Trane CVHE Chiller Surging

Sdílet
Vložit
  • čas přidán 5. 10. 2018
  • Here the chiller is surging due to air being sucked in on this low pressure chiller.

Komentáře • 18

  • @davidperry4013
    @davidperry4013 Před rokem +1

    You don’t want to hurt that poor old chiller with all that surge. That thing has got to last 50 years. My favorite water cooled centrifugal chillers to schedule on Mechanical drawings as an MEP engineer is the Trane Centravac.

  • @YungHVAC
    @YungHVAC Před 4 lety +1

    Yoooooo I wouldn’t know what the hell to do haha . That’s some heavy equipment!!

    • @SombraLocs
      @SombraLocs  Před 4 lety +1

      Yung HVAC There is so much to learn in this trade.

  • @JumpermanTech
    @JumpermanTech Před 5 lety +1

    Sounds like demons inside

  • @martinsalmeron7428
    @martinsalmeron7428 Před 3 lety +2

    Keep uploading videos man

    • @SombraLocs
      @SombraLocs  Před 3 lety

      I will, I just don't know what type of videos to upload. Seems like theres multiple videos of the same thing out there.

  • @patrickgarcia3027
    @patrickgarcia3027 Před 5 lety

    When you went back the next day, was all the air out? Or did it take a bit longer?

    • @SombraLocs
      @SombraLocs  Před 5 lety

      Yes, I let the purge run all day and the next day all the air was out. It had a low side leak. It would only suck up most of the air while the machine was off. The purge unit was in auto, so it would only pump out when the chiller was running.

    • @patrickgarcia3027
      @patrickgarcia3027 Před 5 lety

      Can you give me more details on the purge unit and why you have the restrictor bypassed? We have a CVHF770 that had a leak, we repaired the leak, but we put the contaminated R-123 back in the machine. So your video helped out a bunch but I'm just curious as to how to get non-condensables out of the system now. Thanks again!

    • @SombraLocs
      @SombraLocs  Před 5 lety +1

      I bypassed the Restrictor to accelerate the removal of non condensables. I also disabled Max Pumpout Alarm for 72 hrs to let the Purge get all the air out.

  • @wd8557
    @wd8557 Před 3 lety

    Learn what chiller surge is before you start making videos.

    • @SombraLocs
      @SombraLocs  Před 3 lety +4

      You make a video and show us.

    • @wd8557
      @wd8557 Před 3 lety

      @@SombraLocs I don't have to I know what it is. I don't walk up to a system and say stupid shit like it's surging because their is air in the system. LMAOOOOOOOO

    • @SombraLocs
      @SombraLocs  Před 3 lety +5

      @@wd8557 I didn't say it only surges when theres air. Go ahead make a video, show us. Let's see your knowledge.