Loss Of Charge TRANE CHILLER CGAM070F … Leaks or Something Else

Sdílet
Vložit
  • čas přidán 12. 02. 2024
  • Got a work order for a 70 ton CGAM in alarm after power interruption with flow loss. #trane #airconditioning #chiller #hvac
  • Jak na to + styl

Komentáře • 21

  • @joshstevens9826
    @joshstevens9826 Před 5 měsíci +5

    Trane has an algorithm that takes superheat and exv position over a certain amount of time. If sh doesn't come down and the exv doesn't get in a certain range it says loss of charge. Usually the suction temp sensor reads really high, like 50-60 ° high. Thats always the first thing I look at when I get a loss of charge alarm.

    • @subcoolHVAC
      @subcoolHVAC  Před 5 měsíci +4

      Yep, it was definitely low on charge due to the leaks. That time frame is 5 min run and under 59 leaving , both compressors running SH was 12 after charging. EXV 60% . We’re replacing leaking service valves and replacing sensors anyways as insurance.

  • @zekenzy6486
    @zekenzy6486 Před 5 měsíci +2

    Great Video. Thank you for sharing

  • @thesilentonevictor
    @thesilentonevictor Před 5 měsíci +5

    She needs some love

  • @ccthepope
    @ccthepope Před 5 měsíci +1

    A great vid!

  • @lee-johnson
    @lee-johnson Před měsícem

    What was the subcooling before you added refrigerant?
    Nice work

  • @georgebrabec1749
    @georgebrabec1749 Před 5 měsíci

    . to take your time, as you can see, working around those EEV's can cause more issues. I had an older 115 ton CGAM that kept going into EEV communication loss, even with the new cables. Used silicon on the connections around the valves, end of issue. Great square one troubleshooting of diagnostics.

  • @ericbaker5619
    @ericbaker5619 Před 5 měsíci +3

    Gotta love neglected equipment

    • @subcoolHVAC
      @subcoolHVAC  Před 5 měsíci +3

      Seen worse, we’ll get it fixed up 👍

  • @adamdnewman
    @adamdnewman Před 5 měsíci +1

    There is almost always a leak somewhere 😂

  • @joshstevens9826
    @joshstevens9826 Před 5 měsíci +2

    9.9 times out of 10 cgam loss of charge alarm is a bad suction temp sensor.

    • @subcoolHVAC
      @subcoolHVAC  Před 5 měsíci +1

      Indeed 👍

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC Před 5 měsíci +1

      Not always though....had one that was leaking from the shell of the receiver

    • @subcoolHVAC
      @subcoolHVAC  Před 5 měsíci +2

      Yep, our old friend Rusty has visited this time