DFW HVAC
DFW HVAC
  • 14
  • 121 190
VETO PRO PAC TP6B HVACR LOADOUT
Quick overview on how I have my Veto Pro Pac TP6B set up for HVACR wireless digital refrigerant probes, as well as a quick overview on which brand I prefer in regards to the Testo vs Fieldpiece debate.
zhlédnutí: 2 782

Video

LOW OUTDOOR AMBIENT COOLING - FAN CYCLE SWITCH INSTALLATION & OPERATION
zhlédnutí 8KPřed rokem
Watch in 4K! :) In todays video, I show you the benefits and features of utilizing a low ambient head pressure control such in the form of a condenser motor fan cycle switch. This part can greatly benefit your customer that utilizes comfort cooling in low ambient conditions due to a high building heat load by controlling heat rejection at the condensing unit by allowing the system to build a pr...
Veto Pro Pac Tech Pac Blackout HVACR EDC
zhlédnutí 33KPřed rokem
Like, comment & Subscribe! Thanks for stopping by. links to some of the nifty tools I carry with me. Happy HVACing! www.amazon.com/MulWark-Diameter-Screwdriver-Assembling-Furniture/dp/B07RK93JLY/ref=sr_1_14_sspa?crid=3QM14NR19YCTB&keywords=mulwark+allen+key+set&qid=1680467980&s=hi&sprefix=mulwark+allen+key+set,tools,104&sr=1-14-spons&spLa=ZW5jcnlwdGVkUXVhbGlmaWVyPUExNlk5NVpMVkpCVUQ5JmVuY3J5cHRl...
ISOLATION TEST PT.2 M099 ??????
zhlédnutí 1,4KPřed rokem
Isolation Test held after repairs on both sides of ball valves. Watch as I change the drier core, vacuum, and recharge with 75 lbs M099. Will it work well for this application?
IT KEEPS GOING FLAT ! ISOLATION LEAK TEST AND REPAIR - PT. 1
zhlédnutí 2,5KPřed rokem
A School District maintenance crew sent us a call for a circuit on a large old condensing unit to air handler setup, complaint was a circuit keeps going flat and they need help locating the leak. Watch as I install isolation ball valves with pressure taps to section off the air handler from the condensing unit to help with future service and leak location verification. Found a cracked nut on an...
NON CONDENSIBLES IN SYSTEM !? No Cool Call !
zhlédnutí 13KPřed rokem
Split system AC no cool call where I discovered non condesibles in system! Watch how I resolve the issue , comment and subscribe What do you think was inside the system ?
THEY KEEP RESETTING THE ALARM WITH THE BREAKER - TRANE CGAM CHILLER
zhlédnutí 4,2KPřed 2 lety
Service call for an air cooled Trane CGAM chiller - customer kept resetting the alarm using the main breaker for the unit - thankfully no major issues! Coil Cleaning and system performance check up
The Church Daycare is HOT - Tripped Breaker - No Cool Call
zhlédnutí 6KPřed 2 lety
Old Mismatched split system for church daycare not cooling due to tripped breaker. Watch the video and comment below what you think might have caused the breaker to trip !!
Trane RTAC Pt. 2 - Filter Drier, Vacuum, Recharge
zhlédnutí 11KPřed 2 lety
Finishing out this service call for what was originally a leak repair for this Trane 250 ton RTAC air cooled chiller.
Fieldpiece Vacuum Pump VP87 Quick tutorial
zhlédnutí 24KPřed 2 lety
Just a quick rundown of how to start up your newly purchased fieldpiece 8 cfm vacuum pump
Trane RTAC Leak Repair + Oil Filter Part 1
zhlédnutí 12KPřed 2 lety
What could have been a pretty quick fix turned into a lengthier ordeal when isolation valves on a Trane RTAC chiller didn't hold. Leak Repair oil filter change on screw compressor. Like, comment, and subscribe for future uploads. Will post follow up video when job is complete.

Komentáře

  • @arcadiosalcedo1196
    @arcadiosalcedo1196 Před 8 dny

    How deep was that vacuum?

  • @Parabellum-X
    @Parabellum-X Před 11 dny

    Great job, bro.

  • @TheMaintenanceNetwork-DallasTX

    Keep doing your thing!

  • @Gabriel-vz7ml
    @Gabriel-vz7ml Před měsícem

    Thank you.

  • @s.j.5850
    @s.j.5850 Před měsícem

    Thank you for this video. My system was showing low superheat so I took out some refrigerant out and after that the unit's pressures (low & high side) started surging up & down. Guess I will have to recover whatever is in there, pressure test the system, pull a vacuum, then add some new refrigerant. I'm a new tech gathering all the service tools. Which recovery machine do you recommend?

    • @lammaking333
      @lammaking333 Před měsícem

      The new field piece and navac ones are really nice . The one is most commonly see in the field is the Appion G5 Twin . If you’re going to invest one , make sure it uses a DC brushless motor as well as your vacuum pump . Reason for this is the new line of refrigerants coming next year to replace r410a are classified as flammable and the manufacturers only want brushless motors used so there is no chance for spark ignition ( even though a spark wouldn’t ignite them anyway , it’s a safety precaution )

    • @lammaking333
      @lammaking333 Před měsícem

      I’m the channel creator , this is my personal profile ( sorry I was signed into the wrong account when replying

    • @s.j.5850
      @s.j.5850 Před měsícem

      @@lammaking333 Ok, thanks. Appreciate your advice.

  • @gyo_wrld2767
    @gyo_wrld2767 Před 2 měsíci

    I literally just ran into sum like this the other day think man for confirming my diagnostics

  • @hectorgarcia-zv1wi
    @hectorgarcia-zv1wi Před 2 měsíci

    Cool

  • @saucyg6371
    @saucyg6371 Před 2 měsíci

    Some knipex cobras and pliers wrench might save you some space… or take up more space

  • @robertmason4334
    @robertmason4334 Před 3 měsíci

    I’m struggling with an rtwd chiller been working very well but now it’s tripping on low refrigerant temperature. Possibly low on charge what do you think when you see those alRms

    • @dfwhvac
      @dfwhvac Před 3 měsíci

      Could be a few different things but immediate thought would be low on charge. Check all connections including threaded connections for sensors and transducers , king valves , etc with soap bubbles . Many leaks common from those areas on all Trane chillers. Pull all panels and inspect coils for oil stains . It’s possible could be a metering device problem but not likely - usually you’d get a low suction super heat alarm. After checking with bubbles , pull the water strainer and verify if it’s clean or dirty . Final step to actually know for sure if it’s low charge would be recover the charge and weigh the charge and compare to data tag. If for example your charge weight is 120 lbs and you only recover 70 lbs this for sure would be your tell tale sign. Hope this helps

  • @Matt_Talley
    @Matt_Talley Před 3 měsíci

    How long did it take for you to get your SB-LD?

    • @dfwhvac
      @dfwhvac Před 3 měsíci

      It’s been awhile but off the top of my head I think it was anywhere from 2-4 weeks

  • @glendekoker3682
    @glendekoker3682 Před 3 měsíci

    End this peace must come.

  • @n3ur0tic881
    @n3ur0tic881 Před 4 měsíci

    Can a 16" laptop fit in the front pouch and be secured with the 2 straps?

  • @antonalderliesten1421
    @antonalderliesten1421 Před 4 měsíci

    Thanks man!

    • @dfwhvac
      @dfwhvac Před 3 měsíci

      Thanks for watching

  • @Nightmare52199
    @Nightmare52199 Před 5 měsíci

    Thanks for the video, how often should someone change the oil of the pump?

    • @tomniielander944
      @tomniielander944 Před 4 měsíci

      Most pump's recommend after every use, which I assume would be every couple of days worth of use. A used oil would not allow the pump to pull-down vacuum to full spec. So a pump that can do 25 microns, would top out at 100 or 200 microns with used oil. So you can close off all the vacuum ports, and just have a gauge attached, and see if you can get the spec to check oil condition. Basically the oil is hydroscopic, and absorbs moisture and other stuff that degrades it's performance. Also this Fieldpiece pump has two reservoirs, and allows an oil change without breaking vacuum.

  • @jaronlinux
    @jaronlinux Před 5 měsíci

    Appreciate it bro!

  • @jhatfield2755
    @jhatfield2755 Před 5 měsíci

    Nice actually has tools that are realistic

  • @mattheweveleigh6351
    @mattheweveleigh6351 Před 5 měsíci

    Nice video you did, just wondering what’s better Klein or veto bags? I work in the trades and carry a heavy bag and wondering what will last longer and have a good zipper and storage for my tools.

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      The Klein backpack I had years ago was a good bag , but when you unzipped it , it would not stand up right and would tip over , which was very annoying . I will say this from experience , Veto bags are higher quality and more catered to and have more thought put into the pouch placement and overall design and are more Durable and have a five year warranty. That being said , if you’re trying to save money the Klein bag is still a fantastic bag for the price , and last I checked , the Klein backpack had a lifetime warranty through Home Depot. Meaning you could just bring your old torn up bag in and walk out with a new one same day. I’m not sure if that’s still their policy , but you can’t go wrong with either.

    • @mattheweveleigh6351
      @mattheweveleigh6351 Před 5 měsíci

      Ok thanks for letting me know your experience ,I live in Canada, the veto bag is over 550 with tax and shipping the Klein is 275 plus tax and shipping,

  • @christiansaenz8801
    @christiansaenz8801 Před 6 měsíci

    Awesome video man. Best real world application of your bag/tools I’ve seen

    • @dfwhvac
      @dfwhvac Před 6 měsíci

      Thanks for watching

  • @kennethlobo4420
    @kennethlobo4420 Před 7 měsíci

    Great video! Fixing isolating valves on the system will definitely help in the future in a large system.

    • @dfwhvac
      @dfwhvac Před 6 měsíci

      It really should be some type of mechanical code to install them on large split systems over a certain tonnage/btu.

  • @kennethlobo4420
    @kennethlobo4420 Před 7 měsíci

    Just a question when ubreplace the refrigerant R422 is there any other adjustment u havevto make?

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      Not for r22. If you have an r22 txv or piston , no adjustment is needed. Evacuate system , replace drier , weigh in charge as liquid close to but a little under the original charge weight , then throttle in remaining charge through suction until superheat / subcooling values are in range depending on your metering device .

    • @HHS-LLC
      @HHS-LLC Před 2 měsíci

      It's only that easy when you are using the setup you are using (MQ converting with p/t programmed in). If you are using simple manifold gauges, you need to convert pressure values to temperatures using the pressure temperature chart for R422b (Nu22b). It is not exactly the same like many think it is. www.freon.com/en/-/media/files/freon/freon-mo99-nu22b-retrofit-guidelines.pdf?rev=cb47ceae0ca247879c21e65941aa1546 pgs 13-17 Thanks for the video. Great diagnosis and info.

  • @kennethlobo4420
    @kennethlobo4420 Před 7 měsíci

    Thanks A lot enjoyed watching this video.found ur cannel accidently

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      Thanks for watching

  • @kennethlobo4420
    @kennethlobo4420 Před 7 měsíci

    Thanks for thus great tip to keep the chilled water pump running when on recovery mode,I know that this has to be done when breaking a vaccum.

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      Yessir , recovery and charging should only been done with verified water flow on chilled water systems to prevent potential freezing issues in the tubes or heat exchanger

  • @ReelBermudaMan
    @ReelBermudaMan Před 7 měsíci

    Can these be installed on a heat pump system? I like to use my air conditioning when it’s cold outside but my system is a heat pump so I still need the heat for the rest of the family when they’re home.

    • @dfwhvac
      @dfwhvac Před 7 měsíci

      Yes they can be used on a heat pump system , however it will require the addition al installation of some type of relay such as a SPDT ( single pole double throw ) with the coil wired to “O” , this will allow it bypass control in heating mode, depending on if your unit energizes reversing valve in heat or cool. You don’t actually want the fan cycle switch to be active when running in heat mode as it is likely to cause a freeze up at the outdoor coil due to low airflow when in heating mode.

  • @VoiD1x
    @VoiD1x Před 7 měsíci

    If that was a semi I’d say oil looks like 10+ years old/or dirty system/or running hot. Pre normal for a screw chiller tho considering compression ratios, you’ll get that darker tint on the POE pre quick from the elevated DLT

  • @smartassmart
    @smartassmart Před 7 měsíci

    good stuff! nice to see good no-nonsense tools that get actual use instead of the usual whole knipex & wera line-up that obviously never seen a service minute in their lifespan.

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      No point in overpaying for hand tools that will preform in a similar manner than a cheaper version and that are likely to get beat up from use anyway. Save your money for the high quality tools you actually need or power tools.

  • @michaelmeza9688
    @michaelmeza9688 Před 8 měsíci

    Very nice video.

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      Thanks for watching

  • @Talentman18
    @Talentman18 Před 8 měsíci

    Thank you for this!!!!

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Před 8 měsíci

    Did you send the oil in for analysis by any chance

    • @lammaking333
      @lammaking333 Před 8 měsíci

      No sir we did not . But we came back a month or two after this call for all the chillers on this school district and submitted oil analysis as part of the annual pm

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC Před 8 měsíci

      @lammaking333 nicely done...oil analysis is a big key to spot a potential major issue

  • @bobparrott8130
    @bobparrott8130 Před 9 měsíci

    Nice work 👍

  • @ramonmolina717
    @ramonmolina717 Před 9 měsíci

    Great Job! Thank you for the key info. As well by as sequence of the process.

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      Thanks for watching

  • @dimogeorgiev1420
    @dimogeorgiev1420 Před 9 měsíci

    Hi what is the app that you used. Thanks

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      Hi thanks for watching. That is the measurequick app. There is a free and paid version . It is compatible with different brands of Bluetooth testing equipment

  • @jesuscollazos2326
    @jesuscollazos2326 Před 9 měsíci

    Can you tell me what’s the red light means

    • @brokerful1
      @brokerful1 Před 5 měsíci

      It means that the gas ballast is open

  • @koolairbros7358
    @koolairbros7358 Před 9 měsíci

    Would you have to recover the charge to replace the oil heater located at the oil separator.

    • @rubensabeast
      @rubensabeast Před 6 dny

      No it sits in a well just like on the compressor

  • @natewesley8507
    @natewesley8507 Před 9 měsíci

    Woo hoo I’m gonna get one as well they are just too awesome not to get

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      Still using . It now serves as my Bluetooth testing set. It fits both my fieldpiece and test probes as well as 3 stubby ball valve hoses , with room for service wrench , spare shrader caps and core removal tools

  • @cwilliams6884
    @cwilliams6884 Před 10 měsíci

    clean your shaft HUH

  • @fkdeazevedo
    @fkdeazevedo Před 10 měsíci

    Is that where you add too?

  • @ljay1627
    @ljay1627 Před 10 měsíci

    They will always be referred to as dikes in our trade no one can convince me otherwise

  • @user-rj5wm9ye5n
    @user-rj5wm9ye5n Před 10 měsíci

    Im working on one today in mesquite

    • @dfwhvac
      @dfwhvac Před 5 měsíci

      I’m located in Ft Worth. Greetings fellow Texan

  • @nervouswreck13able
    @nervouswreck13able Před 11 měsíci

    I subcribed just becUse you said you body building and veto congrats on your baby

    • @shawncriner
      @shawncriner Před 11 měsíci

      Me too.

    • @dfwhvac
      @dfwhvac Před 11 měsíci

      Thanks ! Did a show May 27th this yea , got 2nd place and 3rd place in two classes of Classic Physique. Going on a bulking phase currently and next show is October or December next year . I used to do fitness content but there’s so many people making videos like that I never got any views. You can follow my fitness Instagram @ Tighe_Philbin

    • @shawncriner
      @shawncriner Před 11 měsíci

      @dfwhvac Keep at it man! All of my coworkers and fellow tradesmen just drink beer and get progressively fatter every day. Glad to see someone else out there is on this grind!

  • @joshgregg3579
    @joshgregg3579 Před rokem

    whats the box that holds your electrical connectors?

    • @dfwhvac
      @dfwhvac Před 11 měsíci

      It’s husky brand from Home Depot , you can find it in the tool bag isle. It’s pretty light weight but extremely durable and secures very well and is water proof. Only costs $10-15. It’s held up very well , I would definitely recommend it

  • @danwolfe2343
    @danwolfe2343 Před rokem

    The silver puncture under the cap can stay on line the hole up to your oil fill then push down the plastic will puncture the foil so you don't have to pour it in

    • @dfwhvac
      @dfwhvac Před 11 měsíci

      Awesome tip man ! Never tried that but that makes sense ! Great comment .

  • @user-pn8em4mo7c
    @user-pn8em4mo7c Před rokem

    Great video man! Thanks now I feel alone more confident cleaning the oil filter.

    • @dfwhvac
      @dfwhvac Před 11 měsíci

      Great to hear man and glad I can help ! They’re intimidating at first but if you have someone show you how to do it it’s not as hard as you’d think ! That’s why I make these videos

  • @jtee9548
    @jtee9548 Před rokem

    Do you guys charge the same when working one handed and making videos? I get that churches get a discount, we always gave one, and they are often sales tax exempt, but if we would have worked one handed on electrical systems we'd be in trouble. If there was an issue, even years down the road, an insurance company could/would hammer you.

    • @dfwhvac
      @dfwhvac Před 11 měsíci

      This comment is wild man haha. I never work one handed on anything that would ever pose a risk or legitimately require two hands to work with. I’m 100 percent confident in my skills and never do any work or leave equipment in a state that something detrimental might happen . If equipment poses an actual risk it gets locked out and tagged out. You’ve never checked voltage with one hand with two meter leads ? I appreciate the comment but the insurance thing is king of far out there man haha

  • @kelvinpkp5623
    @kelvinpkp5623 Před rokem

    nice job

  • @rsofficial1588
    @rsofficial1588 Před rokem

    Diacore filter

  • @mexicant777
    @mexicant777 Před rokem

    Do in-depth with a 200 ton system.

  • @shaikjuned712
    @shaikjuned712 Před rokem

    Brother you should show how to store gas and how to release gas before we removed filter drier and which way to best for gas charge in chiller pressure Guage or kg limit

    • @dfwhvac
      @dfwhvac Před 11 měsíci

      Next time I run into that scope of work I will definitely make that video !

  • @samyz1660
    @samyz1660 Před rokem

    Awesome work. Good job. Please keep it coming.

  • @darrend1068
    @darrend1068 Před rokem

    How did u get the second bag free

    • @dfwhvac
      @dfwhvac Před 11 měsíci

      It was a promotional offer from Veto. Check their website every so often , they have deals Pop up at random .

  • @kcomfortsystemshvac7060

    Hi mate ,,,,thanks for you explanation very kind of you ,,,always I learning something,,,good blessings,,,,regards Lorenz