Differential protection

Sdílet
Vložit
  • čas přidán 8. 07. 2018
  • This video outlines the basic principles behind differential protection and is a sample of the full 2.5 long ELECTRICAL CONTROL AND PROTECTION PART 3 available on UDEMY, use the following link to access the course..
    www.udemy.com/course/electric...
    If you need a $10 discount voucher please drop me a message!!
  • Věda a technologie

Komentáře • 71

  • @TheNameWithNoNumbers
    @TheNameWithNoNumbers Před 5 měsíci +2

    Stephen's knowledge, delivery, and production quality are superb.

  • @michaelkolade9102
    @michaelkolade9102 Před 5 lety +4

    Very brief and straight to the point. Thanks

  • @mohamedibrahimhussein3007

    Thanks, it is perfect explanation and I appreciate ur skill

  • @Ryan-nh8ef
    @Ryan-nh8ef Před 2 lety +4

    These videos on your channel are amazing, I can’t believe its taken so long to find them! Outstanding effort and the information is unreal. This will help me in my future development and understanding of the theory behind the UK network. I’m hoping to gain a trainee engineer position, so this information is perfect!

  • @estudent-vm7fi
    @estudent-vm7fi Před 7 měsíci

    Man, you are good!
    Please understand that, you are legend.
    Just the way you start from the very bottom and cover everything up to the top is the only way I can understand.

  • @atanquerel
    @atanquerel Před 5 lety +1

    Really useful video thanks

  • @velmurugant2653
    @velmurugant2653 Před 5 lety +1

    Useful video

  • @coltonbutts96
    @coltonbutts96 Před 5 lety +1

    Excellent video!

    • @Electricalsteve
      @Electricalsteve  Před 3 lety

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @lalitjoshi7152
    @lalitjoshi7152 Před 5 lety +1

    Exact explanation... Thankyou

    • @Electricalsteve
      @Electricalsteve  Před 3 lety

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @a.b.m.mesbahuddinahmed3006

    Very good explanation with clear concepts.

  • @Ranjithsriram
    @Ranjithsriram Před 3 lety

    Thank u sir...I can imagine it

  • @SolarEMPSOLUTIONS
    @SolarEMPSOLUTIONS Před rokem

    Ur guide Great 👍

  • @SolarEMPSOLUTIONS
    @SolarEMPSOLUTIONS Před rokem

    Very thankful

  • @AhmedKhan-cm8kr
    @AhmedKhan-cm8kr Před 4 lety

    Very good explained

  • @electricaltech4u45
    @electricaltech4u45 Před 5 lety

    V nice bro

  • @farmaz7667
    @farmaz7667 Před 5 lety

    Good explaine.

  • @AminulIslam-we3kd
    @AminulIslam-we3kd Před 2 lety

    Thanks for the post of your videos regarding differential relays. Please explain how calculate matching transformer ratings for 10 MVA transformer connected to 66/11 line.CTs of 200/5 amp and 600/5amp in high side and low side respectively.

    • @Electricalsteve
      @Electricalsteve  Před 2 lety +1

      Hi Aminul, this subject is not covered on this video steve

  • @saeedahmed4651
    @saeedahmed4651 Před rokem

    amazing videos...

  • @ajugarasiya7546
    @ajugarasiya7546 Před 4 lety +2

    Sir transformer protection video please

  • @mayito714
    @mayito714 Před rokem

    I think I would have uderstood this better with a simple single Station Transformer. The later single buss example was the only one I grasped.

  • @jungwanson3166
    @jungwanson3166 Před 3 lety

    Excellent

  • @mahingajjar6059
    @mahingajjar6059 Před 5 lety

    thanks sir

  • @Boldaslove71
    @Boldaslove71 Před 6 měsíci

    I wonder if it is an ANSI vs. IEC thing, but normally in ANSI we would have the CT's on the opposite side of the breakers, as shown. This was the breakers at each end are protected by the differential protection. In the scheme as shown, either breaker could fail and would need some other protection scheme to sense the fault.

    • @Electricalsteve
      @Electricalsteve  Před 6 měsíci

      Hi, it’s not really an ANSI/IEC conflict, most utilities only have one set of current transformers on the line side now to save money and use other protection functions to detect a fault in between the CT / circuit breaker ( short stub fault ).
      Steve

    • @Boldaslove71
      @Boldaslove71 Před 6 měsíci

      @@Electricalsteve Maybe it's a regional thing. I commission HV substations, including the apparatus outside and the protection systems inside the control house. Our standard new dead tank circuit breakers have a total of 18 CT's per breaker. For a line breaker the bus side CT's are used for primary and secondary line protection and the line side CT's are for primary / secondary bus protection. Having the diff CT's on line side ensures the breaker itself is covered in the diff scheme. In a ring or breaker and a half scheme, it may be a little different. One last set of CT's may be used for breaker failure protection and the last may be for revenue metering. We have older installations that don't have as many CT's (we call CT deficient), but that can cause issues down the line - shared CT circuits and someone does maintenance test with doble -plugs paddle in while connected to doble and shorts diff relay and a nuisance trip. I believe for the relative low cost of additional CT's on a dead tank, many utilities choose to have the extra CT's for flexibility and ease of wiring and maintenance. Digital relays also help quite a bit if sharing CT's as the polarity can be adjusted internally in the relay for compensate.

  • @ELECTRICALFUNDAZ
    @ELECTRICALFUNDAZ Před 5 lety +1

    Hi sir. Which software you use for making such videos?

    • @Electricalsteve
      @Electricalsteve  Před 5 lety

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WETT1001 to get them for $9.99
      Regards
      Stephen Brooks

  • @billyambotane5761
    @billyambotane5761 Před rokem

    May I be enlightened of a high line fault current not being detected by relay to send trip signal to line cb to operate however sensed by generator differential protection and trip the generators.I presume the line line distance protection requires to be reset cater for large fault. currents.

  • @kiamick
    @kiamick Před 4 lety +4

    Stephen you videos are brilliant. I was following this one quite well up until you had an in-zone fault on your feeder that's fed from both ends A & B. The current rises on both CTs as expected and is balanced according to your ammeter animations (2000A). Yet it still trips both breakers on imbalance. It has something to do with the backwards current i presume but don't quite understand why. Can CTs sense direction?

    • @Electricalsteve
      @Electricalsteve  Před 4 lety +2

      Hi Michael,
      The CT will measure current in both directions, the relay is set up to operate when the current is in either the forward or reverse direction to make it possible to identify the fault locations, please refer to the full Udemy protection course for details.
      Regards
      steve

    • @kiamick
      @kiamick Před 4 lety +1

      @@Electricalsteve Steve thanks for the reply. I purchased about 70 quids worth of courses a few weeks ago. I think all of them except 1 that you had available.
      I would really love to have the option to ask you more questions as and when they arise throughout this course. Can I leave you my email and you send me a message so there is always the option for help? I would really appreciate it and I'll tell you more about what I do for a living and how your knowledge will help me develop.
      Thank you

    • @ibrahimhassame8859
      @ibrahimhassame8859 Před 2 lety

      Good

  • @surendrakverma555
    @surendrakverma555 Před 3 lety

    Very good

  • @youssefayman7513
    @youssefayman7513 Před 3 měsíci

    Thank u ❤❤❤

  • @jamesbarber8012
    @jamesbarber8012 Před rokem +1

    Hi Stephen, great videos, well presented and spoken. QQ, do you have any voucher codes so i can start doing these in full on udemy?

    • @Electricalsteve
      @Electricalsteve  Před rokem

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @VinodPrajapati-sb4ho
    @VinodPrajapati-sb4ho Před 3 lety +2

    Thank you sir 😊

    • @Electricalsteve
      @Electricalsteve  Před 3 lety +1

      Most welcome

    • @VinodPrajapati-sb4ho
      @VinodPrajapati-sb4ho Před 3 lety +1

      Sir please
      Explain - Schneider micom relay
      P125
      P222
      All functions...

    • @Electricalsteve
      @Electricalsteve  Před 3 lety +1

      Hi Vinod, the full protection courses on Udemy explain all of the functions in detail steve

    • @VinodPrajapati-sb4ho
      @VinodPrajapati-sb4ho Před 3 lety

      @@Electricalsteve ok sir thank you
      Please suggest link

    • @Electricalsteve
      @Electricalsteve  Před 3 lety +1

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @user-nr5qc6rq1z
    @user-nr5qc6rq1z Před 2 lety

    Thanks

  • @farzanals9701
    @farzanals9701 Před 4 lety +1

    Hai sir, can you please make the vedio lecture on frame leakage protection of busbars & carrier current protection of transmission lines(power system protection) as soon as possible sir.
    Thanking you sir.

    • @Electricalsteve
      @Electricalsteve  Před 3 lety

      Thanks for the suggestions...will see what I can do. steve

  • @subhambhardwaj7329
    @subhambhardwaj7329 Před 3 lety

    Sir please may i know why there was no damage to the equipment in through fault?
    as an overcurrent is already passing through it

    • @Electricalsteve
      @Electricalsteve  Před 3 lety +1

      Hi Subham, Equipment used on electrical networks is designed to carry fault current for a certain time period, normally 1 second or 3 second dependant on the application. This allows time for the protection systems to detect the fault and open the circuit breakers, clearing the fault from the network
      steve

  • @noicyop2142
    @noicyop2142 Před 3 lety +1

    Ohhhh

  • @aryanraiqal2294
    @aryanraiqal2294 Před 12 dny

    sir can u explain by video what happen if we use different class for overhead line..substation A using CT class X..but another remote end substation using CT class 5P20..what happen if fault occured..??

    • @Electricalsteve
      @Electricalsteve  Před 10 dny

      Hi,
      The 5P20 CT’s will be less accurate than the class X CT’s, this will become clear if you have a high current fault and the relays at the two ends will show different current levels, this difference may in incorrectly identify a fault on the line being protected.
      Regards
      Steve

    • @aryanraiqal2294
      @aryanraiqal2294 Před 10 dny

      @@Electricalsteve tq steve..👍