  • The factors that affect the speed and efficiency of evacuation are; size of equipment being
    evacuated, ambient temperature, amount of moisture in the system, the size of the vacuum
    pump and vacuum lines, Figures 10 & 11. In addition, vacuum lines (hoses) should be equal
    to or larger than the pump intake connection. The brand of a micron gauge does not usually
    affect the speed of evacuation, but the method used to connect it to the system may. The
    piping connection to the vacuum pump should be as short in length as possible and as large
    in diameter as possible. For accurate readings during evacuation, the system vacuum gauge
    should be connected as far away from the vacuum pump as possible. Measuring a final
    system vacuum should be done with the system isolated and the vacuum pump turned off. A
    system that will not hold a vacuum after it has been evacuated probably has a leak. During
    evacuation, you may wish to heat the refrigeration system to decrease dehydration time.
    Tapping a compressor with a rubber mallet will aid in releasing trapped refrigerant from the oil.
    Buy course
    airconacademy....
    Our website
    www.airconacad...
    #hvac #hvactraining #hvacschool #hvacairsystem #hvactrainingvideos #cfc #hvaccertification #epa608

Komentáře • 7

  • @kennethlobo4420
    @kennethlobo4420 Před 2 měsíci +1

    Nice to have you back Sir.looking forward to your videos

    • @AirConAcademy
      @AirConAcademy  Před 2 měsíci

      Thank you I hope to get more things going here!!! thank you for watching!!!!

  • @moustaphamuhammad7013
    @moustaphamuhammad7013 Před 2 měsíci +2

    welcome, back I have been waiting for your amazing videos!

    • @AirConAcademy
      @AirConAcademy  Před 2 měsíci +1

      Thank you so much for your kind words! I have just been so busy teaching that it's difficult to do everything I want to do. Thank you for watching!

  • @mohdzaidqureshi5917
    @mohdzaidqureshi5917 Před 2 měsíci +2

    Sir please make a video inverter technology

    • @AirConAcademy
      @AirConAcademy  Před 2 měsíci

      Thank you for your suggestion! I have been very busy, but I do write the suggestions down and I hope to make a video on this soon. And any other suggestions please let me know. Thank you for watching!

    • @mohdzaidqureshi5917
      @mohdzaidqureshi5917 Před 2 měsíci

      Sir please make video all inverter air conditioner troubleshooting and fault finding for example less refrigerant symptom and all sensor working of incerter air conditioner 😊please please please