Single motor branch circuit calculation

Sdílet
Vložit
  • čas přidán 30. 08. 2020
  • Matututunan dito kung paano magcalculate kung ano ang wire size, overload setting at Circuit breaker na gagamitin sa single motor branch circuit

Komentáře • 75

  • @camchannel17
    @camchannel17 Před rokem

    Sir bagohan lng aku sa 3 phase industry dahil video natu madali ku natutunan sir tnks sa video sir

  • @PinoyFanimeTV
    @PinoyFanimeTV Před 6 měsíci

    Sana sa next VLOG How to operates equipments ATS , MVSG, LVSG & GENSET... thanks😊

  • @glennmasumpad7938
    @glennmasumpad7938 Před rokem

    Good morning sir, salamat sa mga binahage mo na mga calculation sa single motor thumbs up sayo sir...sir baka Meron na sa 2017 na PEC na contactor calculation kung Meron sir please po share sa calculation,,, thank you and God bless po,,

  • @glennacas2648
    @glennacas2648 Před rokem +2

    Galin u mgpaliwanag boss salute aq god bless

  • @adonisincenales9160
    @adonisincenales9160 Před 3 lety +3

    Thanks sir..Very informative ... Malinaw at step by step ang pakaka explain...nice well done sir...
    Keep up you good work sir...mas marami kapang matutulungan na nagsisimula palang tulad ko....
    At sana sir kung my time ka gusto ko sanang mag request tungkol sa kung pano mag compute ng kaic ng MCCB, ACB at mag setting ng micrological setting tulad ng long time delay, short time delay at short ckt. etc....thanks po sir in advance and more power sa channel mo...😇

  • @damonyorgalvez1966
    @damonyorgalvez1966 Před 3 lety +2

    Sir sana makagawa ka rin ng video tungkol sa pagcompute ng A.C.U. branch conductor at tamang ocpd ng 3-tonner or 5-tonner na ang given ay rated current at working voltage, abangan po namin pag free kana sir.

  • @doninsoy7596
    @doninsoy7596 Před rokem +1

    Salamat sir.. nsundan q ung PEC..

  • @adonisincenales9813
    @adonisincenales9813 Před 4 měsíci

    Thank you poh...very informative tanong ko lng sir...but malaki ang ampere trip rating ng CB sa conductor rating...please enlighten me thank you poh sir

  • @alvin123456789100
    @alvin123456789100 Před 2 lety

    Maraming salamat sir. Maraming natutunan ako sayo. God bless

  • @leoawag8515
    @leoawag8515 Před 3 lety

    Maraming salamat po sir sa malaking tulong mo sa amin na gustong matoto .
    God bless po.

  • @joelgecain2166
    @joelgecain2166 Před 2 lety

    Very comprehensive and detailed yung paraan mo sa pag-discuss sir. Love it.

  • @epifaniobedro1010
    @epifaniobedro1010 Před 3 lety

    Thank you po Sir..

  • @dynielpagdanganan4260
    @dynielpagdanganan4260 Před 3 lety +1

    More power!

  • @edwardsonmartinez4585

    Thank you sir.question lng po..ok lng po ba na 3.5 mmsq ang wire tas 40at ang breaker?

  • @damonyorgalvez1966
    @damonyorgalvez1966 Před 3 lety +2

    Sir favor lng...baka pde mo gawan ng video yung multiple motors with different size and a combination of a single phase on how to take the main feeder line and main ocpd as well, medyo ndi claro doon sa isa kung napanood, maraming salamat and more power to your channel

  • @danilolegaspi1764
    @danilolegaspi1764 Před 3 lety

    Ty sir

  • @DadiiKo
    @DadiiKo Před 2 lety +2

    Sir pwede po bang makahingi ng soft copy ng mga article nyo po sa pec? Malinaw po kayong magturo, ang rami ko ng napanuod ng mga videos nyo dito sa channel nyo po sir. Galing.

    • @TagalogElectricaltips
      @TagalogElectricaltips  Před 2 lety

      salamat nman. tuloy nyo lang pag aaral

    • @DadiiKo
      @DadiiKo Před 2 lety

      More uploads po sir. Pwede po ba maka hingi ng soft copy sir, baka may pdf po kayo sir..

  • @jhonemmirabuenos1490
    @jhonemmirabuenos1490 Před rokem +1

    Panu po e compute yung wire size na gagamitin sa auxilliary contact?

  • @cas49713
    @cas49713 Před rokem

    Great explanation Sir, ask ko lang about sa voltage drop, kung kailangan din i-consider sa pag compute ng conductor size?

  • @sohrabalmajose4082
    @sohrabalmajose4082 Před 4 měsíci

    please clarify if reduced voltage is used on your sample problem. thank you

  • @marcelinojrdusarann6636
    @marcelinojrdusarann6636 Před 10 měsíci

    Gondola motor 3phase connection running two motor synchronised forward reverse

  • @perquinooasan3835
    @perquinooasan3835 Před 3 lety +1

    sir, kung 380 v supply ano gagamitin na full load current wala po sa table?

  • @DadiiKo
    @DadiiKo Před 10 měsíci

    Sir how about po marami motor with different hp, ano po calculation po ng main breaker at main feeder conductor

  • @darsdng2143
    @darsdng2143 Před 2 lety

    Hi Sir, ask ko lang po ang sa Branch circuit short circuit and ground fault protection kong ang gagamitin mo ay MPCB (Motor Protective Circuit Breaker) same multiplier 250% of full load current? Ty Sir

  • @marvincastanos4791
    @marvincastanos4791 Před 3 lety +2

    sir pwedi pa request paturo sana ako paano mag install ng magnetic contractor salamat sir 😊

  • @mariacrismayugba1418
    @mariacrismayugba1418 Před 3 lety +1

    Master.. Pano ung pag setting ng over load protection

  • @bobbieherrella2561
    @bobbieherrella2561 Před 3 lety

    Sir ung po binigay nyo percentage ng overload protection para po s more than 1 hp.paano po s 1 hp or less ano po gagamitin percentage?kailangan p po b ng overload protection pag less than 1 hp

  • @nadim606
    @nadim606 Před rokem

    Seen

  • @jovenhunat1287
    @jovenhunat1287 Před 3 měsíci

    Dpo ba Sir Ang standard ng 40A CB ay 8.0mm salamat po sa sagot?

  • @abniranasco6239
    @abniranasco6239 Před 3 lety

    Sna my video/actual diagram nyan boss kung paano mapagana....

  • @renechavez8275
    @renechavez8275 Před 3 lety +2

    Screen shot ko master malabo po thanks master

  • @renechavez8275
    @renechavez8275 Před 3 lety +2

    Master okay lang po bah pahingi nito motor cumpute salamat master

  • @sohrabalmajose4082
    @sohrabalmajose4082 Před 4 měsíci

    what happen if I used reduced voltage starter and not direct on line?

  • @ryanvalendez1387
    @ryanvalendez1387 Před 3 lety +1

    Sir pwede mka hingi table and articles for electrical thks

  • @boybravo689
    @boybravo689 Před 2 lety +1

    Sir tanong ko lng kailan po inaaply ang power factor correction sa branch conductor ilang percent sir applicable ba sa single phase at three phase direct on line starter

    • @TagalogElectricaltips
      @TagalogElectricaltips  Před 2 lety

      ang power factor correction ay ginagamit hindi lng sa branch circuit kundi sa buong electrical system ng building. at least 0.85 ang ideal power factor, pero kung mas mataas sa 0.85 ang power factor ay nagbibigay ng discount sa electric bill ang power utility company. kapag mas mataas ang power factor mas malaki din ang discount. kaya yung ibang mga building owner ay nagiinvest para sa installation ng capacitor bank para sa power factor correction para maka avail ng electric bill discount

  • @marcelinojrdusarann6636
    @marcelinojrdusarann6636 Před 10 měsíci

    Sir paki gawa ng vedio ng gondola dalawang 3phase motor na sabay kasi yong gondola namin di sabay pag akyak ng motor ano kaya ang dahilan

  • @mannyregacho5349
    @mannyregacho5349 Před 10 měsíci

    #3.5 mm2 is protected by 40 at cb??

  • @roadtripnivan5590
    @roadtripnivan5590 Před rokem +1

    Good day sir paano naman po kung 30hp or higher na gumagamit ng wye delta ?

  • @boybravo689
    @boybravo689 Před 3 lety +2

    Sir ask ko lng pag sinabi na flc ay nagrerefer sa. Table ng nec pag nag set ka ng olp ay nagrerefer sa fla na kng saan un Yong nakalagay sa nameplate tama ba ako Sir tnx

  • @markmacatuno3218
    @markmacatuno3218 Před 4 měsíci

    3phase pero nasa 230 volts po?

  • @kalusugan6239
    @kalusugan6239 Před 3 lety +1

    Sir, kelan iaapply ung times 6 para sa starting motor? Anong rating ng mga motor ginagamitan ng times 6 sa breaker?

    • @TagalogElectricaltips
      @TagalogElectricaltips  Před 2 lety

      pag direct on line starter or full voltage starter, 6 times ng full load current ang starting current ng 3 phase motor

  • @virgo9424
    @virgo9424 Před 2 lety +1

    wala pa po bang 3 or more motors branch circuit calculation sir?

    • @TagalogElectricaltips
      @TagalogElectricaltips  Před 2 lety +1

      meron a po tyo video tutorial ng 2 or more motors branch cir uit calculation

  • @ianpaulgamayon4320
    @ianpaulgamayon4320 Před 2 lety

    Good day po sir!
    What if naka wye delta ang control ng motor sir pano po magcompute ng overload protection ng motor?
    Thanks po

    • @johnreymaliao3352
      @johnreymaliao3352 Před rokem

      Same lng lods, sa FLA prin mag ba base... Baka ung hinahanap nyo ay Amper ng high-low speed ?

  • @holypriljamesaxlhilario7467

    Yung aral na aral ka na. Tas lalabas mukha ni leni

  • @boyjuaquin5067
    @boyjuaquin5067 Před 6 měsíci

    single phase po at 3 phase parihas lang ang flc?😊

    • @TagalogElectricaltips
      @TagalogElectricaltips  Před 6 měsíci

      magkaiba ang flc ng 3 phase at single phase, mas mababa ang flc ng 3 phase

  • @damonyorgalvez1966
    @damonyorgalvez1966 Před 3 lety +1

    Sir meron ako na-encounter na motor ang input voltage nya na nakalagay ay 380v ano po ang i-consider ko na column 400v o 460v

  • @dynielpagdanganan4260
    @dynielpagdanganan4260 Před 3 lety +1

    Sir paano po mag multiple motors? Salamat.

  • @mathworkph9706
    @mathworkph9706 Před 3 lety

    Tanong lang po sir. Dba dpat po mas mataas ang ampacity rating ng conductor kasya sa protection device??

    • @TagalogElectricaltips
      @TagalogElectricaltips  Před 3 lety +1

      Hindi nman kailangan n ganun. Depende kasi sq clculation. Lalo n pag motor loads mas mataas ang circuit breaker n binibigay ng calculation

    • @mhelvinmanalo3140
      @mhelvinmanalo3140 Před 3 lety

      Yon din tanong ko sir,kasi baka sunog na yong wire tapos di pa nagtritrip ang cb.Meron po ako dinownload app nong nilagay ko yong mga value ,lumabas po na 20 ampere lang cb nya.

    • @gabrielperez-lk9cf
      @gabrielperez-lk9cf Před 2 lety

      Yes tama ka.. mas maganda na mas mataas ang ampacity ni wire sa breaker.. dahil sa PEC minimum lang naman ang 125% na binigay nya sa pag size ng wire, so pwede mo sya taasan . Mas maganda ay equal sa ampacity ni breaker or mas mataas kay breaker na ampacity. Uulitin ko minimum lang ang binigay ni pec so pwedeng taasan.. at yung circuit breaker na 250% maximum na yan pwede mo sya babaan .. yun lang

  • @bloomberg4865
    @bloomberg4865 Před 3 lety

    Master lahat ba ng motor except sa aircon at firepump kpg kukuha ng ocpd ay nka based sa table na mai 2.5 itcb ,1.75 etc ?