PROFIBUS: PLC to PLC communication between S7-300 and S7-1200

Sdílet
Vložit
  • čas přidán 13. 07. 2024
  • This video is a small demo on how make a PLC to PLC communication on the PROFIBUS.
    Used hardware:
    -S7-315 2DP: 6ES7 315-2AG10-0BX0
    -CP 343-1 Lean: 6GK7 343-1CX10-0XE0
    -S7-1214C: 6ES7 214-1HG40-0XB0
    -CM 1243-5: 6GK7 243-5DX30-0XE0
    Used Software:
    -SIEMENS TIA Portal V15.1
    Link to the project: www.4shared.com/s/fy2GTYyFwea
    If you find this video useful - thank me, or buy me a coffe :=] bmc.link/defacto
    Support: whydonate.com/en/fundraising/...
  • Věda a technologie

Komentáře • 17

  • @rajat3333
    @rajat3333 Před 2 lety

    thanks for uploading. many many thanks

  • @NguyenSon-wc9uq
    @NguyenSon-wc9uq Před 2 lety

    good video

  • @thucvu1450
    @thucvu1450 Před 3 měsíci

    Thank you for your sharing. But I have a question, when I connect 2 PLCs to each other in 'devices & networks' and set up the 'Transfer area' in 'I-slave communication' (Ex: Master address : Q10, Slave address I10, master send data to slave) . To send data from Master (Q10) to Slave (I10), what i need to do is 'move data' to Q10 in main block of Master, and Slave (I10) will receive data automatically, right? I am a beginner, so hope you reply.

    • @automatikavaldymas
      @automatikavaldymas  Před 3 měsíci

      Yes, that’s right. Please take a look at this video: TIA Portal: IM151-7 CPU as I Slave for 1500/1200/400/300
      czcams.com/video/f0ptyfkO1Lo/video.html

    • @thucvu1450
      @thucvu1450 Před 3 měsíci

      @@automatikavaldymas Thank you!

  • @francosotot.
    @francosotot. Před 2 měsíci

    Dear, it is possible to simulate this example of communication.

    • @automatikavaldymas
      @automatikavaldymas  Před 2 měsíci

      Unfortunately it is not possible. But you can simulate TCP connection.

  • @moamenalbattal2538
    @moamenalbattal2538 Před 7 dny

    Thank you very much
    I have 9 CPU's slaves and one CPU master connecting with others by profibus (all of that's are S7-1511-PN with profibus module)
    I put transfer area and using move instructions , is it enough ? or I must use GET/PUT instructions??

    • @automatikavaldymas
      @automatikavaldymas  Před 7 dny +1

      Yes, that is enough. What you need to do is to set operating mode of the communication module - "DP slave", because by default it is "DP master".

    • @moamenalbattal2538
      @moamenalbattal2538 Před 7 dny

      @@automatikavaldymas So Put and Get instructions just for profinet not for profibus , Right?

    • @automatikavaldymas
      @automatikavaldymas  Před 7 dny

      Yes, PUT/GET is for PROFINET.

    • @moamenalbattal2538
      @moamenalbattal2538 Před 7 dny

      @@automatikavaldymas thanks alot🙏🙏🙏

  • @alekseyalexej9665
    @alekseyalexej9665 Před 5 měsíci

    Thank you!
    Tell me please, is it possible to connect to the S7-1200 as a slave not a S-300 CPU, but an IM-153 module (for connecting S7300 DI/DO modules to S7 1200)?

    • @automatikavaldymas
      @automatikavaldymas  Před 5 měsíci +1

      Yes, you should be able to assign ET200M IM153 as slave for S7-1200. At least i can compile the project without errors. I will check if i have this module tomorrow, and if so, i will be able to test irl.

    • @automatikavaldymas
      @automatikavaldymas  Před 5 měsíci +2

      @alekseyalexej9665 unfortunately i have no IM153, so i cannot test it irl, but like i wrote in my previous post, you should be able to assign ET200M IM153 as slave for S7-1200. One thing you should take into account, that it might be so, that not all modules will be compatible with S7-1200 system.

    • @alekseyalexej9665
      @alekseyalexej9665 Před 5 měsíci

      @@automatikavaldymas Thank you, everything worked out already. So far only in hardware configuration S7-1200. The principle is the same as in the case of two PLCs.

    • @jenilpatel7048
      @jenilpatel7048 Před 5 měsíci

      @@automatikavaldymas Interesting. I also tried the same and was able to compile it. When I went forward to place the order, Siemens told us they havn't tested this so they can not gaurantee the system will communicate. Then we went for another PLC