Protection Relay Setting Calculation for MV Motor Feeder Relays

Sdílet
Vložit
  • čas přidán 7. 09. 2024

Komentáře • 13

  • @tuna6423
    @tuna6423 Před 8 měsíci +1

    Hi Julius,
    I am thinking that 24:15 Earth fault protection
    If it is set only 2 value i.e., threshold and definite time, it should be called as 50G not 51G
    Unless you select IDMT Characteristic e.g., NINV, VINV or EINV Normal/Very/Extremely Inverse respectively and set time multiplier this will be 51G

  • @shihabahmedalkatrani3050

    Thanks 🙏

  • @Mukhaizna
    @Mukhaizna Před rokem

    great video, thanks for sharing.
    might be a good idea to include the motor inertia, mechanical load details, run a simulation using Digsilent power factory , and see the performance of the protection setting under various operating scenarios.

  • @pinoymaster1067
    @pinoymaster1067 Před rokem

    nice video tutorial sir

  • @aliamoor1541
    @aliamoor1541 Před rokem +1

    Thanks a lot for this great video but how we set IDMT RELAY I mean 51relay second stage

    • @juliussalutan8006
      @juliussalutan8006  Před rokem

      IDMT relay second stage is not being envisage for MV motor feeder relay

  • @ImranKhan-nu6xw
    @ImranKhan-nu6xw Před 2 lety

    Thanks for sharing the valuable information
    Kindly prepare a vedio on radial feeder setting for distribution system of load 7000kva, full load current 400 amp ,bus voltage 11kv ,CT ratio 400/5 ,low settings,high setting i.e I>,I>>& I>>>

  • @rjleal
    @rjleal Před 2 lety

    Hello, great video. Where did you get the settings that you show here? For example, the 80% of the short circuit current? Is there any standard for this? Thank you

    • @juliussalutan8006
      @juliussalutan8006  Před rokem +1

      I think for the 80%, it is related to the setting of undervoltage relay. For industry practice, undervoltage relay setting is being set between 70 % to 80% of the nominal voltage

    • @yassineallouche9844
      @yassineallouche9844 Před měsícem

      And for Time of 70% WE Can let 3sec??​@@juliussalutan8006

  • @reyyanez6705
    @reyyanez6705 Před 2 lety

    Sir, yung SONDE temperature protection, Anong temperature element po gamit nun same lang po ba sa RTD Pt.?