Trane Commercial Package Unit ….8.5 Ton THC102 Not Cooling

Sdílet
Vložit
  • čas přidán 20. 08. 2024
  • Troubleshooting a call for No cooling on a Trane 8.5 ton package unit 3 phase 208/230 volt

Komentáře • 24

  • @Freeagent-z7l
    @Freeagent-z7l Před rokem +2

    I worked on Trane equipment for 24yrs in Trinidad and Tobago with our local dealer comfort engineering ltd.. learnt alot whilst there

  • @MariosACandRefrigeration

    condenser motor sounds rough,thanks for sharing,nice fix.

    • @subcoolHVAC
      @subcoolHVAC  Před rokem

      Thanks, that unit has seen better days for sure.

  • @zekenzy6486
    @zekenzy6486 Před 4 měsíci

    Nice Work and Good Job. Thank you for sharing

  • @jessemayra
    @jessemayra Před rokem +2

    Good work

  • @stevencarrillo3615
    @stevencarrillo3615 Před rokem +2

    Learned something thanks

    • @subcoolHVAC
      @subcoolHVAC  Před rokem

      Thanks for watching, always learning myself

  • @gabrielchiu2650
    @gabrielchiu2650 Před rokem +2

    that poor trane seems to been neglected

    • @subcoolHVAC
      @subcoolHVAC  Před rokem +1

      Unfortunately it only gets attention when it stops cooling.

  • @eramirez5763
    @eramirez5763 Před rokem +2

    That coil should’ve been split and chemically cleaned

    • @subcoolHVAC
      @subcoolHVAC  Před rokem +1

      Scheduled at later date, had to move on. Thanks for watching!

  • @danielarteaga3913
    @danielarteaga3913 Před rokem +2

    Good video

  • @Joshuatimmons1783
    @Joshuatimmons1783 Před rokem +4

    Why is the condenser coil red

    • @subcoolHVAC
      @subcoolHVAC  Před rokem +2

      Good question, It was treated with a corrosion resistant coating when it was new.

  • @RJ-ix4co
    @RJ-ix4co Před 2 měsíci

    Can’t believe you didn’t check those filter dryers. I bet they are getting clogged up from someone using some mo99 or 438a. Just from looking at those pressure and since someone had cut the high pressure safeties off. Those contractors looked bad too.

    • @subcoolHVAC
      @subcoolHVAC  Před 2 měsíci

      The Fixed metering manifold was clogging, A/C Renew added and ended up correcting the restrictions . Condensing coil is also fouled, and that design has a tendency to recirculate condenser discharge air into condenser. It’s shoved in the corner of a building. HP switches also replaced…. Only R22 used… thanks for watching!

  • @JP-sd2cw
    @JP-sd2cw Před rokem +2

    Can you explain the back feeding terminology? your missing a phase, yet to ground they are all the same 118v to ground….so in order for you to go to ground still and miss a phase, basically on of those legs is powering a load i guess that feeds back to the other leg ? Im so confused

    • @subcoolHVAC
      @subcoolHVAC  Před rokem +1

      That’s exactly what is going on , the other legs on line side are feeding through loads giving the 118 v reading. Had I disconnected the line wires from the contactor the missing leg would show to ground. Checking across fuses confirmed .

  • @Shutyourjibbs
    @Shutyourjibbs Před rokem +3

    Did you end up having to add some refrigerant? I saw the R-22 jug hooked up to your gauges at the end of the video.

    • @subcoolHVAC
      @subcoolHVAC  Před rokem +3

      Good catch, ckt 1 had a minor hose leak on high side. By the time I caught I wasn’t sure how long it had been loose. Added some vapor but Superheat was within a degree of ckt 2 so I don’t much was lost.