Trane RTAC Pt. 2 - Filter Drier, Vacuum, Recharge

Sdílet
Vložit
  • čas přidán 19. 07. 2022
  • Finishing out this service call for what was originally a leak repair for this Trane 250 ton RTAC air cooled chiller.
  • Jak na to + styl

Komentáře • 32

  • @iurigonzaga9493
    @iurigonzaga9493 Před rokem +3

    Keep it up the good work ! It really helped me a lot with some old chillers we have around here. Cheers from Brazil.

  • @SoutheastHVAC
    @SoutheastHVAC Před rokem +4

    Your channels gonna blow up with chillers and stuff dude!

    • @dfwhvac
      @dfwhvac  Před rokem

      I have a lot of chiller calls on the job Board coming up , so I should have another video or two on them sometime this coming week. Thanks for watching

  • @jshelby78
    @jshelby78 Před rokem +1

    Great video! really informative! so cool to see chiller repair and maintenance! keep up the awesome content

  • @joshuaricks7730
    @joshuaricks7730 Před rokem +1

    Great Job brother.

  • @ramonmolina717
    @ramonmolina717 Před 8 měsíci +1

    Great Job!
    Thank you for the key info. As well by as sequence of the process.

    • @dfwhvac
      @dfwhvac  Před 4 měsíci

      Thanks for watching

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Před rokem +1

    🤘🤘🤘🤘🤘🤘. I remember the first time i messed with a filter core....wasn't ready for the spring when i took off the cover. Well i found out real quick. Lol

    • @dfwhvac
      @dfwhvac  Před 4 měsíci

      Sucks when you put the cap back on then remember you forgot the spring lol

  • @user-rj5wm9ye5n
    @user-rj5wm9ye5n Před 10 měsíci +1

    Im working on one today in mesquite

    • @dfwhvac
      @dfwhvac  Před 4 měsíci

      I’m located in Ft Worth. Greetings fellow Texan

  • @mansourghadhban236
    @mansourghadhban236 Před rokem +1

    Thnxs more Nd more

    • @dfwhvac
      @dfwhvac  Před rokem

      Will have another video posted tonight or tomorrow

  • @robshuey6881
    @robshuey6881 Před rokem

    Could you film the entire process of recovering and charging to Chillers?

  • @koolairbros7358
    @koolairbros7358 Před 8 měsíci

    Would you have to recover the charge to replace the oil heater located at the oil separator.

  • @robertmason4334
    @robertmason4334 Před 2 měsíci

    I’m struggling with an rtwd chiller been working very well but now it’s tripping on low refrigerant temperature. Possibly low on charge what do you think when you see those alRms

    • @dfwhvac
      @dfwhvac  Před 2 měsíci

      Could be a few different things but immediate thought would be low on charge. Check all connections including threaded connections for sensors and transducers , king valves , etc with soap bubbles . Many leaks common from those areas on all Trane chillers. Pull all panels and inspect coils for oil stains . It’s possible could be a metering device problem but not likely - usually you’d get a low suction super heat alarm. After checking with bubbles , pull the water strainer and verify if it’s clean or dirty . Final step to actually know for sure if it’s low charge would be recover the charge and weigh the charge and compare to data tag. If for example your charge weight is 120 lbs and you only recover 70 lbs this for sure would be your tell tale sign. Hope this helps

  • @shaikjuned712
    @shaikjuned712 Před rokem +1

    Brother you should show how to store gas and how to release gas before we removed filter drier and which way to best for gas charge in chiller pressure Guage or kg limit

    • @dfwhvac
      @dfwhvac  Před 10 měsíci

      Next time I run into that scope of work I will definitely make that video !

  • @lookItsJayden
    @lookItsJayden Před rokem +1

    I’ve had a filer drier like that fall apart in a rtwa090.

    • @dfwhvac
      @dfwhvac  Před rokem

      Yes I really don’t like the design , on top of that you have to get it OEM from trane and it’s ridiculously overpriced . I think the last one I got was close to $300 dollars .

    • @lookItsJayden
      @lookItsJayden Před rokem

      @@dfwhvac I used 2 sporlan cores and it fit perfect.

    • @dfwhvac
      @dfwhvac  Před rokem

      @@lookItsJayden on this particular model RTAC you have to use an OEM drier from trane , the standard size 48 drier core is too wide to fit inside the drier shell.
      Trust me I tried 😂

    • @lookItsJayden
      @lookItsJayden Před rokem

      @@dfwhvac win some loose some😂

  • @matthewclemons1574
    @matthewclemons1574 Před rokem +1

    Nice tools but I never want to see you use a insulated screw driver as prybar. Keep up the good work.

    • @dfwhvac
      @dfwhvac  Před rokem

      That’s fair a reply lol ! Thanks for stopping by

    • @matthewclemons1574
      @matthewclemons1574 Před rokem +1

      @@dfwhvac I know you know based on your which is why I said it. Lol 😂

  • @rsofficial1588
    @rsofficial1588 Před rokem +1

    Diacore filter

  • @bradgeary3467
    @bradgeary3467 Před rokem

    you can not add wile unit is running?

    • @dfwhvac
      @dfwhvac  Před 4 měsíci

      Yes you can , but when starting from a completing empty circuit if you know the total charge weight on the data sticker , I usually will just push in the entire charge and let her go