Paano mag Compute ng Magnetic Contactor Size | circuit breaker/fuse | size of wire- thermal overload

SdĂ­let
VloĹžit
  • čas přidĂĄn 9. 09. 2024
  • Computation for sizing of magnetic contactor, circuit breaker/fuse, size of conductor and overload relay setting for a motor controller in single phase and 3 phase power supply | Tagalog tutorial
    Thank you for watching guys!
    Please visit our Channel👇👇👇
    / @localelectricianph
    for more electrical installation and controls video tutorials.
    FB Page: Electricians Guide
    Direct message on our FB page for other questions. Thanks!!
    OTHER USEFUL VIDEOS 👇
    MANUAL OFF AUTO MOTOR CONTROL
    • MANUAL-OFF-AUTO Motor ...
    FLOAT SWITCH wiring and diagram
    • Float Switch wiring an...
    3GANG SWITCH wiring
    • 3 Gang Switch Wiring t...
    HOW TO USE MEGGER / insulation tester
    • HOW to use MEGGER Insu...
    3-WAY SWITCH Wiring Tutorial
    • 3 Way Switch - tagalog...
    WYE DELTA MOTOR CONTROL
    • WYE DELTA STARTER Wiri...
    Stop Start Wiring Control Circuit and Diagram
    • Stop Start Magnetic Co...
    FORWARD REVERSE STEP BY STEP
    • FORWARD REVERSE Motor ...
    On Delay Timer Wiring Diagram
    • ON Delay Timer Diagram...
    FLOATLESS RELAY WIRING
    • Floatless Relay Wiring...
    Stop Start with Overload Relay Connection
    • Magnetic Contactor Sto...
    • Overload Relay ( therm...
    OVERLOAD RELAY Function tutorials. tagalog
    OHMS LAW
    • OHMS LAW - Voltage Cur...
    24 HOUR TIMER FUNCTIONS
    • HOW TO SET 24 HOUR CLO...
    • Multimeter Paano guma...
    How to use MULTIMETER tagalog video
    STOP START w/ INDICATOR LAMP
    • STOP START w/ INDICATO...
    • HOW TO SPLICE A WIRE -...
    How to Splice a Wire video
    MAGNETIC CONTACTOR PARTS AND FUNCTIONS
    • Magnetic Contactor Par...
    VOLTAGE TESTER
    • VOLTAGE TESTER NEON SC...
    HOW TO COMPUTE ELECTRIC BILL
    • Electric Bill Computat...
    7 WAYS TO REDUCE ELECTRIC BILL
    • HOW TO LOWER ELECTRICI...
    POWER FORMULA
    • POWER CURRENT VOLTAGE ...
    HOUSE WIRING TUTORIAL
    • HOUSE WIRING TUTORIAL-...
    PHOTOCELL with Magnetic Contactor
    Wiring/Diagram-street lights
    • PHOTOCELL w/ Magnetic ...
    Magnetic Contactor VS Mechanical Relay
    Uses and Function
    • Magnetic Contactor VS ...
    SUBMETER INSTALLATION
    • SUBMETER INSTALLATION ...
    MECHANICAL RELAY WIRING
    • RELAY WIRING TUTORIAL ...
    Music:
    Tuff Data | Vans in Japan
    No Copyright claim.
    • Video

Komentáře • 214

  • @simpaticovlog4743
    @simpaticovlog4743 Před 2 lety +3

    Mag kaiba po ang FLC at FLA
    FLC po makikita sa table sa PEC yan po gagamitin sa pag kuha ng size of wire (FLC x 1.25)( FLC x 2.5) nmn po sa CB.FLA po gamit sa pag kuha ng OL FLA a makikita sa name plate of the motor

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety +1

      Salamat sa Inputs Sir 👍👍

    • @arindar4310
      @arindar4310 Před rokem

      boss bkt po napansin ko maliit lng nag wire compara sa rating ng CB??

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem

      Ito po sagot Sir. New video natin czcams.com/video/icOiQXh6D3E/video.html

    • @TeamArVes
      @TeamArVes Před rokem +1

      @@LocalElectricianPH No offense sir Working naman sir yung computation nyo good job and it will work sa real situation pero base sa PEC FLC ang ginagamit sa computation sa Size ng Wire and inverse time CB

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem +1

      @TeamArVes ues Sir FLC po talaga lalo pag planning and designing Sir kasi d pa ho kita ang actual nameplate ng motor..pero f meron napong nameplate Sir. Pwedi po mg refer sa nameplate. Since ito naman po ay tanggap internationally ay nka saad dn po sa PEC na internatinal standards may use

  • @moromagstv6295
    @moromagstv6295 Před 3 lety +1

    Napakalinaw ng computations thanknyou for sharing kapatid

  • @aveghellavandero4447
    @aveghellavandero4447 Před 3 lety +1

    Marami rin ako natutunan sa mga video nyo thank you sir

  • @gonfrics3157
    @gonfrics3157 Před 3 lety +1

    Thanks nang marami mAster...

  • @jomarbelludo9704
    @jomarbelludo9704 Před 3 lety +1

    Salamat master

  • @helcurtbulatao1625
    @helcurtbulatao1625 Před rokem +1

    ayus yan boss

  • @bobbymanerbandilla5110
    @bobbymanerbandilla5110 Před 8 měsĂ­ci

    Salamat sir gets kuna

  • @felixalburo622
    @felixalburo622 Před 2 lety +1

    thank you sir

  • @junexcuarentas8519
    @junexcuarentas8519 Před 2 lety +1

    Salamat boss

  • @HariHari-jr5pg
    @HariHari-jr5pg Před 3 lety +1

    ISATISFIED VERY MUUCH. THANK YOU .BUT GIVE THE DETAIL FOR DOL & ATS& RRS STARTERS.

  • @jmtolentino6397
    @jmtolentino6397 Před 10 měsĂ­ci +2

    yung FLA sa contactor ng main ng 3 phase na dinivide na sa 1.732 para makuha didivide mo ulit sa 1.732? (multiplied by 58% same as 1/1.732)

  • @dibgrol5759
    @dibgrol5759 Před měsĂ­cem

    Nice video very informative, base on motor nameplate aling voltage ang ggamitin pg compute, yung 230v or yung 380v? Sana masagut lodi Thanks

  • @mhelvinmanalo3140
    @mhelvinmanalo3140 Před 3 lety +1

    Sir,baka pwede gawa rin kayo ng tamang pag compute ng capacitor pag singe phase motor,ty

  • @arnilbardelosa2451
    @arnilbardelosa2451 Před 2 lety +1

    FLA is being used for thermal overload computation, FLC you need to check the PEC for Cable and CB computation fyi..

  • @dayveaguilar8638
    @dayveaguilar8638 Před 2 lety +1

    Ung mga formula and computation mo sir Naka base yan sa Philippine electrical code thanks

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Actual ratings at ohms law lang yan sir. Pero meron nka pin comment article sa PEC sir kung saan mo makikita ang standard flc rating.

  • @genrosetvchannel6914
    @genrosetvchannel6914 Před 3 lety +1

    Sir suggestion lang Po dapat may PEC refference table po kayo para hindi po malilito ang mga beginers.

  • @helcurtbulatao1625
    @helcurtbulatao1625 Před rokem +1

    mejo nguluhan ako sa equation nkbraket ung devisor

  • @johnwilliampolicarpio
    @johnwilliampolicarpio Před 3 lety +2

    Correct me If im wrong db yung FLA ay karaniwan nasa nameplate nman sya at yung FLC naman nya nasa PEC book

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Yes sir. FLA ay nasa name plate po ng motor at ang resulta ng actual test ng ibat ibang manufacturer sir.

  • @ryanraybusoy422
    @ryanraybusoy422 Před 2 lety +1

    Hi sir .. good tutorial.. hoping and praying na marami pa Po kayung matulongan....
    Tanong ko lang Po ..always Po ba .08 Ang power factor nag motor? Or nag depende Po sa electric motor?

  • @JoseLeslieMontecillo
    @JoseLeslieMontecillo Před měsĂ­cem +1

    Sir ano po reference natin at san po nang galing ang 58% for the main at delta contactor at 33% for the wye contactor? Thank you!

  • @animedc9903
    @animedc9903 Před 6 dny

    Sir tanong ko topic 3phase my nameplate motor naka lagay naman ampere mostly...FLA bayan nasa name plate?

  • @ryanraybusoy422
    @ryanraybusoy422 Před 2 lety +1

    Hi sir good evening...
    Mabuhay Po kayu sana marami pa Po kayung ma eturo sa kagaya namin na nag sisimula....
    May tanong lang ako sir..dba Ang
    Answer nang 100% x FLA
    100% x 29.9
    Convert to decimal Ang 100%
    So .100 x 29.9 = 2.99
    Or 1.0 x 29.9? Yan Po ba?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Hindi Sir...100% ng 29.9 is 29.9 dn..wag nyo na po e convert kasicyun napo yon

    • @ryanraybusoy422
      @ryanraybusoy422 Před 2 lety +1

      @@LocalElectricianPH ahh ok ..salamat po ....Isa Po ako sa subscriber nyo Po.....
      Last question Po .san Po makikita ag amperes nang Isang magnetic contractor?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Nasa gilid meron yan nkalagay specs

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Or sa box pag bibili ka

    • @ryanraybusoy422
      @ryanraybusoy422 Před 2 lety +1

      @@LocalElectricianPH ahh ok sir Akala ko may computation din....thanks Po godbless 🙏 more blessings Po..

  • @xxsuperacerxx
    @xxsuperacerxx Před 3 lety +2

    Sir tanong ko lang po saan po reference ninyo ng table po ninyo? Curios lang po sir

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety +2

      Yan po ay base sa actual formula Sir. Meron din pong standard FLC ratings sa PEC nasa article 4.30.14.2 up to 4

  • @jeromecarullo66
    @jeromecarullo66 Před rokem +1

    Baliktad computation mo sa nontime and time delay fuse.

  • @bobbymanerbandilla5110
    @bobbymanerbandilla5110 Před 8 měsĂ­ci +1

    Sir sa nkuha Yung 167

  • @engr.mathik1392
    @engr.mathik1392 Před 3 lety +1

    Sana may reference kayo sa PEC.

  • @HariHari-jr5pg
    @HariHari-jr5pg Před 3 lety +1

    MAGNETIC CONTACTOR SIZING FOR DOL AND ATS STARTERS

  • @busraahmed1708
    @busraahmed1708 Před 2 lety +1

    please english subtitle

  • @Creator-ux9uf
    @Creator-ux9uf Před 3 lety +2

    san mo kinuha ang 167 boss?

  • @aveghellavandero4447
    @aveghellavandero4447 Před 3 lety +1

    Yan din poh ba ang formula sa multiple motor example sa ricemill

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety +1

      Yes sir f individual..pero f multiple tapus my main breaker kayu. Iba po computation ng main feeder

    • @aveghellavandero4447
      @aveghellavandero4447 Před 3 lety +1

      Pwedi poh maggawa poh kau video kasi sa ricemill may 2 main breaker ung 1st breaker malaki ung 2 breaker ma's maliit NG kaunti. All motor nasa 300hp kung minsan lahat lahat ang hp NG mga motor

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety +1

      Anong control po gamit nyo sir. Soft starter?

  • @alterlaroza6503
    @alterlaroza6503 Před rokem +1

    Good day sir, ilang amps po ng C.B. , magnetic contactor at overload relay po ang pwedeng gamitin sa 1 HP na motor? Thanks in advance po sir.

  • @jhonemmirabuenos1490
    @jhonemmirabuenos1490 Před rokem +1

    Paano po e compute ang wire size ng auxilliary contact?

  • @jumelnonod6849
    @jumelnonod6849 Před 2 lety +1

    Master tanung q lang po..may control po ung motor namin ng isang start stop n panel..saka isang wye delta n panel..saan po kabilang un sa delay po ba o non delay or sa CB?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Y8ng wye delta po sir ang may delay. Sa transistion from wye to delta. Nasa 2 to 4 sec difference

  • @lofttakobetv1018
    @lofttakobetv1018 Před 2 lety +1

    Paturo naman mag wiring ng wixim mc with ol para sa float switch.. mahirap Kasi sundan wiring mo dun sa isang video using fuji mc

  • @gearupracing5588
    @gearupracing5588 Před 3 lety +1

    Boss ano po amp pwede gamitin na contactor sa 10hp motor phase converter at ilang mfd na capacitor po gagamitin. Salamat

  • @junexcuarentas8519
    @junexcuarentas8519 Před 2 lety +1

    Sir paanu malaman ang tamang overload para sa isang motor example po sir.fla ng motor ay 3.58.

  • @wildfangs-tv8637
    @wildfangs-tv8637 Před 4 měsĂ­ci

    naiba na master explanation mo 3years after netong video mo about sa wye delta connection,naging Overload relay setting= FLA x 125%(maximum) or 115%(minimum)

    • @LocalElectricianPH
      @LocalElectricianPH  Před 4 měsĂ­ci

      125% to 140% payan Sir max dependi sa load and sa minimum naman kahit up to 70% basta di lng mg trip ang pwedi naman po...

  • @benjohntombado4960
    @benjohntombado4960 Před 10 měsĂ­ci +1

    Pano naman sir pag compute ng required current rating ng time delay relay?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 10 měsĂ­ci

      Time delay fuse po yata nasa video Sir...para saan po gagamitin ang time delay relay?

    • @benjohntombado4960
      @benjohntombado4960 Před 10 měsĂ­ci

      @@LocalElectricianPH on delay ng automatic pump motor after blackout sir

    • @LocalElectricianPH
      @LocalElectricianPH  Před 10 měsĂ­ci +1

      @benjohntombado4960 controls lng naman po ang time delay Sir..as is napo ang computation sa motor power coonections and supply..meron ako video sa channel playlist about time delay controller sir pki visit lng po

    • @benjohntombado4960
      @benjohntombado4960 Před 10 měsĂ­ci +1

      @@LocalElectricianPH bale pag sa control circuit yung aux. contacts nya di sya affected ng FLA ng motor?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 10 měsĂ­ci +1

      @benjohntombado4960 di po..power circuit lng ang apectado ng FLA n syang recta ng switch ng motor..ang control ckt mga coil ng contactor at relay at indicator lamps lng load nyan

  • @kalikotpangmasa301
    @kalikotpangmasa301 Před 4 měsĂ­ci +1

    Ano Po Ang gagamitin na magnetic contactor (ampheres)sa walong ilaw na halogen 4,000watts Ang isa

  • @bobbymanerbandilla5110
    @bobbymanerbandilla5110 Před 8 měsĂ­ci +1

    Sir San Po b yang 8.0 para sa Fedder Po b Yan o papunta sa load

  • @karmich8648
    @karmich8648 Před rokem +1

    Sir panu b malalaman yong isang device kung motor load kpag b may horsepower yon yong babasihan para malaman kung motor load

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem

      Yes po..sa hp po tayo mag base f anong size ng wirr gagamitin..at amperahe na kailangan para sa contactors at breakers po

    • @karmich8648
      @karmich8648 Před rokem

      Kpag may horse power ibig sabihin motorload sya.. Salamats po..

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem

      @karmich8648 Sir..horsepower or watts or kilowatts same lang naman po yan Sir..unit ng Power parin yan..1 hp is 746 watts...1 kw is 1000 watts

  • @jovindejesus8076
    @jovindejesus8076 Před rokem +1

    Saan po nakuha Yun 499.6 n sagot?

  • @senpaikai278
    @senpaikai278 Před 3 lety +1

    Master, okay lng ba 7kw booster pump, gamitan ko ng magnetic relay 10A for interlocking controls bukod pa po yung magnetic contactor.

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      3 phase po ba? Maliit yan sir

    • @senpaikai278
      @senpaikai278 Před 3 lety +1

      @@LocalElectricianPH opo master 3phase 220v 19.8FLA booster pump, bale alternate yung dalawang booster pump. Kailangan kasi ng relay for interlocking, mga ilang ampere po ba ng relay ang kailangan?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety +1

      Ahh ok po..kaya n nyan 10 amps for interlocking sir.

    • @senpaikai278
      @senpaikai278 Před 3 lety +1

      @@LocalElectricianPH sige master maraming salamat po

    • @senpaikai278
      @senpaikai278 Před 3 lety +1

      Akala ko kasi if anong rating ng magnetic contactor eh ganun din sa magnetic relay.

  • @zaldybuenaobra1781
    @zaldybuenaobra1781 Před 2 lety +2

    Idol tanong ko lng po saan po b gling Yung 167?

  • @markjoeydavid7992
    @markjoeydavid7992 Před 3 lety +1

    Sir question lang po. Bale po sa unang part ng presentation nyo po, ang computed wire/conductor size is 8.0 na nasa 40 - 50amps rating tapos po ang computed fuse/cb ay nasa 70 plus. Okay lang po ba na undesize ang wire?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Ang conductor sizing po kasi sir ay 125% ng full load current. Samantala ang cb o fuse po ay ng range ng 170% to 300%

  • @bryanblanks8042
    @bryanblanks8042 Před 2 lety +1

    AyOs.

  • @eugeniogozon7440
    @eugeniogozon7440 Před 7 měsĂ­ci

    Sir, deep well water pump motor, 1/2hp 1-phase , SF 1.6 , SFA 5.3 at 230V. Paano malaman ang FLA?

  • @kilogrammountain3453
    @kilogrammountain3453 Před 3 lety +1

    Boss tanung lang po halimbawa may gagawin ako start stop DOL tapos gusto ko sya lgyan ng breaker para maging safe yung mga contactor coil mga ilang amps po ang kailangan na breaker para sa control at panu po malalan kung ilan yung amp ng isang contacto coil

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Hindi po kasi given ang amperahe sa coil kung gusto nyo po malaman. Pwedi nyo po sukatin amperahe ng controls nyo sir. Gamit ang clampmeter tpus jan napo kau mg base ng breaker size

    • @kilogrammountain3453
      @kilogrammountain3453 Před 3 lety +1

      @@LocalElectricianPH ah ok posir slamat sa idea

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Welcome po

  • @dynamokingtv6144
    @dynamokingtv6144 Před rokem +1

    Boss magandang araw, ang 2hp 230v single phase 9.4amps, max load 12.9amps na waterpump boss ano kaya pwede gamitin na ampere ng contactor at overload, di kase ako marunong mag compute..

  • @jasperlacap3481
    @jasperlacap3481 Před 2 lety +1

    Sir...
    Yung overload relay po ba ng 3 phase motor is Min(70%) and Max(125%) parin po ba ng Main Contactor na 58% of FLA?
    Example :
    19.01 yung FLA so ang Main contactor is 11A dahil 58% lang sya ng FLA.
    Mag babase po ba yung Min70% and Max125% ng Overload relay sa 19.01A or sa 11A?
    Salamat po.

  • @jameszamora2499
    @jameszamora2499 Před rokem +1

    Sir question lang po.
    Saan po magbabase ng full load current kapag may Service Factor(SF) po na 1.15 sa nameplate ng motor (Computation po for Circuit Breaker)
    Ex:
    At 15 hp, 230 V, 3 phase motor
    IFL= 41.6 A
    IFL with SF = 47.84 A
    Alin po gamitin ko sa kanila sa pag multiply po ng 250%?
    Thank you in advance, Sir. ⚡

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem

      42A po ang flc ng 15hp base sa PEC Sir. ..so pasok jan ang nasa nameplate na 41.6A

  • @paulosalenga34
    @paulosalenga34 Před 2 lety +1

    Panu po kunin ung efficiency.?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Output/inputx100

    • @paulosalenga34
      @paulosalenga34 Před 2 lety +1

      @@LocalElectricianPH saan nman po mkikita ung input output.?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Power po in watts..nasa name plate ng motor. Convert hp to watts

    • @paulosalenga34
      @paulosalenga34 Před 2 lety +1

      @@LocalElectricianPH salamat po kita ko na po..😊

    • @paulosalenga34
      @paulosalenga34 Před 2 lety

      Ang hp ng motor ko ay 30hp ang kw po kw po ay 22 ang nkuha ko pong efficiency ay 1017 tama po ba.?

  • @leonardoso4301
    @leonardoso4301 Před 2 lety +1

    Sir San po nakuha ang 167? 220/167? And .8 and 95%... ty

  • @kentlybaguin.eteeap7434
    @kentlybaguin.eteeap7434 Před 3 lety +1

    Sir sa Sizing ng Conductor diba FLC Dapat as per NEC 430,22

  • @guitarone71
    @guitarone71 Před 3 lety +1

    Sa single phase section sir 8.0mm ang wire which is 40ampacity pero sa CB is 80Ampere. Ok lang ba yun sir undersize ang wire na 8.0mm sa 80amp breaker?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety +1

      Delicado yan sa sunog sir. Dapat po match

    • @guitarone71
      @guitarone71 Před 3 lety +1

      @@LocalElectricianPH Ah so lahat ng computation ang wire size sa motor control naka match lang sa CB tama ba sir?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Match sa wire. cb. at full load current ng motor sir

    • @guitarone71
      @guitarone71 Před 3 lety +1

      @@LocalElectricianPH Ok sir mali lang ako pagkakaintindi sa video. maraming salamat

    • @humbeym9069
      @humbeym9069 Před 2 lety +1

      @@guitarone71 tama ka po sir, okey lang po na #8 ang wire mo at 80amps ang breaker kase nga kaya mataas ang breaker para hindi mag trip kase may starting current tapos after ilang seconds mag nonormal na ang current kaya kayang ihandle ng #8 na wire ang running current

  • @janjanboquia6738
    @janjanboquia6738 Před 3 lety +1

    Sir pano po mag determine ng wire size na gagamitin sa control circuit.,? Ano po formula?

  • @mikelife714
    @mikelife714 Před 3 lety +1

    master plano ko mag run ng 50 units 3000w each kakayanin ba ng residential to? any tips

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Yes sir. Gamit lng po kau ng magnetic contactor na higher sa 3000 w ang capacity sir

    • @mikelife714
      @mikelife714 Před 3 lety +1

      @@LocalElectricianPH kahit ilang unit po sir? bale sa 50 units po sir, gamit lang po ako ng tigiisang magnetic contactor na may 3000w capacity? di naman po 3000w yung unit exacto nasa 2600w lang po

    • @mikelife714
      @mikelife714 Před 3 lety +1

      kaya po yung nung entrance wiring from post to metro kahit ilang unit sir?

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Pwedi naman po sir kaso napaka laking load po nyan. Kailangan nyo po mag palit ng service entrance conductor. Mas mainam po ipa compute nyo lng po sa regĂŹstered electrical engineer sir para sure at safe sir

    • @LocalElectricianPH
      @LocalElectricianPH  Před 3 lety

      Hindi sir number 8 lng po yan sa minimum residential service entrance up to 32 amps lng po kaya nyan..yong sinasabi nyo sir ay aabot yun ng up to 652 amps

  • @btmachinist6085
    @btmachinist6085 Před 3 lety +1

    Sir ano po size ng contactor saka thermal relay para sa motor na 2.2kw

  • @ricafordvestidas3709
    @ricafordvestidas3709 Před rokem +1

    Ask lg sir nka depende pla sir ang size nang breaker protection sa type nang breaker.ask lg sir ang miniature circuit breaker po ilang percent po sya at saan sa na belong sa time delay,non time delay or normal cb lg ba?salamat sir sana matugunan mo.😊

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem

      Miniature cb at cb ay same lng yan Sir 250% pinagkaiba lng ng miniature ay hqnggang 100A png pinaka mataas nyan..

    • @mecoulyssescumpio9145
      @mecoulyssescumpio9145 Před rokem +1

      Mayron Ng 125A mcb Po sir

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem

      100A lng po max ng mcb

    • @ricafordvestidas3709
      @ricafordvestidas3709 Před rokem +1

      ​@@LocalElectricianPHsir ask lg po about wye delta starter ang pag sizzing nang breaker nya same D.O.L parin ba applications sir?thank you po sa pagsagot sir.

    • @LocalElectricianPH
      @LocalElectricianPH  Před rokem

      Hindi po..3 phase kc wye delta. Kalimitan sa dol 1 ph

  • @hatchiretchi1955
    @hatchiretchi1955 Před 3 lety +1

    idol pwede po patulong, ilang ampere po ba yung magnetic contactor para sa 2hp na motor? Paano po e calculate yun master? At pwede po oa example idol Salamat po 🙏

  • @shadshad2851
    @shadshad2851 Před rokem +1

    paano nakuha ang 499.62 sa 3phase kasi compute ko mali man dimo kasi sinasabi kung paano nakuha

  • @jeffersonacosta6030
    @jeffersonacosta6030 Před 2 lety +1

    sir Hindi ko gets San galing Ang 499.62 sir sa 3phase

  • @jonathantalirongan3830
    @jonathantalirongan3830 Před 3 lety +1

    Boss saan kinuha ang 167?

  • @joristylegaspi9413
    @joristylegaspi9413 Před 3 lety +1

    San galing yung 167 sir

  • @jhunanario6075
    @jhunanario6075 Před 2 lety +1

    Sir sorry paano naging 167 ang sagot

  • @bambi7872
    @bambi7872 Před rokem

    Anong nangyari Dyan 14 amp lang Ang gagamitin na contactor sa 10 HP na motor sunog Yan gaya Ng sa air compressor 10 HP Ang nakakabit 35 amp...paki sagot po

  • @jessiejalimbawa9966
    @jessiejalimbawa9966 Před 10 měsĂ­ci

    I=5000/220v*.8*.95 = 17.5 po lumalabas sken bakit po ganun

  • @Korn-7005
    @Korn-7005 Před 2 lety +1

    Sir mali po yung sequence ng computation nyo ng FLA...i-apply nyo po yung PEMDAS iba po yung magiging resulta ng sagot...salamat😊

    • @LocalElectricianPH
      @LocalElectricianPH  Před 2 lety

      Salamat lods.

    • @rhadcliff5556
      @rhadcliff5556 Před 2 lety +1

      Parang wala namang mali.

    • @Korn-7005
      @Korn-7005 Před 2 lety +1

      @@rhadcliff5556 sir pansinin mo yung ginamit n symbol ( / ) slash represent division pr P/V dapat (----) fraction n symbol pr P
      _______
      V x pfxn

    • @Korn-7005
      @Korn-7005 Před 2 lety +1

      Dahil kung PEMDAS yung i-aapply natin una mong idi-divide yung P/V kasunod yung multiplication

    • @Korn-7005
      @Korn-7005 Před 2 lety +1

      Dahil yung division ay ns left side

  • @jessiejalimbawa9966
    @jessiejalimbawa9966 Před 10 měsĂ­ci

    hindi po lumalabas 167