line

  • @Bestofthebest383
    @Bestofthebest383 Před měsícem

    I had an exams question in college how to do earth rod test . I didn’t pass it 😢

  • @aruquest25
    @aruquest25 Před 3 lety

    The green wire is for?

    • @rictorrictor888
      @rictorrictor888  Před 3 lety

      electrode wire..

    • @olegkotletov7857
      @olegkotletov7857 Před 3 lety +2

      green wire is for grass. grass is green. make sense right? put green wire on grass and see resistance of grass. grass is green, green wire is green too. make sense right? right.

  • @HENRYFANUELPHIRI
    @HENRYFANUELPHIRI Před 10 dny

    Why the leads are in same line? pliz assist me sir.

  • @yumon6515
    @yumon6515 Před 2 lety +1

    Sir, can I set the tester 200ohm? Should I take that result? Thank you 🙏

  • @junsmackalbos4565
    @junsmackalbos4565 Před rokem

    Sir the result you shown is that good or bad grounding

  • @islammaidul6999
    @islammaidul6999 Před 2 lety

    Overall resistance how is it calculation sir

    • @rictorrictor888
      @rictorrictor888  Před 2 lety

      Total of test 1 ,2 ,3 then / by 3..it show on video min 13.20

  • @kennedymutuku8950
    @kennedymutuku8950 Před rokem +1

    Hello Sir,what if the result is above 10,let say 50..how can you improve this to 5?

    • @AutodidactEngineer
      @AutodidactEngineer Před rokem

      Use a combination of vertical and horizontal grounding!
      My tip would be get copper/or in poorer countries galvanized pipe works well enaugh and install it in conjunction with galvanized steel bar/ or do the same but with copper if you can afford it!

    • @fidelcatsro6948
      @fidelcatsro6948 Před rokem +2

      add more earthing rods all around the place the more the better🐱👍🏿

    • @neilblenkinsop2613
      @neilblenkinsop2613 Před rokem +2

      All earth rod supplies these days are carbon steel with copper coating add to and go deeper using brass connection.

  • @ervingjonaj9082
    @ervingjonaj9082 Před 5 měsíci +3

    music is shocking

  • @bruce.bchannel9046
    @bruce.bchannel9046 Před 3 lety +1

    Macam mna kalo erathing buat ats tnh bacaan bukit tu tnh...

    • @rictorrictor888
      @rictorrictor888  Před 3 lety

      tetap kena dapat kan bacaan bawah 10 ohm juga...tapi ada kaedah2 untuk menurunkan bacaan jika di buat atas tanah berbukit..tq

    • @bruce.bchannel9046
      @bruce.bchannel9046 Před 3 lety +1

      Sa lbih 15ohm bgtu

    • @bruce.bchannel9046
      @bruce.bchannel9046 Před 3 lety

      Nnti whatapps kmi 0138724857 mhu tnya kaedah lain

    • @rictorrictor888
      @rictorrictor888  Před 3 lety

      @@bruce.bchannel9046 boleh tambah point lagi tu..atau guna wayer tembaga bogel gulung jadi kan coil...tanam terus dlm tanah.hujung nya sambung ke electrod yang sedia ada..

    • @bruce.bchannel9046
      @bruce.bchannel9046 Před 3 lety

      Mcm mna cara ti

  • @MNor-nb8sp
    @MNor-nb8sp Před 2 lety +1

    What we do if earth volt not zero

    • @rictorrictor888
      @rictorrictor888  Před 2 lety +1

      Find another location for grounding the rod..

    • @30mAkills
      @30mAkills Před rokem

      De-energize that service and procced if the voltage is more than 10.

  • @FabioHM71
    @FabioHM71 Před 2 lety +3

    the operator wears the helmet because there are suspended loads?

  • @thanhthoangngo2591
    @thanhthoangngo2591 Před 3 lety

    hi sir, if the screen will perform "1 . " , what's wrong?

    • @rictorrictor888
      @rictorrictor888  Před 3 lety +1

      show me photo..

    • @octaviohurtado2779
      @octaviohurtado2779 Před 3 lety +3

      The valor is over the Range selectionated in the istrument or the cables are not conected correctly to the Spikes You should to check again all the conections. If the problem continue changue the Spikes of place.

    • @thanhthoangngo2591
      @thanhthoangngo2591 Před 3 lety

      @@octaviohurtado2779 Thank you! I'll check carefully. Good day!

    • @thanhthoangngo2591
      @thanhthoangngo2591 Před 3 lety +1

      @@rictorrictor888 Sorry, I don't know how to share a photo via a youtube comment. Anyway, I'll check my device. Thank you for your guidance.

  • @lenslens7379
    @lenslens7379 Před 2 lety +1

    I think 1/RT = 1/R1 + 1/R2 + 1/R3

    • @SpecialVeloce
      @SpecialVeloce Před 8 měsíci +2

      Sorry your Appying the wrong formula, it's average, not resistances in paralel

  • @Mike-ry4ti
    @Mike-ry4ti Před rokem +1

    Your value of 1.63 ohms is a little high. Ideally less than 1 ohm is what you want...

  • @johnhayhurst5884
    @johnhayhurst5884 Před 3 lety +2

    Very Very different to how it's done in the UK, In the UK those reading wouldn't be satisfactory but the method is way different so I don't know. Interesting though

    • @azleeman
      @azleeman Před 3 lety

      Maybe the humidity in UK is different if we compare to Malaysia. The water in soil can effect the meter reading.

    • @nasrulhelmeihalimppksistem7432
      @nasrulhelmeihalimppksistem7432 Před 2 lety

      @@azleeman biasanya ada 2 jenis earth tester yg selalu diguna measure grounding resistance. yg dlm video ni guna kyoritsu & location potential spike tu ditengah2 antara ground rod & current spike. yg satu lg jenama megger tapi jarak potential spike tu 62% dari jarak antara earth rod & current spike. & potential spike tu kena ubah 10% ke depan % 10% ke belakang dari kedudukan asal & diambil average dr 3 reading td. mungkin kat uk guna jenama megger sbb tu dia ckp different dgn kt sini.

    • @30mAkills
      @30mAkills Před rokem

      All over the world FOP (Fall of Potential) method is same.

    • @johnhayhurst5884
      @johnhayhurst5884 Před rokem

      Incorrect@@30mAkills

    • @30mAkills
      @30mAkills Před rokem

      @@johnhayhurst5884 then tell the correct. Here our earthing is TT.

  • @johnvillellegunas186
    @johnvillellegunas186 Před rokem +1

    Hi sir. If floor is concrete, how to insert voltage and currrent spikes?

    • @fidelcatsro6948
      @fidelcatsro6948 Před rokem

      break concrete and place into the soil below?

    • @30mAkills
      @30mAkills Před rokem +1

      It need not be inserted. Wrap the spikes in wet towel and place them horizontally on the concrete floor with weights (stone) placed on the sack. Wet the whole area by watering.

    • @fje1948
      @fje1948 Před 9 měsíci

      @@fidelcatsro6948
      Jesus, what planet are you on…..

    • @fje1948
      @fje1948 Před 9 měsíci +1

      @@30mAkills
      Excellent explanation….

    • @fidelcatsro6948
      @fidelcatsro6948 Před 9 měsíci

      @@fje1948 planet Kittygystan 🐱 of the 23rd Constellation, why do you ask amigo?

  • @daspecialist1220
    @daspecialist1220 Před rokem

    Attack of the silent explanation vid strikes yet again

  • @ahmadwahab1641
    @ahmadwahab1641 Před 3 lety +1

    untuk apa select ke earth voltage?

    • @rictorrictor888
      @rictorrictor888  Před 3 lety +3

      kita uji dahulu jika terdapat voltage dalam tanah.. terutamanya di kawasan kediaman yang berdekatan dengan sub station

    • @fidelcatsro6948
      @fidelcatsro6948 Před rokem

      kalau ada voltage baguslah pasang diode boleh charge bateri kereta anda🐱👍🏿

  • @aruniimalka6123
    @aruniimalka6123 Před 2 lety +1

    what is this aim?

    • @rictorrictor888
      @rictorrictor888  Před 2 lety +2

      Protect human and electrical equipment from electric short

  • @thunderhype5972
    @thunderhype5972 Před 2 lety

    Sub

  • @user-vd6wb5ef8v
    @user-vd6wb5ef8v Před 6 měsíci

    Why to use this device with long cables and sticks while THEORETICALLY one can get more relevant results using any household electric appliance like, say, Incandescent light bulb, a mulimeter and the old good Ohm's Law? One terminal of the bulb is connected to live (hot), the other to earth and the current is measured. Divide voltage by current and subtruct the bulb's resistance and the result is the earth resistance. What is wrong in such approach?

    • @Godfa539
      @Godfa539 Před 5 měsíci +1

      The results would only be resistance on the load , not main earth resistance

    • @user-vd6wb5ef8v
      @user-vd6wb5ef8v Před 5 měsíci

      @@Godfa539 will you justify this statement please?

    • @hidennseek1483
      @hidennseek1483 Před 2 měsíci

      I get what you mean and yes you can get accurate measurement through ohms wall but use a proper load resistor that is large enough to limit the current so the damage you will cause on the ground rod is limited.

  • @rjaramilloc
    @rjaramilloc Před 11 měsíci

    Ese método no existe, tomaste medidas arbitrarias y sacaste un promedio... No tiene sentido.

  • @MasudRana-sr1vf
    @MasudRana-sr1vf Před 2 lety +1

    One time check can't ? Why 3 time check,

    • @rictorrictor888
      @rictorrictor888  Před 2 lety +1

      More accurate ..

    • @SpecialVeloce
      @SpecialVeloce Před 8 měsíci

      And if you need to get only one value, measure twice to rule out reading errors.