Temperzone / Split Ducted System not Cooling

Sdílet
Vložit
  • čas přidán 26. 10. 2023
  • Service call for a Temperzone slot ducted unit not cooling the space.

Komentáře • 12

  • @liamsaliba96
    @liamsaliba96 Před 9 měsíci +1

    Temperzone really do overkill the screws ey, good work legend

  • @Cre666in666
    @Cre666in666 Před 9 měsíci

    Good video man thanks for explaining how the unit monitors and triggers high discharge superheat

  • @jpenn727
    @jpenn727 Před 9 měsíci

    Great video, thanks!

  • @VoiD1x
    @VoiD1x Před 3 měsíci +1

    Draw system looks mint! What brand is it?

    • @hvacraustralia
      @hvacraustralia  Před 3 měsíci

      The company that made the service body and draws is ezToolBox Melbourne. They’re a little rough around the edges but it’s a handy setup compared to what we had previously.

  • @Thermoelectric7
    @Thermoelectric7 Před 9 měsíci

    I did a PM on a few massive heatpumps servicing the hot water for some student accommodation yesterday. Found one circuit was running lower discharge temps, higher EEV position and had a flashing sight glass compared to all the other circuits.
    I'm going to have to go look at my readings now, sounds like discharge temp should go up not down on a low charge, where condensing pressures are similar. Interesting!

    • @hvacraustralia
      @hvacraustralia  Před 9 měsíci

      Discharge temps go higher when low on refrigerant because there is less cooling coming back to the comp so the motor runs hotter. If you have an EEV that’s open more than you think it should be, a flashing sight glass and low discharge temps you could be flooding back due to a suction sensor that’s reading out.

  • @bradroesler7072
    @bradroesler7072 Před 5 měsíci

    Why haven't you been uploading any vids lately?

    • @hvacraustralia
      @hvacraustralia  Před 5 měsíci

      I started a new job for a manufacturer and they’re a little more stringent on me filming. Hopefully I’ll get some more out at some point 🤞