HVAC Service Call: Water Cooled Heat Pump Not Working (Red Light On Wet Switch Flood Detector) Reset

Sdílet
Vložit
  • čas přidán 10. 09. 2024
  • HVAC Service Call: Water Cooled Heat Pump Not Working (Red Light On Wet Switch Flood Detector) How To Reset Wet Switch Flood Detector / McQuay WSHP Water Source Heat Pump Not Cooling / Water Cooled Heat Pump Not Cooling / Air Conditioner Not Blowing Cold Air
    Diversitech WS-1 Wet Switch Flood Detector
    amzn.to/39WbVKf
    Milwaukee Cordless Job Site Light (M12 Rover Light)
    amzn.to/3Sc3kaF
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Veto Pro Pac Tech Pac MC (Compact Tech Pac)
    amzn.to/2ZGttI4
    DIVERSITECH WS-1 WET SWITCH FLOOD DETECTOR
    A solid state control designed to help prevent flooding, damage to carpets, walls, furniture, ceilings, etc. Now has a built-in test and reset button for easier installation. Turns system off when detecting moisture due to condensate or drain leaks. One or two drops will cause Wet Switch to turn off a unit, alerting a serviceman to a moisture problem. A lit LED indicates the Wet Switch is activated and has turned the unit off. Reset simply by drying the absorbent pad with a paper towel and pressing the reset switch. Connects to 24 VAC. More than one unit may be connected to a system. 2 amp contact rating. Simple 5 wire installation.
    Integral Feet
    Integral feet raise the hydrophilic pad and sensor array off the drain pan slightly to prevent nuisance tripping and pan corrosion (metal pans only) from interfering with the sensor array.
    Hydrophilic Pad
    A high tech polymeric fiber quickly draws water into the sensor array using proven capillary technology.
    Multiple Unit Connectivity
    Multiple unit connectivity allows for multiple Wet Switches to be connected in series to adequately cover large drain pan areas.
    Standard 24AC Control
    Power supply to the Wet Switch® is 24VAC, the standard power available on most air handler units. This makes hookup quick and easy. There is no need to run different power to the switch.
    Double Throw Relay
    The double throw relay allows for wiring to interrupt the system and to sound an alarm (by others) when moisture is detected.
    Stainless Steel Sensor Array
    A high tech array of multiple stainless steel sensors detects even a minimal amount of water drawn into the hydrophilic pad.
    Solid State Electronics
    Proven electronics prevent mechanical failure in an aggressive operating environment.
    Push to Reset
    When the Wet Switch® activates, it locks out the call for cool circuit on the air conditioner until the switch is manually reset. This prevents continuing damage in cases where the overflow water drains out of the pan, onto the surrounding ceiling.
    Push to Test
    The push to test button on Wet Switch® gives the installer a quick, easy way to test the wiring on their installation. Giving you the confidence the switch will work as designed, when needed.
    Compact Package
    This technology is packed into a hockey puck sized 3-5/8" diameter by 1-1/4" high cylinder. Furnished complete with 5-conductor 22AWG stranded cable, 6' long.
    Thanks for watching!
    Email: JumperManTech@Gmail.com
    Follow me on Instagram! @JumpRmantech

Komentáře • 43

  • @rickyhertz7250
    @rickyhertz7250 Před 2 lety +3

    That air vent is a Honeywell/Resideo model FV147a
    the plastic tab is to help catch air bubbles .
    Great video and content keep it up .

    • @JumpermanTech
      @JumpermanTech  Před 2 lety +1

      Thank you for that information! You learn something new everyday in this field. Thanks for watching & stay tuned for new videos every week🔧⚡️

  • @Longeno55
    @Longeno55 Před 2 lety +1

    Very interesting. You diagnosed and explained the issues very nicely. Your customers are fortunate to have you!

    • @JumpermanTech
      @JumpermanTech  Před 2 lety +1

      Thank you! I appreciate the feedback & support. Thanks for watching! Stay tuned for new videos every week🔧⚡️

    • @Longeno55
      @Longeno55 Před 2 lety +1

      @@JumpermanTech I definitely will! Thank you!

    • @JumpermanTech
      @JumpermanTech  Před 2 lety

      @@Longeno55 Awesome!

  • @MarioDallaRiva
    @MarioDallaRiva Před 2 lety +2

    I used to service high end enterprise servers and storage.
    One of the universities we had as customers had a raised floor in the data centre that was crazy deep about 5-6ft down!
    The network guys there masterfully bundled the network cables under the floor and to all the end points to perfection it was like art work. Never saw anything so clean and organized. A beautiful site, those guys were major OCD.
    Other sites’ cabling under the raised floor?? Gli spaghetti 🍝

    • @JumpermanTech
      @JumpermanTech  Před 2 lety +1

      Thats awesome. I really appreciate when people put in time to run neat wires. Its def a mix of OCD and also taking pride in what you do. That spaghetti wiring makes things seem so complicated and frustrating 😅 Thanks for sharing and watching. Always appreciate your support 🙏 Stay tuned for new vids! 🔧⚡️

  • @jusrobington
    @jusrobington Před 2 lety

    Had a similar issue with a water sensor on Wednesday. Water dripping from suction line at air handler got caught in pan set off water sensor. Some foam tape and a rag solved that issue.
    Good job, thanks for the videos.

  • @user-ut3uy3oo9u
    @user-ut3uy3oo9u Před 9 měsíci +1

    great video thank you!!! keep em' coming...

    • @JumpermanTech
      @JumpermanTech  Před 9 měsíci

      Thank you very much! You got it🤙⚡️🔧

  • @robertdavenport9095
    @robertdavenport9095 Před 2 lety +1

    Came across this same problem I work a lot with forced air and not so much water cooled. So I appreciate your videos bro keep up the great work.

    • @JumpermanTech
      @JumpermanTech  Před 2 lety +1

      These wet switches are very common in the AC field and it's definitely a common thing for them to trip. The question is why did it trip? They are very reliable I must say. Always appreciate you watching & your support🙏 Stay tuned for new videos every week🔧⚡️

  • @Eddy63
    @Eddy63 Před 2 lety +1

    Very useful and very nicely done ... Thx for what you do , it helps the young people coming into the trade ...

    • @JumpermanTech
      @JumpermanTech  Před 9 měsíci

      Thank you very much! You're very welcome. Glad I can help 🔧⚡️

  • @izzybell11
    @izzybell11 Před 2 lety +2

    Interesting and helpful video. As always well explained. Excellent job.

    • @JumpermanTech
      @JumpermanTech  Před 2 lety

      Thank you! Always appreciate you watching and commenting. Stay tuned for new videos every week🔧⚡️

  • @thesilentonevictor
    @thesilentonevictor Před 2 lety +2

    Good quick fix jmt

    • @JumpermanTech
      @JumpermanTech  Před 2 lety

      Thank you brother! Much appreciated 🙏🔧⚡️

  • @mrbugenhagen3364
    @mrbugenhagen3364 Před rokem

    Vents in general does not like glycol in my experience and they tend to leak after a few years. I would have done exactly as you did and have a manual vent instead.

  • @stephwaylonwells3218
    @stephwaylonwells3218 Před 2 lety +2

    👍

    • @JumpermanTech
      @JumpermanTech  Před 2 lety +1

      Thank you brother!! Much appreciated 🙏👍

  • @MarioDallaRiva
    @MarioDallaRiva Před 2 lety +2

    💪🏼
    Niiice 👏🏼

  • @shine-cg9uf
    @shine-cg9uf Před 2 lety +2

    🇺🇸👍💪❄ nice vid n info 👌👍

    • @JumpermanTech
      @JumpermanTech  Před 2 lety

      Thank you Shine! Appreciate your support 🔧⚡️

  • @Voxus77
    @Voxus77 Před rokem

    Pressure relief valve

  • @renecuevas4128
    @renecuevas4128 Před rokem +1

    That unit looked like a Mc Quay from my viewpoint. When it was installed there was not Servers or wires in that room. Trust me

    • @JumpermanTech
      @JumpermanTech  Před 9 měsíci

      Those are McQuay units! I think you might be right about that. Only makes sense 🔧⚡️

  • @christiankeller3656
    @christiankeller3656 Před 2 lety

    What gloves are you using and how much electrical protection does it give you?

  • @peterking1134
    @peterking1134 Před 2 lety +3

    Terrible installation of heat pump above servers!

    • @rickyhertz7250
      @rickyhertz7250 Před 2 lety +2

      Not well planned out ,equipment change out will be very costly and time consuming.

    • @cableguyi7
      @cableguyi7 Před 2 lety +1

      Could been the heatpump being there in the beginning and then later they added the racks. Which isn't a good design choice as you got expensive gear below.
      just poor planning on the facility to put network gear there.
      the cabling looks like it was added afterwards

    • @JumpermanTech
      @JumpermanTech  Před 2 lety

      I agree Peter! Thanks for watching & stay tuned for new videos every week🔧⚡️

    • @JumpermanTech
      @JumpermanTech  Před 2 lety

      @@rickyhertz7250 I agree. That's for sure! Thanks for watching & commenting 🔧⚡️

    • @JumpermanTech
      @JumpermanTech  Před 2 lety

      @@cableguyi7 I believe that was the case here. Not really the greatest planning. Especially since it's water cooled equipment and there's so many pipes running through that area. Definitely dangerous but it is what it is. Thanks for watching & commenting! Stay tuned for new videos every week🔧⚡️

  • @tinymanthebeast
    @tinymanthebeast Před 2 lety +1

    OMG. In a server room . Yikes 😬.

    • @JumpermanTech
      @JumpermanTech  Před 9 měsíci

      Haha yup. Thats what I was thinking. Thanks for watching! 🔧⚡️

  • @user-dx4bp8rf1l
    @user-dx4bp8rf1l Před 6 měsíci

    How much cost this work bro

  • @richardbaugh8845
    @richardbaugh8845 Před 2 lety

    Honestly man I just take a bunch of paper towels and squeeze the hell out of that wet sensor pad until no more water is on it and it usually resets

  • @I_sivaprakash
    @I_sivaprakash Před 2 lety

    Thats a flow switch. Used to sense running water, but not flow rate.

  • @dylankornegay9794
    @dylankornegay9794 Před rokem +1

    Bruh...Who puts a Unit right above a server room SMH.