  • I was sent to site to suss out if a VRV-S systems temperature issues were related to install or to the connected BMS.

Komentáře • 13

  • @BrannndonM
    @BrannndonM Před měsícem +4

    It’s a good day when you make an upload!

    • @hvacraustralia
      @hvacraustralia  Před měsícem

      Thanks for the supper mate, always appreciated!

  • @jimmyteesahn
    @jimmyteesahn Před měsícem +1

    Nice vid mate very thorough diagnosis

  • @Matthew-rt2ii
    @Matthew-rt2ii Před měsícem +1

    Good job.

  • @michaelburns5680
    @michaelburns5680 Před měsícem

    Just a couple of suggestions.
    You can just hold down the bottom right hand button, go into group address and release it so the BMS not long recognises it, just remember to put it back when finished.
    Also when you have any central control connected to a Daikin the temp reported to the BMS is the return air (even if you have it set up to sense at wall controller). So it may just be cycling off. Trying changing field setting to 20 6-02 and this will allow it so sense at the wall controller, hopefully does the trick.

    • @hvacraustralia
      @hvacraustralia  Před měsícem

      That makes perfect sense. Remove the group address so the BMS doesn’t recognise it. Wish I’d thought of that while I was there 😂
      Thanks for sharing that, I was unaware. I believe my R/A temp was pretty high in the video. Daikin had attended this site to set up the system originally, so hopefully this was something they set. I’ll try and find their commissioning report and see if they adjusted that setting. Thanks for the information mate.

  • @richardbartlett6932
    @richardbartlett6932 Před měsícem +1

    Can the BMS guys lock it on heat in winter and cool in summer . increase the deadband or lock the range to prevent overshoot.

    • @hvacraustralia
      @hvacraustralia  Před měsícem

      Could do, but I’ve had mixed results setting up a seasons schedule. Works great during the winter and summer but all other times they struggle. I think this solution should work well 🤞