stephen brooks
stephen brooks
  • 107
  • 777 313
Wenner test
This video is a sample of the full 2.5 Hour long course available on Udemy, published by Stephen Brooks
Here is the link to access it below
www.udemy.com/course/substation-grounding-1/?referralCode=36FCCAD6DD94B1722DE1
zhlédnutí: 635

Video

Tolerable step potential
zhlédnutí 426Před 8 měsíci
This video is a sample of the full 2.5 Hour long course available on Udemy, published by Stephen Brooks Here is the link to access it below www.udemy.com/course/substation-grounding-1/?referralCode=36FCCAD6DD94B1722DE1
Ground potential rise
zhlédnutí 2,7KPřed 8 měsíci
This video is a sample of the full 2.5 Hour long course available on Udemy, published by Stephen Brooks Here is the link to access it below www.udemy.com/course/substation-grounding-1/?referralCode=36FCCAD6DD94B1722DE1
Grid resistance calculation
zhlédnutí 507Před 8 měsíci
This video is a sample of the full 2.5 Hour long course available on Udemy, published by Stephen Brooks Here is the link below www.udemy.com/course/substation-grounding-1/?referralCode=36FCCAD6DD94B1722DE1
Fall of potential test
zhlédnutí 856Před 8 měsíci
This video is a sample of the full 2.5 Hour long course available on Udemy, published by Stephen Brooks Here is the link below www.udemy.com/course/substation-grounding-1/?referralCode=36FCCAD6DD94B1722DE1
Transformer impedance
zhlédnutí 787Před 8 měsíci
This is a sample of the full 2.5 hour course which is available on Udemy, published under my name Stephen Brooks Use the link below to access... www.udemy.com/course/substation-grounding-1/?referralCode=36FCCAD6DD94B1722DE1
Substation grounding course
zhlédnutí 943Před 8 měsíci
A sample of the full 2.5 hour long course on Udemy..search for my name Stephen Brooks to see all of the courses available Link below www.udemy.com/course/substation-grounding-1/?referralCode=36FCCAD6DD94B1722DE1
Substation DC Room Layout
zhlédnutí 706Před rokem
This is an excerpt from the air insulated substation design part 3 course covering control cabling, panels, interlocking, DC systems, current transformers and voltage transformers The full course is available on UDEMY via the following link.. www.udemy.com/course/air-insulated-substation-design-part-3/?referralCode=91A5476641EC84979CB8
Cable measurement
zhlédnutí 469Před rokem
This is an excerpt from the air insulated substation design part 3 course covering control cabling, panels, interlocking, DC systems, current transformers and voltage transformers The full course is available on UDEMY via the following link.. www.udemy.com/course/air-insulated-substation-design-part-3/?referralCode=91A5476641EC84979CB8
Control room layout
zhlédnutí 938Před rokem
This is an excerpt from the air insulated substation design part 3 course covering control cabling, panels, interlocking, DC systems, current transformers and voltage transformers The full course is available on UDEMY via the following link.. www.udemy.com/course/air-insulated-substation-design-part-3/?referralCode=91A5476641EC84979CB8
Substation Cable Tray
zhlédnutí 466Před rokem
This is an excerpt from the air insulated substation design part 3 course covering control cabling, panels, interlocking, DC systems, current transformers and voltage transformers The full course is available on UDEMY via the following link.. www.udemy.com/course/air-insulated-substation-design-part-3/?referralCode=91A5476641EC84979CB8
Air Insulated Substation Design Part 3
zhlédnutí 453Před rokem
This is the third part of the air insulated substation design course covering control cabling, panels, interlocking, DC systems, current transformers and voltage transformers The full course is available on UDEMY via the following link.. www.udemy.com/course/air-insulated-substation-design-part-3/?referralCode=91A5476641EC84979CB8
Transformer Offloading
zhlédnutí 2,6KPřed 2 lety
This video shows how a power transformer can be offloaded onto the transformer foundation using jacks. This is a sample of the full Udemy course, use this link to access.. www.udemy.com/course/air-insulated-substation-design-part-2/?referralCode=46A3615DD3630A810DB7
Air Insulated Substation Design Part 2
zhlédnutí 849Před 2 lety
This is the second part of the air insulated substation design course covering transformer design, installation and delivery, interlocking, primary plant numbering and RMU's The full course is available on UDEMY via the following link.. www.udemy.com/course/air-insulated-substation-design-part-2/?referralCode=46A3615DD3630A810DB7
Substation control and protection part 5
zhlédnutí 9KPřed 4 lety
This video is a summary of the new 3 hour long protection and control course available on the Udemy online university platform, use the following link to access the course... www.udemy.com/course/electrical-control-and-protection-part-5/?referralCode=6E46F874F743140059D2 If you need a $10 discount voucher please drop me a message!!!
Impedance protection blocking scheme
zhlédnutí 2,1KPřed 4 lety
Impedance protection blocking scheme
Impedance protection acceleration scheme
zhlédnutí 894Před 4 lety
Impedance protection acceleration scheme
Impedance protection two ended scheme
zhlédnutí 1,2KPřed 4 lety
Impedance protection two ended scheme
Impedance protection reach definition
zhlédnutí 4KPřed 4 lety
Impedance protection reach definition
Pilot isolation transformers
zhlédnutí 1,3KPřed 4 lety
Pilot isolation transformers
Pilot wire differential protection
zhlédnutí 11KPřed 4 lety
Pilot wire differential protection
Diameter substation protection zones
zhlédnutí 965Před 4 lety
Diameter substation protection zones
Double busbar substation protection zones
zhlédnutí 3,3KPřed 4 lety
Double busbar substation protection zones
Single busbar substation interlocking
zhlédnutí 1,3KPřed 4 lety
Single busbar substation interlocking
Interlocking logic
zhlédnutí 3,9KPřed 5 lety
Interlocking logic
Meter locations
zhlédnutí 1,2KPřed 5 lety
Meter locations
Power factor compensation
zhlédnutí 2,6KPřed 5 lety
Power factor compensation
Relay flags
zhlédnutí 3,4KPřed 5 lety
Relay flags
Fault clearance time
zhlédnutí 6KPřed 5 lety
Fault clearance time
Mechanical interlocking
zhlédnutí 6KPřed 5 lety
Mechanical interlocking

Komentáře

  • @synapticmemoryseepage4447

    Awesome! Great explanation.

  • @synapticmemoryseepage4447

    Wow, fantastic explanation in such a short interval!

  • @xxxBradTxxx
    @xxxBradTxxx Před 19 dny

    Hey, I've watched your stuff on Udemy

  • @awesomeelectricalengineer3487

    So before I buy your course, what about split factor? Is there a reason why you're assuming all the fault current returns via the earth grid at the substation? Thanks

    • @Electricalsteve
      @Electricalsteve Před 23 dny

      Hi, We cover the current division factor in the course. Regards Steve

  • @aryanraiqal2294
    @aryanraiqal2294 Před 25 dny

    sir can u explain by video what happen if we use different class for overhead line..substation A using CT class X..but another remote end substation using CT class 5P20..what happen if fault occured..??

    • @Electricalsteve
      @Electricalsteve Před 23 dny

      Hi, The 5P20 CT’s will be less accurate than the class X CT’s, this will become clear if you have a high current fault and the relays at the two ends will show different current levels, this difference may in incorrectly identify a fault on the line being protected. Regards Steve

    • @aryanraiqal2294
      @aryanraiqal2294 Před 23 dny

      @@Electricalsteve tq steve..👍

  • @alimanaal-atefi3622
    @alimanaal-atefi3622 Před 26 dny

    thanks alot 👩‍🎓👍❤🙋‍♀️

  • @hpvide
    @hpvide Před 2 měsíci

    Wow 😳.. thank you so much

  • @engalaamenshawy5377
    @engalaamenshawy5377 Před 2 měsíci

    wow!! very very nice not teacher but you are doctor congratulation.

  • @alimanaal-atefi3622
    @alimanaal-atefi3622 Před 2 měsíci

    🙋‍♂️💟💟🙋‍♀️👍

  • @Tom-nj3ru
    @Tom-nj3ru Před 2 měsíci

    How can i buy all your protection and control video, at once, not part by part

    • @Electricalsteve
      @Electricalsteve Před 2 měsíci

      Hi Tom, unfortunately that’s not an option on Udemy, you need to pay for each course separately. Regards Steve

  • @kevinbreslin5718
    @kevinbreslin5718 Před 3 měsíci

    Wouldn't the sheath be energized up to the receiving station

    • @Electricalsteve
      @Electricalsteve Před 2 měsíci

      Hi Kevin, at several cable joints along the route we ground the sheath with a non linear resistor to keep the induced voltage down to an acceptable level. steve

  • @arishsiddiqui3292
    @arishsiddiqui3292 Před 3 měsíci

    Thank you Sir. You illustrations and explanations have helped me understand so many concepts. Appreciate it!

  • @user-mu2qu8uo4z
    @user-mu2qu8uo4z Před 3 měsíci

    Awesome as usual

  • @ninojamescagat9780
    @ninojamescagat9780 Před 3 měsíci

    Good day Sir, can you give me some advise what books should i read to understand the field of power system protection. Thank you Sir Have a nice day

    • @Electricalsteve
      @Electricalsteve Před 3 měsíci

      Hi Nino, I would suggest looking at the free CZcams videos to give you an introduction, if your interested do the full Udemy courses to give you in depth knowledge. Regards Steve

  • @youssefayman7513
    @youssefayman7513 Před 4 měsíci

    Thank u ❤❤❤

  • @tintinfan007
    @tintinfan007 Před 4 měsíci

    Must watch

  • @user-cc6jy9zm7x
    @user-cc6jy9zm7x Před 4 měsíci

    Good from thailand❤

  • @user-cc6jy9zm7x
    @user-cc6jy9zm7x Před 4 měsíci

    Good from thailand❤

  • @RyanMcCusker
    @RyanMcCusker Před 5 měsíci

    Hi Stephen, is this course still available ? Do you know if there are any discounts on courses?

    • @Electricalsteve
      @Electricalsteve Před 4 měsíci

      Hi Ryan, Use the voucher code TWHD1001 to get the following Udemy courses for $9.99…. ELECTRICAL CONTROL & PROTECTION SYSTEMS ELECTRICAL CONTROL & PROTECTION SYSTEMS PART 2 ELECTRICAL CONTROL & PROTECTION SYSTEMS PART 3 ELECTRICAL CONTROL & PROTECTION SYSTEMS PART 4 ELECTRICAL CONTROL & PROTECTION SYSTEMS PART 5 AIR INSULATED SUBSTATION DESIGN AIR INSULATED SUBSTATION DESIGN PART 2 AIR INSULATED SUBSTATION DESIGN PART 3 SUBSTATION GROUNDING ELECTRICAL POWER EQUIPMENT ELECTRICAL POWER ENGINEERING CONSTRUCTION SITE ELECTRICAL SYSTEM DESIGN COUPONS ONLY VALID UNTIL THE 3rd March 2024 Regards steve

  • @gaddevishnuvardhan5227
    @gaddevishnuvardhan5227 Před 5 měsíci

    Great Information 👍

  • @pratibhaprajapati7984
    @pratibhaprajapati7984 Před 5 měsíci

    if for longer period the step voltage applied is less....then how person is in more dangerous position in less voltage......pl guide

  • @shanu3588
    @shanu3588 Před 5 měsíci

    In RYB star connection...if r phase is grounded...then other phase voltage will be equal line voltage.....is it correct?

  • @TheNameWithNoNumbers
    @TheNameWithNoNumbers Před 5 měsíci

    Stephen's knowledge, delivery, and production quality are superb.

  • @Ryan-nh8ef
    @Ryan-nh8ef Před 5 měsíci

    Hi Stephen, thank you for making the videos, is there a discount code for the online courses? I’m looking to purchase them in bulk if possible.

  • @pacificlite
    @pacificlite Před 5 měsíci

    Awesome video!

  • @IEPBrasilia-Marco_Oliveira
    @IEPBrasilia-Marco_Oliveira Před 5 měsíci

    Hello, any recommendations for an application to calculate the NH Fuse Melting Time?

  • @30mAkills
    @30mAkills Před 5 měsíci

    Useful tutorial

  • @andrewcarper9970
    @andrewcarper9970 Před 5 měsíci

    I appreciate your walkthrough Stephen. I am studying for the PE (power) exam and this helped me tremendously. One thing I want to add is the formula you referenced is only applicable for grids with depths between 0.25 - 2.5m. However, the concepts remain the same and all formulas are provided by NCEES. Thank you again!

  • @pietervdberg7055
    @pietervdberg7055 Před 6 měsíci

    Thanks for the formula and explanation. Will the shape of the earth system conductor play a roll in the Value of Rg. A rectangular bar will have a larger circumference and more contact area with ground than a round conductor.

  • @JOANHILLA
    @JOANHILLA Před 6 měsíci

    Compre curso substation grounding y ahora no puedo entrar.

  • @Boldaslove71
    @Boldaslove71 Před 6 měsíci

    I wonder if it is an ANSI vs. IEC thing, but normally in ANSI we would have the CT's on the opposite side of the breakers, as shown. This was the breakers at each end are protected by the differential protection. In the scheme as shown, either breaker could fail and would need some other protection scheme to sense the fault.

    • @Electricalsteve
      @Electricalsteve Před 6 měsíci

      Hi, it’s not really an ANSI/IEC conflict, most utilities only have one set of current transformers on the line side now to save money and use other protection functions to detect a fault in between the CT / circuit breaker ( short stub fault ). Steve

    • @Boldaslove71
      @Boldaslove71 Před 6 měsíci

      @@Electricalsteve Maybe it's a regional thing. I commission HV substations, including the apparatus outside and the protection systems inside the control house. Our standard new dead tank circuit breakers have a total of 18 CT's per breaker. For a line breaker the bus side CT's are used for primary and secondary line protection and the line side CT's are for primary / secondary bus protection. Having the diff CT's on line side ensures the breaker itself is covered in the diff scheme. In a ring or breaker and a half scheme, it may be a little different. One last set of CT's may be used for breaker failure protection and the last may be for revenue metering. We have older installations that don't have as many CT's (we call CT deficient), but that can cause issues down the line - shared CT circuits and someone does maintenance test with doble -plugs paddle in while connected to doble and shorts diff relay and a nuisance trip. I believe for the relative low cost of additional CT's on a dead tank, many utilities choose to have the extra CT's for flexibility and ease of wiring and maintenance. Digital relays also help quite a bit if sharing CT's as the polarity can be adjusted internally in the relay for compensate.

  • @rkprasadbhookya1878
    @rkprasadbhookya1878 Před 7 měsíci

    Superb trick

  • @abbasdairawy390
    @abbasdairawy390 Před 7 měsíci

    thank you

  • @estudent-vm7fi
    @estudent-vm7fi Před 8 měsíci

    Man, you are good! Please understand that, you are legend. Just the way you start from the very bottom and cover everything up to the top is the only way I can understand.

  • @thesilentgamer4210
    @thesilentgamer4210 Před 8 měsíci

    sir, do you know how to size cable for transformer neutral earthing? my transformer is delta y. 3MVA 33KV / 415 V.. I hope you can help me sir

  • @Ehobbs10
    @Ehobbs10 Před 8 měsíci

    Hi Stephen please can you send me a 9.99 voucher code. Thanks

  • @muhammadsuleiman7806
    @muhammadsuleiman7806 Před 8 měsíci

    I NEED THE VOUCHER, SIR,

    • @Electricalsteve
      @Electricalsteve Před 8 měsíci

      Hi Muhammad , To use the attached coupon code go to the Udemy website, register, search for the course / my name ( Stephen Brooks ) then select the course you want and enter the $9.99 voucher code UHEK1001 Regards steve

  • @WarwickChapman
    @WarwickChapman Před 9 měsíci

    Does the course cover DC busbar sizing?

  • @sambathbunkh
    @sambathbunkh Před 9 měsíci

    Great topic

  • @anujdubey4367
    @anujdubey4367 Před 9 měsíci

    What if the generator is impedance grounded like neutral point is having a NGT?

  • @bicunisa
    @bicunisa Před 9 měsíci

    Wave cycles that occur every second, not every minute.

  • @vanlahm4728
    @vanlahm4728 Před 10 měsíci

    Hi Sir. Just a quick question. The busbar rating for the current is multiplied by 3. But why is the voltage not mulplied by 3 also?

    • @Electricalsteve
      @Electricalsteve Před 10 měsíci

      Hi, The system voltage is kept constant regardless of the power output of the transformers or the size of the loads. If the voltage is constant then the only thing that can change as the power magnitude changes is the current and it does, when the power drawn by the load increases the current increases. Regards Steve

  • @kennethchiebuka5168
    @kennethchiebuka5168 Před 10 měsíci

    Wow!! You are indeed a legend in the power sector and a great teacher too.

    • @Electricalsteve
      @Electricalsteve Před 10 měsíci

      Thanks for the kind words Kenneth, glad you found the course useful!! Steve

  • @vipulwadkar8502
    @vipulwadkar8502 Před 10 měsíci

    Informative 👍

  • @ipyanakasanga936
    @ipyanakasanga936 Před 10 měsíci

    Excellent explanation

  • @zaidshahab7196
    @zaidshahab7196 Před rokem

    i need discount

    • @Electricalsteve
      @Electricalsteve Před 11 měsíci

      Hi Zaid Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code IGST1001 to get them for $9.99, vouchers expire in 5 days. Regards Stephen Brooks

  • @dileepana6637
    @dileepana6637 Před rokem

    Power cables have a more bending radius then control cables

    • @Electricalsteve
      @Electricalsteve Před rokem

      Hi, Every cable has its own unique bending radius defined by the manufacturer. steve

  • @danielmlynarz8900
    @danielmlynarz8900 Před rokem

    Hi Stephen, could you please write me your email address? I need it in relation to the Udemy voucher. Thank you in advance.

    • @Electricalsteve
      @Electricalsteve Před rokem

      Hi Daniel Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code IGST1001 to get them for $9.99, vouchers expire in 5 days. Regards Stephen Brooks

    • @danielmlynarz8900
      @danielmlynarz8900 Před rokem

      @@Electricalsteve Thank you, purchased.

  • @osmansafi1972
    @osmansafi1972 Před rokem

    Sir, what about the electrical room in which main panel (floor mounted) of the building are installed. half meter distance is enough from the wall for future maintenacne?

    • @Electricalsteve
      @Electricalsteve Před rokem

      Hi Osman, I recommend 1.5 meters in the video, but the actual distance will depend on your circumstances….as a minimum you need to be able to walk between the opened panel door and wall…Steve

  • @archive9994
    @archive9994 Před rokem

    Interesting