Water Source Heat Pump Not Cooling. How to Diagnose. EP67

Sdílet
Vložit
  • čas přidán 15. 08. 2024

Komentáře • 25

  • @deavonsanchez3084
    @deavonsanchez3084 Před 2 lety +4

    Working on a ton of WSHP today for first time. This helps alot. Thank you

  • @hectordaniel30
    @hectordaniel30 Před 3 měsíci +2

    Great video.

  • @LocalcoolingandheatingPB
    @LocalcoolingandheatingPB Před 2 lety +2

    Great video you should do more I like how u showed us everything I’m 1 year into hvac and have ran into this issue now I feel a little better about attempting back flush

  • @hkhsm359
    @hkhsm359 Před 3 lety +2

    Nice job.
    Thanks for sharing your experience.

  • @manuelpineda8159
    @manuelpineda8159 Před 2 lety +2

    Wonderful explanation
    Thanks for your help
    I got the same problem

  • @KT-tm8yu
    @KT-tm8yu Před 2 lety +1

    Great video

  • @tonydelgrego2906
    @tonydelgrego2906 Před 3 lety +1

    Nice professional repair

  • @hectordaniel30
    @hectordaniel30 Před 3 měsíci +1

    You should make more videos

  • @mikemorassi210
    @mikemorassi210 Před 2 lety +2

    Good video, just wished you showed the set up for the backflush.

  • @plainrock-ik3se
    @plainrock-ik3se Před 2 lety +1

    Thanks for the video sir

  • @buffordbaxter3370
    @buffordbaxter3370 Před 3 lety +5

    Nice video! But I would like to add my 2 cents. As I work on geothermal units from close loops to open loops..etc. This system needs PT ports, boiler drains and ball valves. Then you could’ve checked water, temperature and pressure delta t’s and then isolated the system and flushed the system loop. Placing refrigerant gauges on a geothermal is always the last resort. Like I said just my 2 cents. Keep up the good work 👍🏻

    • @NighthawkHVAC
      @NighthawkHVAC  Před 3 lety +2

      This buildings installation is horrible. Only in a perfect world would it be installed correctly. And clients never want to pay to correct it. Thanks for watching.

  • @leebigbee4889
    @leebigbee4889 Před 9 měsíci +1

  • @stephwaylonwells3218
    @stephwaylonwells3218 Před 2 lety +1

    👍

  • @TheIceman101
    @TheIceman101 Před měsícem +1

    Probably a dirty Water Condenser loop or inlet strainer.

  • @robertpeters9438
    @robertpeters9438 Před rokem +1

    What about air locking? Or water circuit flowrate?

  • @rodgermiller8980
    @rodgermiller8980 Před 2 lety +2

    I have a water source HP with some issues,in cooling cycle the hi head pressure switch trips,in heating mode low pressure switch trips,its an old Florida Heatpump that's had problems before,I've also noticed that someone replaced the txv on unit,my suction pressure runs around 50 psi in heating when it starts up,then falls to about 20 psi in about 2 minutes,I thought at first it was overcharged bc in cool head pressure runs up to 375 and shuts off on hi head pressure,but I dont understand why when in heating it drops so low on suction pressure it trips low pressure switch,have any ideas for me?the water flow is sufficient,around 50 to 60 psi is what it runs,could the txv be the problem??

    • @michaellocascio6840
      @michaellocascio6840 Před rokem

      Was the bulb properly insulated?
      High head can come from air in the lines or a blockage with the water. Reverse the flow and/or blow down from the supply side. If not, may need to run some descaled through. But most likely the high head is coming from a clogged water line (or tube/ fin) in the compressor

  • @rorymikael5909
    @rorymikael5909 Před 10 měsíci +1

    If it was locked out, why was the high limit closed>'
    ?

    • @NighthawkHVAC
      @NighthawkHVAC  Před 10 měsíci

      When the high pressure switch trips open 3 times it energies a lockout relay which shuts down the unit. Once the pressures equalize the high pressure switch resets to closed.

  • @renecuevas4128
    @renecuevas4128 Před 2 lety

    Every body here want to see the back flush u didn't show. It was no need to remove the strainer just by doing a back flush would it be ok

  • @dentonterry4540
    @dentonterry4540 Před rokem

    Ground source

  • @hatmakerluck4705
    @hatmakerluck4705 Před 2 lety +1

    Hey man I have a couple questions on a water source heat pump I’m working on. Did not know if I could contact t you.

  • @mountainmgtow5421
    @mountainmgtow5421 Před 6 měsíci +1

    Horrible technician XD