Trane Air cooled chiller. How To use- adaptive controller. Lock a circuit out

Sdílet
Vložit
  • čas přidán 20. 08. 2024

Komentáře • 28

  • @mr_queue
    @mr_queue Před 25 dny +1

    New guy in the chiller side of things, you saved me on the spot. Thanks!

  • @muhammadjangir5198
    @muhammadjangir5198 Před 2 lety +1

    Very best explains

  • @pawelduc2230
    @pawelduc2230 Před rokem +1

    Thanks a lot, good job 👏

    • @Junkremoval-hvac
      @Junkremoval-hvac  Před rokem

      No problem I remember 10 years ago starting and having a Hard time remembering how to go through this. Really happy it helped. Subscribe if you can just got my license goi g solo now

  • @lammaking333
    @lammaking333 Před 2 lety +1

    Just picked up a school district with 5 of these. Trying to learn everything I can about the RTAC line and there’s a shortage of footage on CZcams

  • @mansourghadhban236
    @mansourghadhban236 Před 2 lety +1

    Good job

  • @ArshadAli-wf1nq
    @ArshadAli-wf1nq Před rokem +1

    Very.NICE

  • @chrisnorris1959
    @chrisnorris1959 Před 2 lety +1

    Thank you, Stephen!!

  • @waseemakramdaula8033
    @waseemakramdaula8033 Před 3 lety +1

    Very nice

  • @kundanchavan2482
    @kundanchavan2482 Před rokem

    Chiller train rtac 350 the problem was Compressor command coming A1 and Compressor started B2 why like this

  • @omkumarsubba3967
    @omkumarsubba3967 Před 2 lety +1

    My rtac trane chiller display sundunly going to dim can't see anything please help me how to bring back

    • @Junkremoval-hvac
      @Junkremoval-hvac  Před 2 lety +1

      In the bottom right right corner tap it there is a small black circle there to darken the screen.

  • @simongumes1896
    @simongumes1896 Před 2 lety +1

    Super

  • @loveramesh3499
    @loveramesh3499 Před rokem

    Trane air cooled chiller 2A 2B isn't coming online at the same time why please help other one is working normal

  • @jasonpham0223
    @jasonpham0223 Před rokem

    hello sir
    my chiller ch530 circuit 1 stopped after running for about 20mins. and it said External circuit lockout . how do i solve this? please help
    thank you

  • @crown139
    @crown139 Před 2 lety +1

    Hallo sir
    Tanks for you
    (IN Hibited by External source Waiting for bas communications)
    The is problem in chiller trane What is the probability of this problem???

    • @Junkremoval-hvac
      @Junkremoval-hvac  Před 2 lety

      That means it waiting for signal for you BAS “building Automation System” that’s what tells it to run or you can run it off local, that will run off temp not on off signal from BAS system.

    • @crown139
      @crown139 Před 2 lety

      Thanks
      What about solutions

    • @crown139
      @crown139 Před 2 lety

      the chiller is currently Inhibite from starting (and running ) but may be allowed to start if the Inhibiting or diagnostic condition is cleared

    • @crown139
      @crown139 Před 2 lety

      damper scanning steps

  • @cristiangaleon6817
    @cristiangaleon6817 Před 9 měsíci

    Hi can i ask what about low suction presure in trane unit.is it possible low suction transducer have problem.when i check in my manifold charge is good but when i check in navigator or monitor its only have 40psi .

    • @Junkremoval-hvac
      @Junkremoval-hvac  Před 9 měsíci

      Sounds bad to me, if there are 2 circuits then swap the sensors and see if the problem follows. Make sure to bind them in.

  • @omkumarsubba3967
    @omkumarsubba3967 Před 2 lety +1

    please sir i need your help we have trane chiller rtac 185 not cooling no alarm and all parts working but not cool proper and how fill oil which valve or line i will use

    • @Junkremoval-hvac
      @Junkremoval-hvac  Před 2 lety +1

      Use the suction line so oil goes back to the compressor on start up. If the chiller is running and making temp. Confirm leaving water temp. It’s it’s at set point then check if there is a shut automatic-valve at the air handler not open and not letting chilled water go across coil

    • @omkumarsubba3967
      @omkumarsubba3967 Před 2 lety

      Please help me one more my chiller cooling set locked how to open lock please sir

  • @ashpaktechnicalsupport

    Hallo Sir,
    TRANE RTAC 400 chiller goes sometimes in 24 hours on low oil flow when reset chiller, oil pressure is normal (ok) sometime less oil pressure or sometime running chiller more than 24 hours it's goes again low oil flow so what should I guess to solve this problem...

    • @stevent8691
      @stevent8691 Před rokem

      Had the same issue> Theres a check valve in the compressor that sometimes sticks. Theres a service note out on it.