Protection Relay Setting Calculation for Transformer Feeder Relays

Sdílet
Vložit
  • čas přidán 20. 08. 2024

Komentáře • 28

  • @ASIFKHAN-ui7jp
    @ASIFKHAN-ui7jp Před 8 měsíci

    Excellent explanation. Thanks

  • @surendrakverma555
    @surendrakverma555 Před rokem +1

    Excellent lecture. Thanks 🙏🙏🙏🙏

  • @karthikeyan3140
    @karthikeyan3140 Před rokem

    Great explanation sir..

  • @ahmedelmasry7435
    @ahmedelmasry7435 Před 2 lety +1

    Thanks Engineer

  • @AAEL2010
    @AAEL2010 Před 10 měsíci

    Thank you ❤

  • @shihabahmedalkatrani3050

    Thanks 🙏

  • @TheSurgeArrester
    @TheSurgeArrester Před rokem

    Care should be taken when following the steps mentioned here especially when it is across transformer. There are points which are important are not considered in the setting calculation.

  • @ImranKhan-nu6xw
    @ImranKhan-nu6xw Před 2 lety +1

    Very nice appreciate you sir g

  • @9999afshin
    @9999afshin Před 6 měsíci

    Nice

  • @lilmamaw1204
    @lilmamaw1204 Před 2 lety

    thank you po sir

  • @cracklyoyster6625
    @cracklyoyster6625 Před 2 lety +2

    Why was 35430A used instead of 1288A as 11KV fault current in the computation of 11KVside pickup current?

    • @emmanuelmanteaw7931
      @emmanuelmanteaw7931 Před 2 lety +1

      I have same question.. why the 35430 is used instead of the 1288

    • @rodsilver19
      @rodsilver19 Před rokem +1

      Same question here

    • @sanjaykashikar940
      @sanjaykashikar940 Před rokem +1

      It is to be taken 1288A. As you can't divide LV current by HT ct ratio. Needs correction.

  • @PhilsChannel
    @PhilsChannel Před 2 lety +1

    I have seen your bus bracing rating, How do we select bus bracing? And when do we use 1sec against 3 secs?

    • @juliussalutan8006
      @juliussalutan8006  Před 2 lety

      When it is based on ANSI 37 standard, bus bracing will be based on momentary network. For HV & MV switchgears, the corresponding asymmetrical RMS and asymmetrical peak short circuit currents have to be considered. Whilst, for LV switchgears, it's symmetrical RMS and asymmetrical RMS are being considered. All these information have to be clearly specified in a dedicated table once we prepared a power system study report. In my previous experience, we normally indicate in the drawing the asymmetrical RMS rating of the bus (for MV/HV SWGR) only and symmetrical RMS rating of the bus (for LV SWGR). For HV/MV SWGRS, the standard values for assymetrical RMS raring are 25kA, 31.5kA & 40kA in 3 seconds. But my last project ( nuclear power plant project), we used 50kA 3 seconds (which is rarely used in other facilities). The assymetrical crest rating of the SWGR will be considered/verified by the manufacturer once they start production of the SWGRS. Meanwhile, for LV SWGRS, the standard values in the market for symmetrical RMS rating are 25kA, 31.5kA, 40kA, 50kA, 65kA in 1 second. 80kA or 100kA is seldom used. One of my projects, a GOSP ( gas oil separation plant) we used the latter ratings. The assymetrical RMS will also be considered based on the actual short circuit study (maximum) that has to be provided to the SWGR manufacturer as well.

    • @PhilsChannel
      @PhilsChannel Před 2 lety

      @@juliussalutan8006 Thank you for your response. But how they choose the 3sec for MV/HV and 1 sec for LV applications? why only 1 sec and 3 sec? Why not 2sec, 4sec or 5 sec at most?

    • @juliussalutan8006
      @juliussalutan8006  Před 2 lety +1

      @@PhilsChannel as we know energy is directly proportional to the square of the current multiply by time. So the 3-second rated time has a higher short circuit withstand capability against rated 1 second. MV/HV has been rated in 3 seconds to facilitate the coordination time interval (CTI) in which upstream protection device time delay becomes longer as it requires to coordinate downstream protective devices. We need to consider also the relay operation time, lock out relay operation time, circuit breaking interrupting time, etc.. Thus, upstream HV/MV switchgears are being designated with a higher rated time i e. 3-sec but it could be 1 second as well. From your question why not use 2s, 4s or 5s? Im not sure how it was agreed by the industry practitioners or by any standard ( i havent seen yet). Its has been an industry practice to use 1 second or 3 seconds for switchgears and 2 seconds for transformers.

    • @PhilsChannel
      @PhilsChannel Před 2 lety +1

      @@juliussalutan8006 Great response.
      Thank you for your sharing.

  • @bagusirawansaputra
    @bagusirawansaputra Před rokem

    Why for 51P, you are using 1.5 pu ? why you are not using 1.1 or 1.2 since if exceed the 1 pu, I think it transformer will slowly damage ? and For 50P, what it 2,5 pu ? It is consider through fault current refer to IEEE 242 and or it has consider transformer inrush instead of 2nd harmonic block ?

  • @gerryboypanot7344
    @gerryboypanot7344 Před 2 lety

    Thanks sir.........

  • @abdalhameedstohy9207
    @abdalhameedstohy9207 Před rokem

    Supply the equations

  • @allenchesteralcantara2580

    How to get po yung 4330A @ 0.4kV thank you

  • @Al-rk6gm
    @Al-rk6gm Před rokem

    reference book pls